ML20024D756

From kanterella
Jump to navigation Jump to search
First Interim Deficiency Rept Re Violation of Spacing Requirements for Grouted Anchors.Initially Reported on 830701.Possibility of Using Anchors in Present Condition Being Evaluated.Next Rept Expected by 831202
ML20024D756
Person / Time
Site: Bellefonte  Tennessee Valley Authority icon.png
Issue date: 07/28/1983
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
10CFR-050.55E, 10CFR-50.55E, NUDOCS 8308080119
Download: ML20024D756 (2)


Text

~

s

~

TENNESSEE VALLEY AUTHORITY SNgg CH ATTANOOGA. TENNESSEE 374ot

' ' i [4 [jO[/*.

400 Chestnut Street Tower II

'L OR<f/p dl/C y NO.* / g July 28, 1983 BLRD-50-438/83-44 BLRD-50-439/83-37 U.S. Nuclear Regulatory Coinnission Region II Attn:

Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - VIOLATION OF SPACING REQUIREMENTS FOR GROUTED ANCHORS - BLRD-50-438/83-44, BLRD-50-439/83 - FIRST INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector Linda Watson on July 1,1983 in accordance with 10 CFR 50.55(e) as NCR BLN 2408. Enclosed is our first interim report. We expect to submit our next report by December 2, 1983 If you have any questions, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY D$ %

hL.M. Mills, Manager

/

Nuclear Licensing Enclosure cc:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Records Center (Enclosure)

Institute of Nuclear Power Operations 1100 Circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 yy f > W,'

l 9

8308080119 830728

'983-TVA SOTH ANNIVERSARY 27 PDR ADOCK 05000438 An Equal Opportunity Employer S

PDR

- - ~ ~.

ENCLOSURE BELLEFONTE NUOLEAR PLANT UNITS 1 AND 2 VIOLATION OF SPACING REQUIREMENTS FOR GROUTED ANCHORS BLRD-50-438/83-42, BLRD-50-439/83-37

.NCR 2408 10 CFR 50.55(e)

FIRST INTERIM REPORT i

Description of Deficiency General Specification G-32 Appendix D (implemented onsite by BNP-QCP-2.8) requires that in large holes or chipped out areas where grouted anchors are used, the chipped out area shall extend at least three nominal bolt diameters for individual and six nominal bolt diameters for multiple anchors beyond the end of the anchor. These chipped areas should then be refilled with concrete for support. Seismic pipe supports have been installed with anchor bolts such that the chipped areas have possibly been chipped only to the bottom of the anchor.

Interim Progress TVA's Division of Engineering Design (EN DES) is evaluating the possibility of using the anchors in their present condition. We will provide more information in our next report.