Text

_. -.

OPERATING DATA REPORT DOCKET NO.

sn_ tn?

DATE 11/2/82 COMPLETED BY

n. naanrt TELEPHONE tonn Yos-6486 OPERATING STATUS
1. Unit Name:

Crystal River Unit #3 Notes

2. Reporting Period:

10/1/82 - 10/31/82 3, Licensed Thermal Power (MWt):

2544 890

4. Nameplate Rating (Gross MWe):
5. Design Electrical Rating (Net MWe):

825 845

6. Maximum Dependable Capacity (Gross MWe):

806

7. Maximum Dependable Capacity (Net MWe):
8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report.Give Reasons:

I N/A

9. Power Level To Which Restricted.lf Any (Net MWe):

7475 W tharmal

10. Reasons For Restrictions. lf Any:

Pumo Power Monitors in bvoass.

This Month Yr. to Date Cumulative

!!. Hours in Reporting Period 745 7296 49416

12. Number Of Hours Reactor Was Critical 381.5 5901 31350.4
13. Reactor Reserve Shutdown Hours 0.0 71.1 1280.3
14. Hours Generator On.Line 368.8 5807.4 30619.6
15. Unit Reserve Shutdown Hours 0

0 0

16. Gross Thermal Energy Generated (MWH) 893237 13150047 68516988
17. Gross Electri:al Energy Generated (MWH) 30534_4 ___.

4470927 23270518

18. Net Electrical Energy Generated (MWH) 291056 4251746

.22081044

19. Unit Service Factor 49.5%

79.6%

62.0%

20. Unit Availability Factor 49.5%

79.6%

62.0%

21. Unit Capacity Factor (Using MDC Net)
48. 5_%

72.3%

56.9%

41.4%

70.6%

54.2%

22. Unit Capacity Factor (Using DER Net)
23. Unit Forced Outage Rate 50.5%

20.4%

25.5%

24. Shutdowns Scheduled Over Next 6 Months (Type. Date, and Duration of Each t:

Refuel Outane beeinnine 3/19/82.

25. If Shut Down At End Of Report Period. Estimated Date of Startup:

N /A

26. Units in Test Status (Prior to Commercial Operation):

Forecast Achiesed INITIA L CRITICA Lily I/14 /77 INITIAL ELECTRICITY 1/30/77 COMMERCIAL OPER ATION 3/13/77 (4/77) 8211160303 821112 PDR ADOCK 05000302 R

PDR

AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.

50-302 UNIT FLCRP-3 DATE 11/2/82 COMPLETED BY D. Bogart TELEPHONE (904) 795-6486 3

MONTH October 1982 DAY AVERAGE DAILY POWER LEVEL DAY '

  • AVERAGE DAILY P6WER LEVEL (MWe Net)

(MWe Net) 810 17 0

2 767 gg 0

770 0

3 39 810 4

20 5

804 21 0

815 22 6

807 0

7 23 8

24 0

9 813 25 0

807 0

10 26 794 g,

27 0

12 801 28 0

813 0

13 29 512 14 30 172 is 0

33 791 0

16 INSTRUCTIONS On this 'ormat, list the average daily unit power leselin MWe Net for each day in the reporting month. Compute io the nearcst whole megawatt.

(o 17 7 )

DOCKET NO.

50-302 UNIT SHUTDOWNS AND POWER REDUCTIONS UNIT NAME Ff N 'l DATE 11/5/82 COMPLETED BY M Li-f'ul va r REPORT MONTil 10/82 TELEPHONE (9041 795-6486 n.

E c

.5 ?

3

$.U Licensee h

%'s Cause & Corrective No.

D.ite g

3g g

jg5 Event

~g Action to gO Present Recurrence

$E 5

Report *r in U 5 5 =g H

o u

C 2-28 821014 F

376.2 A

1 N/A WB HTEXCH RC drain tank cooler failed re-quiring SW cooling to the tank to be secured. Pressurizer relief valves leaked into the drain tank, eventu-ally causing the RC drain tank to relieve to the reactor building.

The unit was shutdown to correct the cooler leak and replace the pressurizer valves.

i I

2 3

4 F: Forced Reason:

Method:

Exhibit G. Instructions S: Scheduled A Equipment Failure (Explain) 1-Manual for Preparation of Data B-Maintenance of Test 2-Manual Scram.

Entry St.ects for Licensee C-Refueling 3-Automatic Scram.

Event Reporn (LER) File (NUREG-D Regulatory Restriction 4-Other (Explain) 0161)

E-Operator Training & License Examination F-Administrative 5

G-Operational Error (Explain)

Exhibit I.Same Source 19/77)

Il Other (Explain)

~

MONTHLY OPERATIONAL SlRDIARY STATEMENT DOCKET NO.

sn-an?

UNIT F1.CRP-1 DATE 11/s/R2 COMPLETED BY M_w. culver TELEPHONE (9041 795-6486 MONTH oc c ab'r 10A7

SUMMARY

STATEMENT:

The unit experienced one shutddwn-during the mod'h.

t

.