05000373/LER-1982-152-03, /03L-0:on 821115,during Performance of LIS-RI-01, Differential Pressure Indicating Switch 1E31-N007A Setpoint Found Out of Tolerance in Nonconservative Direction Per Tech Spec 3.3.2.Cause Unknown.Switch Recalibr

From kanterella
(Redirected from ML20023B211)
Jump to navigation Jump to search
/03L-0:on 821115,during Performance of LIS-RI-01, Differential Pressure Indicating Switch 1E31-N007A Setpoint Found Out of Tolerance in Nonconservative Direction Per Tech Spec 3.3.2.Cause Unknown.Switch Recalibr
ML20023B211
Person / Time
Site: LaSalle 
Issue date: 12/13/1982
From: Houston R
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20023B200 List:
References
LER-82-152-03L, LER-82-152-3L, NUDOCS 8212270148
Download: ML20023B211 (2)


LER-1982-152, /03L-0:on 821115,during Performance of LIS-RI-01, Differential Pressure Indicating Switch 1E31-N007A Setpoint Found Out of Tolerance in Nonconservative Direction Per Tech Spec 3.3.2.Cause Unknown.Switch Recalibr
Event date:
Report date:
3731982152R03 - NRC Website

text

I LICENSEE EVENT REPORT l

.Q CONTROL PLOCK: l l

l l

l l

I (TLEASE PRINT OR TYPE ALL REQUIRED INFORMAT17NI t o li l l I I t I L l S Ic 11 l@l 010l -l O i 01 o l 010 ! - l 0 ! 0 l@l 4 Il t o l0 10!@l l

Ig 7

8 9 LaCENSEE CCCE to 15 LICENSE N6M8ER 25 26 LaCENSE TYPE 40 53 CAT 58 CON'T

,",','Cy l L @l 01 51 0l 01 01 31 7 ! 3 Ql 1 l 11 115 l S 12 @l ll 21 1 ! 3 l 8 12 l@

lois) 8 to 61 DOCKET NwM8ER 64 69 EVENT CATE 74 7S REPORT DATE 40 EVENT DESCRIPTION AND PRC8 ABLE CONSEQUENCES h io i:; l On November 15, 1982 at 0200 hours0.00231 days <br />0.0556 hours <br />3.306878e-4 weeks <br />7.61e-5 months <br />, during the performance of LIS-RI-01, DPIS lE31-g N007A setpoint was found out of tolerance in the non-conservative direction per g

90,3; g l o 6 41 i Technical Specification 3.3.2.

DPIS lE31-N007B and lE31-N013B setpoints were found g

within tolerance. These switches would have isolated the Inboard Steam Isolation g

io Isl l Valve 1E51-F063 and the Steam Line Warm-up Valve lE51-F076 had an isolation been Io j6 [ l lcI7ll required.

g I

}O48l \\

so 7

s9 SYSTEM

CAUSE

CAUSE Ccamp.

vaty E C00E C00E 3U8COCE CCMPCNENT CCOE SueCODE SuecC3E loisi I c I E l@ Ld@ l x i@ I t l x i s IT la lu !@ Ls_1@ Li;J @

7 9

10 11 12 13 18 19 20 SEcVENTIAL CCCURRENCE nePORT REvessom LE4/Ao EVENT VE AR R EPORT NO.

COCC TYPE No.

@,atg i8121 l-l 11!5!21 Ld 10 13 I l' I

'-l Lo1 u

,_ 21 22 23

4
6 27 28 29 30 31 22 K N C ON ON P 7

YE HOVRS 22 58 i PCR UE.

PP MAN F MER lEl@]Zl@

l Zl@

lZ l@

l0l0l0lUl lY lg lN lg l A lg lI l2 l0l4 g 33 34 23

6 3

40 at 42 43 44 47 CAUSE DESCRIPTION AND CCRRECTIVE ACTICNS li;a;}

This was an isolated incident. The cause of the setpoint drift is unknown at this

i,i;l time.

The differential pressure indicating switch was manufactured by ITT Barton, J

Model 288. DPIS lE31-N007A was recalibrated on November 15, 1982 and declared i

, ;;; g
, ;3gl operable.

g I

it 4 41 l THER status @ 5'EcOSav'

  1. '*E sPCwER onscoveny oEsCntrTtoN sTA NA l

lBl@l LIS-RI-01 l

l1 i 5 l l B l@ l 01 41 2 l@l 45 e

ao

'2 n

a, s, y,,,

cR,,y,

?

  • ELIASED PaELEASE AMOUNT OF ACTivtTV LOCAT10N or RELIASE NA l

l NA l

O 16 l l Z l lZ l@l 7

8 9 10 11 44 45 50 PE85CNNEL E *PCSURES NLwSEA TyeE C ESCpipttCN I

NA l

l t ! ? l l 0 l 0 l 0 l@l Z @l PE A sCNN E L INJURIES NuveER C JSCRIPTICN NA J.

{t IallOl0l0l@]

80 7

8 9 11 12 LOSS os *.m OAvaCE To PactLITY TYPE D E SCRIP 7 ton l9llZ l

NA

.[

1 ao 921'2270148 821213

.untb OEsCaiPTic"@ {' PDR ADOCK 05000373 NRC USE CNLY cu t-eon i

i iiiiiiiiiiiri i: !aiiNrei s

68 69

80. ;

T 8 3 10

~

o on (RIST 157-6761

{

NAVE CP PAE8 APER PMONE:

l -

j s

l I.

LER NUMBER:

82-152/03L-0

)

II.

LASALLE COUNTY STATION: Unit 1 III. DOCKET NUMBER: 050-373 IV.

EVENT DESCRIPTION

On November 15, 1982 at 0200 hours0.00231 days <br />0.0556 hours <br />3.306878e-4 weeks <br />7.61e-5 months <br />, during the performance of LIS-RI-01, Steam Line High Flow RCIC Isolation Calibration and Functional Test, DPIS lE31-N007A setpoint was found out of tolerance in the non-conserva-tive direction per Technical Specification 3.3.2.

V.

PROBABLE CONSEQUENCES OF THE 0':CURRENCE:

At the time of the occurrence the reactor was in the Run mode producing 1575 MWT, 460 MWE.

DPIS lE31-N007B and 1E31-N013B setpoints were found within tolerance. These switchas would have isolated the Inboard Steam Isolation Valve IE51-F063 and the Steam Line Warm-Up Valve lE51-F076 had an isolation been required. Safe plant operation was maintained at all times.

VI.

CAUSE

This was an isolated incident. The cause of the setpoint drift is unknown at this time. The Differential Pressure Indicating Switch was manufactured by ITT Barton, Model 288.

VII. CORRECTIVB ACTION:

DPIS lE31-N007A was recalibrated on November 15, 1982 and declared operable.

Prepared by:

R. W. Houston