05000373/LER-1982-151-03, /03L-0:on 821117,emergency Makeup Control Room Ventilation Fan B Failed to Start.Caused by Bent Outlet Damper Shaft to B Train & Broken Bearing Housing Cap. Linkage Misaligned When Installed Initially.Damper Repaired

From kanterella
(Redirected from ML20023B265)
Jump to navigation Jump to search
/03L-0:on 821117,emergency Makeup Control Room Ventilation Fan B Failed to Start.Caused by Bent Outlet Damper Shaft to B Train & Broken Bearing Housing Cap. Linkage Misaligned When Installed Initially.Damper Repaired
ML20023B265
Person / Time
Site: LaSalle Constellation icon.png
Issue date: 12/15/1982
From: Wittenburg K
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20023B264 List:
References
LER-82-151-03L, LER-82-151-3L, NUDOCS 8212270180
Download: ML20023B265 (2)


LER-1982-151, /03L-0:on 821117,emergency Makeup Control Room Ventilation Fan B Failed to Start.Caused by Bent Outlet Damper Shaft to B Train & Broken Bearing Housing Cap. Linkage Misaligned When Installed Initially.Damper Repaired
Event date:
Report date:
3731982151R03 - NRC Website

text

'

LICENSEE EVENT REPORT e@

(PLEASE PRINT CR TYPE ALL REQUIRED INFORMATION)

CONTROL BLOCK: l l

l l

}

l l

Ll LI S I C l l l@l 0 l o l 10 lo lo lo lo I l ol ol@l 4 I 1 l 0 l 0 (0 !@l l

]g 10 l11 l II 7

8 'S tiCENSEE CCOE 14 15 LICENSE NUMSER 26 26 LsCENSE TYPE JG

$7 CAT M CON'T "PCylL @lSt0] 5 l 0 ] 0 l0 l 31713 @ll l 111171812 @l11211 15 l 8 I 2 l@

4, loIil DOCKET NLMBER 68 69 EVENT DATE 74 75 REPORT DATE 80 l

8 60 EVENT DESCRIPTION AND PROSABLE CONSEQUENCES h Io l2l l On 11/17/82 with the Unit is Startup Mode, the "B" Emergency Makeup Control Room

[

ventilation fan failed to start during the performance of LOS-VC-M1.

The "A" Emer- [

g]

go,,,l gency ventilation fan was started per Tech. Spec. 3.7.2 in conjunction with the

[

g o,3, normal VC HVAC System. The health a'nd safety of plant personnel was maintained at 1

aH d es.

l lo (6 l l I

l o 17 l l I

l o is l l 6

o E

Su C E COMPCNENT CCDE Stacodt 5e E

t.o_LJ l S 1 c l@ l Alh l El@ l X lX ! X lX lX IX lh Wh y h

,7 8

9 10 11 12 IJ 18 39 20 SEQUENT 1At OCCUR RENCE REPORT REvtssom l

LER/Ro EVENT YE AR R EPORT No.

CooE WPE No.

h,R,Eg l218l 2l l-l l1l5lll y

l0 l3 l y

b W

22 23 24 26 27 25 29 30 31 32 N

C" C oNP T

ME HOUR $

$8 i FCR bus.

SU L MA F

JRER j

gl clg la Cl@ l zl@

lcl010l3l y@

y h lAl@

[z l 9 l 9 l 9 '

22 24 as si ao 4

42 as 44 4:

Il CAUSE DESCRIPTICN ANC CCRRECTIVE ACTICNS @

ligoll Investigation showed that the outlet damper shaft of the "B" train was bent and the t

,,,,,g earing housing cap was broken. When the linkage was initially installed it appears to b

,,,,,jhave been misaligned. The damper was removed to effect repairs and temporary duct work

! Ii 13 I I installed until the damper was reinstalled.

"B" train passed LOS-VC-M1 after being i3i4i j repaired.

ec

! 7 a sAh

% POWER o?NER STATUS Cl3 RV DAScovERY DESC*4tP11oN NA l

lBl@l LOS-VC-M1 l

l115 l l B l@ l0 l0 l0 l@l S

12 is

.4 4s 46 ao 8,q7,y,7y co'drgy7 7

AuouMTon ACTIVITY @ l tocATion o, REuise @

cEtEAsEo en af TEASE I

NA l

Na l

li Is l l z l @ l Zl@#Es

.ERsew EttoCs cEscRi> Tion @

NuMsER Ts er i

I t 171 101 O ! O @W@l NA

' PERseNNEL iN;u7iEs otsemPricN@ NA Nuwsta l t la j l 0 l 0 l 0 l@l

~

~

^

e9 n

12 8212270100 821215

$8,0'C"0^",^G8'0'Acitiry@

PDR ADOCK 05000373 3e,r 0y S

PDR l 1 l 9 l l z lhl NA 3

7 8 9 10 NRC usE oNLY e'ESemierioN@

12lcllNfhl issut 1

NA l

ll 1lllllll [f I

68 69 7

3 3 to NAVE OF PAES ARER PHONE:

d I.

LER NUMBER: '82-151/03L-0 II.

LASALLE COUNTY STATION: Unit 1 III. DOCKET NUMBER: 050-373 IV.

EVENT DESCRIPTION

On 11/17/82 with the unit in Startup Mode, the "B Emergency Makeup Control Room Ventilation Fan failed to start during the performance of LOS-VC-M1.

Technical Specification 3.7.2 prevents the unit from going to the run condition.

V.

PROBABLE CONSEQUENCES OF THE OCCURRENCE:

The "A" Emergency Makeup Control Room Ventilation Fan was started per T.S. 3.7.2 in the pressurization mode, in conjunction with the normal VC HVAC system. The health and safety of plant personnel was main-tained at all times.

VI.

CAUSE

The outlet damper of the "B" train failed to open.

Investigation found that the damper shaf t was bent and the bearing housing cap was broken.

This damage was apparently caused by a misalignment on the linkage when it was initially installed.

4

VII. CORRECTIVE ACTION

i j

Work Request L19787 was written and the damper was removed to complete j

the repairs. Temporary duct work was installed and the damper position i

limit switches were jumpered to allow the train to run if needed.

LOS-VC-M1 was performed satisfactorily to prove the operability of the "B" Emergency Makeup Ventilation System after the damper was reinstalled.

This is believed to be an isolated incident.