Final Deficiency Rept Re Thermowells in Diesel Generator Lube Oil Sys Mfg by Cooper Energy Not Procured to ASME Code. Initially Reported on 820316.Deficiency Determined Not Reportable Per 10CFR50.55(e)
ML20028A481
Person / Time
Site: Palo Verde  
Issue date: 11/04/1982
From: Van Brunt E
ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR
To: Sternberg D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
10CFR-050.55E, 10CFR-50.55E, ANPP-22203-GHD, NUDOCS 8211220218
Download: ML20028A481 (3)


Text

._

Docket Nos. 50-528/529/530 1

50.55(e) Report Arizona Public Service Company P o. BOX 21666 + PHOENIX ARIZONA 85036 November 4, 1982 ANPP-22203-GHD/BSK U. S. Nuclear Regulatory Commission J

Region V Creekside Oaks Office Park 1450 Maria Lane - Suite 210 Walnut Creek, California 94596-5368 Attention:

Mr. D. M. Sternberg, Chief Reactor Projects Branch 1 Subj ect:

Final Report - DER 82-9 A 50.55(e) Report Relating to Thermowells in Diesel Generator Lube Oil Systems by Cooper Energy Were Not Procured to ASME Code File:

82-019-026 D.4.33.2

Reference:

(A) Telephone Conversation Between T. Bishop and G. Duckworth on March 16, 1982 (B) ANPP-20715, dated April 16, 1982 (Interim Report)

(C) ANPP-21183, dated June 15, 1982 (Time Extension)

(D) ANPP-21834, dated September 15, 1982 (Time Extension)

Dear Sir:

1 Attached, is our final written report of the deficiency referenced above, which has been determined to be Not Reportable under the requirements of 10CFR50.55(e).

Very truly yours, UcLL m L(

E. E. Van Brunt, Jr.

APS Vice President Nuclear Projects Management ANPP Project Director EEVBJr/GHD:db Attachment cc: See Attached Page 2

, rm

.j v

8211220218 821104 b,

PDR ADOCK 05000528 S

PDR

e a

U. S. Nuclear Regulatory Commission ANPP-22203-GHD/BSK Attention:

Mr. D. M. Sternberg, Chief November 4, 1982 l

cc: Richard DeYoung, Director Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, D. C. 20555 T. G. Woods, Jr.

J. A. Roedel D. B. Fasnacht G. C. Andognini A. C. Rogers B. S.- Kaplan W. E. Ide J. Vorees J. A. Brand A. C. Gehr W. J. Stubblefield W. G. Bingham R. L. Patterson R. W. Welcher R. M. Grant D. R. Itawkinson L. E. Vorderbrueggen G. A. Fiorelli Lynne Bernabel, Esq.

Ilarmon & Weiss i

1725 "I" Street, NW Suite 506 i

Washington, D. C. 20006 R. L. Greenfield Assistant Attorney General Bataan Memorial Building Santa Fe, New Mexico 87503 k_ _

e.

e FINAL REPORT - DER 82-9 DEFICIENCY EVALUATION 50.55(e)

ARIZONA PUBLIC SERVICE COMPANY (APS)

PVNGS UNITS 1, 2 & 3 I.

DESCRIPTION OF DEFICIENCY Specification 13-!!M-018 requires certain piping assemblies for the diesel generator system to be ASME Section III, Class 3.

Contrary to this, stainless steel thermowells for RTD's and thermometers are not traceable to ASME Section III, Class 3 material and are installed in Class 3 piping.

II.

ANALYSIS OF SAFETY IMPLICATIONS The piping systems are low pressure (less than 100 psig) and low temperatures (less than 200F). The thermowells serve only as pressure retaining parts.

Should this condition have remained undetected and/or unrepaired, it would not represent a safety significant condition as standard thermowells are rated in excess of 6,000 psig at 200F.

III.

CORRECTIVE ACTION Nonconformance Reports MG-1190, 1191, and 1192 (Units 1, 2 and 3 respectively) will be dispositioned to replace all the thermowells with thermowells traceable to the ASME Section III Code.