ML20011B044
| ML20011B044 | |
| Person / Time | |
|---|---|
| Site: | Browns Ferry |
| Issue date: | 10/23/1981 |
| From: | Ippolito T Office of Nuclear Reactor Regulation |
| To: | Parris H TENNESSEE VALLEY AUTHORITY |
| References | |
| RTR-NUREG-0737, RTR-NUREG-737, TASK-2.K.3.27, TASK-TM NUDOCS 8111040050 | |
| Download: ML20011B044 (3) | |
Text
y e
b October 23, 1981 Docket No. 50-259 50-260 50-296 Mr. Hugh G. Parris O-[.T TA
'f fj h[~
U\\
Manager of Power f
Tennessee Valley Authority al 500 A Chestnut Street, Tower II GCT2 719815. -
Chattanooga, Tennessee 37401 u3 -,-
CO/W44$$3CH
/
Dear Mr. Parris:
BROWNS FERRY PLANTS, UNITS 1, 2. AND 3
% Fi NUREG-0737 ACTICP ITEM II.K.3.27 (C0fNON REFERENCE LE RE:
Reference:
(a) Letter from L. M. Mills to H. R. Denton dated April 9,1981 We have performed our post-implementation review of your modification (reference (a)) for the subject Action Item. The criteria used in our review were:
1.
All level instruments should be referenced to the same point.
2.
Licensees should comit to modify docununtation, including operating procedures and technical specifications, as required, to reflect the new reference level.
3.
Licensees should comi t to provide appropriate training for plant operators.
Our review did not encompass a human factors evaluation of your water level instrumentation (e.g. placement, legibility, etc.). That evaluation will be perfomed as part of the detailed control r som review (Action Item I.D.1) that you will be expected to conduct per NUREG-0737 and NUREG-0700.
We find that, while your modification is an acceptable interim measure with respect to the July 1, 1981 implementation date, it does not completely resolve the concern upon which this Action Item is based. The rationale of Action Item II.K.3.27 is that the operator should not have to perfom mental interpolations to understand what a reading on one water level indicator means relative to a reading on another water level indicator.
Your modification makes infomation readily available that the operator needs to perfom a mental interpolation, but it does not eliminate the need for perfoming the interpolation.
omcE t 8111040050 811023 suanAuch PDR ADOCK 05000259 P
PDR DATEy OFFICIAL RECORD COPY usom mi-mm Nac ronu sia oo-803 nacu c24a
1 i
.. I Therefore, we request that you submit within 90 days of this letter:
1.
Your comitmant to install a modification that provides a comon reference le wl; 2.
a description of that modification, including proposed implementation schedules, and; 3.
your commitraent to meet acceptance criteria 2 and 3, above.
Please contact your project manager if you have questions on this matter.
Sincerely, e
l Thomas A. Ippolito, Chief Operating Reactors Branch #2 Division of Licensing cc: See next page DISTRI3UTION:
Docket File NRC PDR Local PDR ORB #2 Rdg D. Eisenhut OELD I&E(3)
D. Clark S. Norris NISC TERA ACRS(10)
Gray J. Heltemes, AE0D 1
i
)
'l J
DRB ORB #
ORABF ORB #2, Q'
OR i
omce pg.g(2d.........
g
..g.h'V 'i' 'i
'0'%'M'i '
' "b'C'l'i"
T'1'p 1 i 6' d
sua u u q )f. M /81 "
" "l 0/30/81""" t0/"(*/8t" " * "10/f3/8t' '
... "104.).78 om>
Nac ronu sia no-soi nacu ona OFFICIAL RECORD COPY usago: nsi.-333-*m
Mr. Hugh G. Parris cc:
H. S. Sanger, Jr., Esquire General Counsel Tennessee Valley Authority'.*
400 Commerce Avenue E llB 33 C
~
Knoxville, Tennessee 37902 Mr. Ron Rogers Tennessee. Valley Authority
- 400 Chestnut Street, Tower II Chattanooga, Tennessee 37401 Mr. H. N. Culver 249A HBD 400 Commerce Avenue Tennessee alley Authority Knoxville, Tennessee 37902 Robert F. Sullivan U. S. Nuclear Regulatory Commission Route 2, Box 311 Athens, Alabama 35611 Athens Public Library South and Forrest Athens, Alabama 35611 Mr. John F. Cox Tennessee Valley Authority W9-D 207C 400 Commerce Avenue Knoxville, Tennessee 37902 l
Mr. Herbert Abercrombie Tennessee Valley Authority P. C. Box 2000 i
l Decatur, Alabama 35602 l
i l
.