Text
.
D DA/RYLAND
[k COOPERAT/VE PO BOX 817 2615 EAST AV SOUTH. LA CROS6E. WISCONSIN S4601 a
(608) 788 4 000 August 6, 1981 In reply, please refer to LAC-7736 DOCKET NO. 50-409 Director of Nuclear Reactor Regulation
(' -((0(/
ATTN:
Mr. Dennis M. Crutchfield, Chief Operating Reactors Branch #5
,#}%
s Division of Operating Reactors
'\\\\
U. S. Nuclear Regulatory Commission W
- (t ggg l 4198F g Washington, D. C.
20555 w n At e ~
- WS5"
SUBJECT:
DAIRYLAND POWER COOPERATIVE c,
LA CROSSE BOILING WATER REACTOR (LACBWR)
'/
PROVISIONAL OPERATING LICENSE NO. DPR-45 4
6 SEP TOPIC III-l - CLASSIFICATION OF STRUCTURES, w
SYSTEMS AND COMPONENTS
Reference:
(1)
NRC Letter, Crutchfield to Linder, dated July 7, 1981.
Gentlemen:
In response to your request in Reference (1), the attached table has been reviewed and comple.ad.
The systems and components were built and tested in accordc,r e with the stated design criteria.
and the structures were des:3ned to the Uniform Building Code, 1958 Edition.
Very truly yours, DAIRYLAND POWER COOPERATIVE Frank Linder, General Manager FL:RMB:af Attachment cc:
J. G. Keppler, Dir., NRC-DRO III NRC Resident Inspectors 4.\\1 0108170329 810806 )
PDR ADOCK 05000409:
P
- PDR,
QUALITY GROUP SEISMIC CLASSIFICATION R.G.I.29 PLANT SECTION XI R.G.l.29 PLANT L
COMP 0NENTS/ SUBSYSTEMS SRP 3.2.2 DESIGN CLASSIFICATION SRP 3.2.1 DESIGN (1)
REMARKS
?
- 1. STRUCTURES j.
Containment Building Seismic Category I l
Containment Shell and ASME III ASME, Sec. II, Covered Under 10CFR Seismic l
Penetrations MC Sec. VIII 50, APP. J, Testing Category I (1962) Sec. IX l
Stack' Non-Seissitc (2)
Crib House (Water Intake Seismic Structure)
Category I
_ Turbine Building (Portions Seismic (3)
Hous'ng Class 1 Equipment)
Category -I
_ Control Room' Seismic-Category I l-Waste Treatment Building-Non-Seismic l
l Spent Fuel Storage Well Seismic Category I l
New Fuel.. Storage Racks
' Seismic.
Category.-I l
l
QUALITY GROUP SEISMIC CLASSIFICATION
~
~R.G.I.29 PLANT SECTION XI R.G.1.29.
PLANT COMP 0NENTS/ SUBSYSTEMS SRP 3.2.2 DESIGN CLASSIFICATION SRP 3.2.1 DESIGN (1)-
REMARKS
- Reactor Vessel ASME ASME Class I Seismic Sec. III Sec. VIII Category I Class I (1962) 7 Reactor Vessel Support Seismic Category I Reactor Vessel Internals ASME Unknown Class I Seismic Sc.. III Many ASTM Category I Class I Specs.
- 3. RECIRCULATION SYSTEM Piping
'ASME ASA B31.1 C1 ass I Seismic Sec. III
- B16.9 Category I Class I Valves ASME
-ASA B16.10 Class I~
Seismic Sec..III BI6.5 Category. I Class I O
Puaps ASME Unknown C1 ass'I Seismic JSec III Category I Class I L:
QUALITY GROUP SEISMIC CLASSIFICATION R.G.1.29 PLANT SECTION XI R.G.1.29 PLANT COMPONENTS / SUBSYSTEMS _
SRP 3.2.2 DESIGN CLASSIFICATION SRP 3.2.1 DESIGN (1)
REMARV,5
- 4. EMERGENCY SYSTEPS Baron Injection System Tank' ASME AWWA D-100
-Class III Seismic Sec. III Category I Class II Piping and Valves ASME ASA B31 1 Classes I, II, & III Seismic Sec. III
. B16. 9 Category I
-Class II High Pressure Core Spray System
~
Pumps ASME-Unknown Class II Seismic Sec. III Category I Class II Overhead Storage Tank-
.ASME ASME Class II Seismic Sec. III Sec. VIII Category I
' Class II
-Piping'and Valves ASME ASA B31.1 Class I & II Seismic Sec. III B16.9
. Category I Class II B16.5 B16.10 o
' Core Spray Header-
_ASME
.ASA B31.1-Classes I, II, &.III Seismic Sec. III B16.5 Category I
_ Class II.
B16.9-B16.10
7....
g QUALITY GROUP SEISMIC CLASSIFICATION 1
R.G.1.29 PLANT SECTION-XI
~.G.1.29 PLANT COMPONENTS / SUBSYSTEMS SRP 3.2.2 DESIGN CLASSIFICATION SRP 3.2.1 DESIGN (1)
REMARKS
'4. EMERGENCY SYSTEMS (Cont'd)
Alternate Core Spray System Diesel Driven Pumps ASME Unknown Class III Seismic Sec. III
' Category I Class II Piping and Valves ASME ASA B31.1 Classes'I, II, & III Seismic
.Sec. III B16.5 Category' I Class II B16.9 B16.10 Building Spray System Piping and Valves ASME ASA'B31.1 Not Included in the Seismic Sec. III
.B16.5 Linservice Inspection Category I Class II B16.9 Program B16.10 Manual Depressurization System Pihingand' Valves
'ASME ASA B31.1 Classes I & II Seismic Sec. III B16.5 Category I Class I
.B16.9 B16.10
- 5. SAFETY RELIEF VALVES ASME ASME Class:I Seismic Sec. III Sec. VIII' Category I
. Class.I
l QUALITY GROUP SEISMIC CLASSIFICATION' R.G.1.29 PLANT SECTION XI R.G.1.29 PLANT-COMPONENTS / SUBSYSTEMS SRP 3.2.2
-DESIGN CLASSIFICATION SRP 3.2.1 DESIGN (1)
REMARKS l
- 6. REACTOR COOLANT PRESSURE i
BOUNDARY
[
Piping From Reactor ASME ASA B31.1 Class I Seismic i
Vessel Up to. and Sec. III B16.5 Category I Including First Isolation Class I B16.9 Valve External to 816.10 Containment i
l
- 7. ISOLATION VALVES i
i (OtherthanValves ASME.
ASA B31.1 Classes I, II, & III Seismic Identified Under Sec. III B16.5 Category I l
Item 8)
Class I B16.9 B16.10
- 8. CONTAINMENT PENETRATIONS
- ASME ASA B31.1 Classes'I, II, & III Seismic VALVES AND PIPING Sec. III B16.5 Category I
~
Class II B16.9.
816.10
.9. CONTROL RODS Seismic l
. Category I l
l l-
- 10. CONTROL R00 DRIVE ASME.
. Class I Seismic HOUSING Set. !!!
Sec. Vill Category I Class I
- 11. CONTROL R00 DRIVE Seismic.
HOUSING SUPPORTS Category I
-QUALITY GROUP SEISMIC' CLASSIFICATION R.G.1.29 PLANT SECTION XI R.G.1.29 PLANT COMP 0NENTS/ SUBSYSTEMS SRP 3.2.2 DESIGN CLASSIFICATION SRP 3.2.1 DESIGN (1)
REMARKS
- 12. CONTROL R0D DRIVE SYSTEM ASME Unknown Classes II & III Seismic Sec. III Category I Class II j
13.-STORAGE WELL COOLING SYSTEM
. Pumps ASME Unknown Class III Seismic Sec. III Category I Class III Heat Exchanger ASME ASME' Class III Seismic Sec. III Sec. VIII Category I Class III Case 1270N Piping and Valves ASME ASA B31.1 Class III Seismic Sec. III Category I Class III
- 14. CONDENSATE /FEEDWATER-SYSTEM Piping From Outermost ASME ASA B31.1 Class II Seismic Containment Isolation Sec. III Category I Valve Up To and Class II-Including the Shutoff
. Valve and Connected
' Piping Up.To and Including tne First Shutoff Valve ~ (4)
Balance of Feedwater Quality
-ASA B31.1:
Class III.
.Non-Seismic System From Shutoff Group D Valve to the Condenser
QUALITY GROUP SEISMIC CLASSIFICATION R.G.1.29 PLANT SECTION XI R.G.1.29 PLANT COMPONENTS / SUBSYSTEMS SRP 3.2.2 DESIGN CLASSIFICATION SRP 3.2.1 DESIGN (1)
REMARKS
- 15. MAIN STEAM SYSTEM From Outermost Contain-ASME ASA B31.1 Class II Seismic
' ment Isolation Valve Up Sec. III Category I
-To Turbine Stop and Class II Sypass Valves and Cor.nected Piping Up To arid Includina First Valve
- 16. PRIMARY PURIFICATION ASME ASA B31.1 Class II Non-Seismic
' SYSTEM Sec. III Category I Class III
- 17. DECAY HEAT COOLING SYSTEM Heat Exchanger ASME ASME Classes I & III Seismic Sec. III Sec. VIII Category I Class II Case 1270N
' Tube ASME ASME Class I Seismic Sec. III Sec. VIII Category I
-Class II Case 1270N Shell ASME ASME Class III Seismic Sec. III Sec. VIII Category I Class III Case 1270N
- 18. COMPONENT COOLING-ASME ASA B31.1 Class III Seismic WATER SYSTEM Sec. III Category I Class III
t
\\
QUALITY GROUP SEISMIC CLASSIFICATION
.R.G.I.29 PLANT SECTION-XI R.G.I.29 PLANT COMPONENTS / SUBSYSTEMS SRP 3.2.2 DESIGN CLASSIFICATION SRP 3.2.1 DESIGN'(1)
REMARY,5
- 19. SHUTDOWN CONDENSER SYSTEM
.ASME ASA B31.1 Classes I & II Seismic Sec. III Category I Class II~
- 20. WATER PURIFICATION SYSTEM ASME' N/A
.N/A Non-Seismic Sec. III Category I Class III
- 21. SEAL INJECTION SYSTEM ASME ASA B31.1 Class'III.
Non-Seismic Sec. III Category I.
Class III
-22. HIGH-PRESSURE SERVICE ASME ASA B31.1-Class III Seismic WATER SYSTEM Sec.-III Category I' Class III 23.. LOW PRESSURE SERVICE ASME
'ASA B31'.1 Class III Seismic WATER SYSTEM Sec. III-Category I Class.III b
-3 f
+
a NOTES, SPECIFIC
"(1) Plant was designed to Uniform Building Code 1958 ~ Edition per SAR.
I,2) The effect of the. stack collapse on the underground off-gas ' storage tanks near'the Waste Disposal Building and on critical piping systems in the Turbine Building will be investigated and any necessary protective 1
structural modifications made will ensure that a safe condition can be-maintained.
1 (3) The addition of lateral bracing in the Turbine Building steel framework will be investigated and necessary bracing installed to preclude excessive damage to the Turbine Building structure.
1 (4) Seismic Analysis of those piping systems which are Lrequired for reactor r
safety is-proceeding in order to determine the type.and. location of
{
additional seismic restraints.