Forwards LER 81-073/03L-0
Date released: 01/25/2020 Download: ML20011A608


LER 81-073/03L-0:on 810920,24 & 1007,diesel Generator 4 Did Not Attain Rated Speed in Required Time When Started.Caused by Intermittent Electrical Connection on Diesel Right Starting Air Bank Dc Solenoid Valve.Connection Repaired
ML20011A612
Person / Time
Site: Brunswick 
Issue date: 10/19/1981
From: Pastva M
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20011A612 (2)
Forwards LER 81-073/03L-0
ML20011A606
Person / Time
Site: Brunswick 
Issue date: 10/19/1981
From: Dietz C
CAROLINA POWER & LIGHT CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML20011A606 (1)