Proposed Tech Spec 3.3.3 Actions,Revised to Make Actions for Various ECCS Actuation Instrumentation Consistent W/ Purpose & Logic of Instrument Involved
ML20029C366
Person / Time
Site: Perry 
Issue date: 03/19/1991
From:
CENTERIOR ENERGY
To:
Shared Package
ML20029C365 List:
References
NUDOCS 9103270224
Download: ML20029C366 (3)


Text

-

~

TABLE 3.3.3-1 s

EMERGENCY CORE COOLING S'rSTEM ACTUATION INSTRUMENTATION Xtho <

a-MINIMUM CPERABLE APPLICABLE Me CHANNELS PER OPERATIONAL i

Oc TRIP FUNCTION (*} CONDITIONS ACTION

$d.

TRIP FUNCTION ou ES" A.

DIVISION 1 TRIP SYSTEM om g

1.

'RHR-A (LPCI MODE) AND LPCS SYSTEM ow a.

Reactor Vessel Water Level - Low, Level 1 2

1,2,3,4*,5*

30 I M,5 b.

Drywell Pressure - High 2

1,2,3 30 fig j.

c.

LPCS Pump Discharge Flow - Low (Bypass) 1 1,. 2, 3, 4*, 5*

39 t

d.

Reactor Vessel Pressure -- Low (LPCS Infection 1

1,2,3 31 Valve Permissive) 4*, 5*

32 e.

Reactor Vessel Pressure - Low (LPCI Injection 1

1,2,3 31 3

Valve Permissive) 4 *, 5*

32 r

i

{

f.

LPCI Pump A Start Time Delay Relay 1

1, 2, 3, 4*, 5*

31 g.

LPCI Pump A Olscharge Flow - Low (Bypass) 1 1, 2. 3, 4*

5*

39 i

T h.

Manual Initi nion 1

1, 2, 3, 4 *, 5*

33 f

AUTOMATIC DEPRESSURIZATION SYSTEM TRIP SYSTEM "A"#

f 2.

L ID) a.

Reactor Vessel Water Level - Low, tevel 1 2

1, 2, 3 3D l

b.

Manual Inhibia I

1, 2, 3 L33 3 0 c.

ADS Timer 1

1,2,3 31 -

l l.

d.

Reactor. Vessel Water Level - Low, Level 3 (Pers:issive) 1 1,2,3 31

[

LPCS Pump Discharge Pressure - High (Permissive) 2 1,2,3 31

]

f.

LPCI Pump A Discharge Pressure - High (Permissive) 2 1,2,3 31 I

j e.

g.

Manual. Initiation 2

I, 2, 3 33 l

i

,pg

-~=

D"N5 m.

C Ee m

1

-Y"

--P P'-

g-w-

r wi-c 9

a w

,,c

-y,

- rp -

TA8LE 3.3.3-1 (Continued) h' EMERGENCY CORE COOLING SYSTEM ACTUATION INSTRUMENTATION MINIMUM OPERABLE APPLICABLE CHANNELS PER OPERATIONAL TRIP FUNCTION (*)

CONDITIONS ACTION c-

'{

TRIP FUNCTION 4

B.

DIVISION 2 TRIP SYSTEM 1.

RHR B AND C (LPCI M00E)

ID}

a.

Reactor Vessel Water Level - Low, Level 1 2

1, 2, 3, 4*, 5*

30 ID}

b.

Drywell Pressure - High 2

1,2,3 30 c.

Reactor Vessel Pressure Low (LPCI Injection 1

1,2,3 31 Valve Permissive) 4*, 5*

32 d.

LPCI Pump B Start Time Delay Relay 1

1, 2, 3, 4*, 5*

31 e.

LPCI Pump Discharge Flow - Low (Bypass) 1/ pump 1, 2, 3, 4*, 5*

39 f.

Manual Initiation 1

1, 2, 3, 4 *, 5

  • 33 Y

AUTOMATIC DEPRESSURIZATION SYSTEM TRIP SYSTEM "B"#

2.

~

I) a.

Reactor Vesse t Water Level - Low, Level 1 2

1, 2, 3 30 t

b.

Manual Inhibit 1

1,2,3 CaEB_3 C3 c.

. ADS liner 1

1,2,3 JI _

s1 Reactor Vessel Water Level - Low, Level 3 (Permissive) 1 1,2,3 31 LPCI Pump 8 and C Discharge Pressure - High (Permissive) 2 1,2,3 31 e.

f.

Manual Initiation 2

1, 2, 3 33 i

4A~

mOe o ;? 4 35E a~

5 c-

.m W

r W

y e

.w

-c

PY-CEl/NRR-1316L Page 3 of 3 TABLE 3.3.3 1 (Continued)

EMERGENCY CORE COOLING SYSTEM ACTUATION INSTRUMENTATION ACTION ACTION 30 -

With the number of OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip Function requirement:

ADS trip system 8.

With one channel inoperable, place the inoperable Channel or ECCS in the tripped condition within one hour or declare the l

ssociated"han one channel inoperable, declare the associated W r inoperable, fth more t b.

jer 4eo inoperable.

ACTION 31 -

With tre number of OPERABLE channels less than required by the Minimun OPERABLE Channels per Trip Function requirement, declare the associated ADS trip system or ECCS inoperable.

ACTION 32 With the number of OPERABLE channels less than the Minimum CPERABLE Channels per Trip Function requirement, place the inoperable channel in the tripped condition within one hour.

ACTION 33 -

With the number of OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip Function requirement, restore the inoperable channel to O RPBLE status within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or declare the associated AD3F:9dp__fCCS inoperable.

With the number of OPERABNS64 Ness than required by the ACTION 34 -

Minimum OPERABLE Channels per Trip Function requirement:

For one trip system, place that trip system in the tripped a.

condition within one hour or declare the HPCS system inoperablel b.

For both trip systems, declare the HPCS system inoperable.

i ACTION 35 -

With the number of OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip Function requirement, place at least one inoperable channel in the tripped condition within one hour, or ali suppression pool,gn the HPCS system to take suction from the or declere the HPCS system inoperable.

ACTION 36 With the number of OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip Function requirement, place at least one inoperable channel in the tripped condition within one hour or declare the HPCS system inoperable.

1 ACTION 37 -

With the number of OPERABLE channals less than the Total Number of Channels, declare the associated emergency diesel gensrator inoperable and take the ACTION required by Specification 3.8.1.1 or 3.8.1.2, as appropriate.

ACTION 38 -

With the number of OPERABLE channels less than the Total Number of Channels, place the inoperable channel in the tripped condi-tion within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />; operation may then continue until perform-l ince of the next required CHANNEL FUNCTIONAL TEST.

ACTION 39 With the number of OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip Function requirement, place the inoperable channel in the tripped condition within one hour.

Restore the inoperable channel to OPERABLE ctatus within 7 days or declare the associated system inoperable.

I PERRY - UNIT 1 3/4 3-31 Amendment No. 30

)