'-'?yaair.xms.;a wggy m

7

- (I P0pE R fhT *h UP "D

I U.

j J C BRONS RESIDENT MANAGER N

[ g l4'\\

..,1Og,g-2ip j

PO BOX 215 suCHANAN NY 10s11 O

mg

- Aug u_,

4-034e725272003 09/29/81 ICS IPMMTZZ CSP PHAB 2 9147392000 MGM TDMT 8UCMANAN NY 09-29 0137P EST O

e NUCLEAR REGULATORY COMMISSION

[#~2 REGION 1 0FFICE OF INSPECTION AND ENFORCEMENT Q \\ "9 !)N O

  • 52 P'"^

^vE r

~

\\

e j

KING UF PRUSSIA PA 19406

/

O OCT 319815 $

e u.s. eggug;ns

~

s g

THIS IS A CONFIRMATION COPY OF A TELEGRAM ADDRh8 ATIN H NALD C HAYNES DIRECTOR g

O UN *EDNE5vAY 9-23 81 AT 2300 MOURS THE UNIT STARTED TO PROCEED FROM HQT C

Ssuic0*N TO COLD SMuTD0aN AFTER VERIFYING PRIMARY TO SECONDARY g

LEAKAGE EXISTED IN NO. 31 STEAM GENERATOR FOLLOWING AN RCS HYDRO.

AFTER SUdSEQUENT VERIFICATION OF THE CALCULATIONS FOR DETERMINING THE O

SIZE OF THE LEAK, IT aAS IDENTIFIED ON 9-28=81 THAT THE LEAK BREAK g

WAS APPk0XIMATELY 0.77GPH WHICH IS IN EXCESS OF THE TECHNICAL SPECIFICATIONS LIMIT OF 0.3GPM AS IDENTIFIED IN SECTION 3.1.F 8 THE REAC O

  • ^S IN CotD SHUTD0aN AT 1710 HOURS ON 9-24=81. THIS HAS BEEN g

DISCUSS aI1: RESIDENT INSPECTOR T. KENNY ON 9-29-81. THIS TELEGRAM SERVES AS THE PROMPT NOTIFICATION REQUIRED BY TECHINICAL SPECIFIC

('a ATIONS o.9.1.7.C.

g J C BRONS RESIDENT MANAGER POWER AUTHORITY OF THE STATE OF NEa YORK INDIAN 3 NUCLEAR P0aER PLANT Q