LER-1981-043, /03L-0:on 810702,relay 590-123B Did Not Drop Out When Turbine First Stage Pressure Exceeded 45% of Normal During Routine Load Increase.Caused by Defective Pressure Switch.Pressure Switch Defective Wiring Removed & Replaced |
| Event date: |
|
|---|
| Report date: |
|
|---|
| 2371981043R03 - NRC Website |
|
text
NRC FORM 386 ILS. NUCLEAR REGULATORY COMMISSION (7 77)
LICENSEE EVENT REPORT CONTROL BLOCK: l l
l l
l l 'l (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION) lT[Tl l Il Ll D l R l S l 2 l@l 0 l 0 l-l 0 l0 l0 l0 l0 l-l 0 l 0 l@l 4 l 1 l 1 l1 l 1 l@l l
jg 7
8 9 UCENSEE CODE 14 15 UCENSE NuMOER 25 26 uCEMSE TYPE 40 57 CAT 54 CON'T 4
lol1I NURCE l L gl l5l0j0l0l2l3l7 gl 0 l 7 l 0 l 2 l 8 l 1 @l 0 l 7 l 2 l 8 l8 l1 l@
i a
e0 si coCxETNuueER es se EVENT oATE 74 75 REPORT QATE 80 EVENT DESCRIPTION AND PROSA8LE CONSEQUENCES O'o
- ol2l l During routine
- load increase on Dresden Unit.2, Relay 590-123B did not drop out when l-
,g,3, l turbine first stage pressure exceeded 45 percent of normal. The saf y implications
,,,,,, were minimal because the 3 remaining switches were all operable and would have per-g.
,g,,,, formed the necessary trip at 400 PSIG. There was no effect on public health or safety.;
,, g,, First occurrence at Dresden.
lo!Il!
l lo ta l !
l 7
ea s0 SYSTEM
CAUSE
CAUSE COMP.
VALVE CODE CODE SusCODE COMPONENT CODE SUSCOCE SU8COQE l0l9l' l Il Al@ W@ lB l@ l I l N l S lT lR lU l@ l S l@ l Z l @
7 8
9 to 11 12 13 is.
19 20 SEQUENTIAL OCCU R R ENCE REPORT REVISION LE R/Ro EVENT YEAR REPORT No.
CODE TYPE No.
h aE l8 l1 l l-l l 014 l 3 l l/l l0 l 3l lLl l- -j l0l yV
_ 21 22 23 24 26 27 28 29 30 33 32 N A ON O P NT MET MOURS 22 50 ITT POR 5.
SU U MAN P RER _
l A l@l Z l@
lZl@
l Zl@
l 0l 0l 0l 0l lNl@
lY l@
l Nl@
l 8 l 0 l 6 l 9 l@
33 34 35 36 37 40 41 42 43 44 47 - -
CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h l l i l o l l Relay 590-123B would not drop Out because of a defective pressure switch (PS 504B).
I li#ii i Cause attributed to a micro switch part of the pressure switch.
Since the pressure I i 12 I l switch is equipped with two mict-switches, wiring was removed from the defective l
l,;3g l switch and installed on the spare. Pressure switch was calibrated via DIS 500-7 and l
i, 34, l returned to service. Defective micro switch was subsequently replaced.
7 8 9 80 A
% POWER OTHER STATUS ISC EY OtSCOVERY DESCRIPTION l l1 l5 I bh l 0 l 5 l1 l@l NA l
lAl@l Operator Observation l
l 7 8 A$nviTY COMTENT 12 n
44 4e as s0
(
RELEAsto OPRELEASE AMouNTOF ACTivlTY LOCAftON OF RELEASE l l1l6l y @
@l N/A l
l N/A l
PERSONNEL EXPOS ES NUM8ER TYPE @l DESCRIPTION ltl7llnlq lq l l
N/A l
lZ PERSONNE'L iNau' RIES cESCRiPTiONh NuueER li la l l0 l0 l0 l@l NA l
7 8 9 11 12 80 LOSS 08 OR OAMAGE TC PAClWTY TYPE CESCRIPTTON l_!.19_l !Z lh!
NA l-_
i
,Usu$iY 8108110630 810728 s0 cESCRiPTiON h PDR ADOCK 05000237 NRC USE.ONLY
,$$uto 12 l o f l N {Q NA S
PDR
- ;;;;gl9;;;;lj 8 9 to 68 69 80.*4 Wayne Mor 942-2920 Ext. 422 0
l
_ f ' M" ^ " * "." ' ' " " " ;_ _ __ _ _.. _ g a n_ _. _ _ _
m s,_,?
DEVIATION REPORT DV R NO.
~
Commonwealth Ed.ison STA UNIT YEAR NO.
8-12 81 - 73 PART Il TI TLE OF DEVl ATION OCCU UED 7/2/81 2050 Generator Load Reject and Stop Valve Closure Scram Bypassed Above 45% Power DATE TIME SYSTEM AFFECTED 500
PLANT CONDITIONS
TESTING RPS C3 E"3 Run 1304 MODE pwpguw73
, LOAD (MWE)
YES NO DESCRIPilON OF EVENT Relay 590-123B did not drop out when turbine first stage pressure was greater than 45%. Alarm (902-5) H-4 would not reset.
DESCRIPTION OF CAUSE Unknown at this tine.
WTHER APPLICABLE INFORMATION Fuse 590-7263 was pulled and the 590-123B relay dropped out.
Alarm H-4 then reset.
IM's called in to investigate.
EQUIPMENT YES DR NO.
WR NO.
J. Achterberg 7/2/81 FAILU RE Q NO N/A D14518 RESPONSIBLE SUPERVISOR DATE PART 2 l OPERATING ENGINEERS COMMENTS Pressure switch 504B recalibrated and returned to service.
SAFETY-TYPE OF CEVIATION EVENT OF POTENTIAL TECH SPEC NON-REPORTABLE ANNUAL RELATED REPORTABLE OCCURRENCE PUBLIC INTEREST VIOLATION OCCURRENCE REPORTI NG WR ISSUED 10CFR21 14 DAY YES X YES x 30 CAY TlFlCATION NO NO l
6.6.B.2.b l
REPORTAPLE CCCURRENCE ACTION ITEM NO.
PROMPT ON-5I TE NOTI FICATION NWBER C. E. Sargent 7/7/81 1700 iTL DATE TIME XXRX 81-43/03L-0 T I TLE DATE TIME 24-HOUR NRC NOTIFICATION PRCMPT OFF-SITE NOTIFICATION TPH N/A F. A. Palmer 7/8/81 0908 REGION III CATE TIME TI TL E DATE TIME TGM N/A REGION lli & COL CATE TIME TITLE DATE TIME RESPONSI BLE COMP ANY OFFI CER I N FO RMED O F 10CFR21 c0N0fTIONS AND TWEIA DEPO AT TO N PC TITLE DATE TiML
" 8" REV1 EW AND COMPLETED OPERATING ENGINEin DATE CEP BY STATION REVIEW 3
j DATE 7!3e{9f l
RESOLUTION APPROVEC AND Ml e
La_
AUTHORI ZED FOR CI STRI BUTION STATION (LjERINgDENT OfTE i
96*Sf7' fr*??
(F09w '5*staPf I
I
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000249/LER-1981-001, Has Been Cancelled | Has Been Cancelled | | | 05000010/LER-1981-001-03, /03X-1:on 801210,radwaste Storage Tank Sampling Frequency Failed to Meet Tech Spec Requirements.Caused by Personnel Failure to Follow Procedures.Personnel Reinstructed | /03X-1:on 801210,radwaste Storage Tank Sampling Frequency Failed to Meet Tech Spec Requirements.Caused by Personnel Failure to Follow Procedures.Personnel Reinstructed | | | 05000010/LER-1981-001, Forwards LER 81-001/03X-1 | Forwards LER 81-001/03X-1 | | | 05000249/LER-1981-003-03, /03L-0:on 810120,Model 288 Differential Pressure Indicating switch,3-1349B,tripped Above Tech Spec Limit. Caused by Instrument Drift.Switch Readjusted & Repeatability Verified | /03L-0:on 810120,Model 288 Differential Pressure Indicating switch,3-1349B,tripped Above Tech Spec Limit. Caused by Instrument Drift.Switch Readjusted & Repeatability Verified | | | 05000249/LER-1981-003, Forwards LER 81-003/03L-0 | Forwards LER 81-003/03L-0 | | | 05000010/LER-1981-003, Forwards LER 81-003/03L-0 | Forwards LER 81-003/03L-0 | | | 05000237/LER-1981-005, Forwards Updated LER 81-005/03X-L.Deviation Rept Encl | Forwards Updated LER 81-005/03X-L.Deviation Rept Encl | | | 05000237/LER-1981-005-03, During Local Leak Rate Testing,Measured Leakage of Single Isolation Valve Exceeded Tech Specs.Caused by Normal Deterioration of Valve Seat. Valve Replaced | During Local Leak Rate Testing,Measured Leakage of Single Isolation Valve Exceeded Tech Specs.Caused by Normal Deterioration of Valve Seat. Valve Replaced | | | 05000237/LER-1981-006, Forwards Updated LER 81-006/01X-1 | Forwards Updated LER 81-006/01X-1 | | | 05000237/LER-1981-006-01, Excessive Leakage Indicated Various Penetrations in Feedwater Check Valves. Caused by Cracked O Ring & Worn Swing Pins.Valves Repaired & Broken Components Replaced | Excessive Leakage Indicated Various Penetrations in Feedwater Check Valves. Caused by Cracked O Ring & Worn Swing Pins.Valves Repaired & Broken Components Replaced | | | 05000237/LER-1981-007-03, /03L-0:on 810122,temp Switch TS 2-261-18D Failed to Trip.Caused by Fill Matl Leakage Due to Broken Capillary Tube Close to Sensing Bulb.Broken Switch Replaced W/New Calibr Switch | /03L-0:on 810122,temp Switch TS 2-261-18D Failed to Trip.Caused by Fill Matl Leakage Due to Broken Capillary Tube Close to Sensing Bulb.Broken Switch Replaced W/New Calibr Switch | | | 05000237/LER-1981-007, /03L for Dresden, Unit 2 Re While Conducting Steam Line Area Temperature Switch Calibration Surveillance, Temperature Switch TS 2-261-180 Failed to Trip | /03L for Dresden, Unit 2 Re While Conducting Steam Line Area Temperature Switch Calibration Surveillance, Temperature Switch TS 2-261-180 Failed to Trip | | | 05000237/LER-1981-011-03, L-0 for Dresden, Unit 2 Re Observed Inadequacies in the Implementation of Administrative or Procedural Controls Which Threaten to Cause Reduction of Degree of Redundancy Provided in Reactor Protection Systems or Engineered S | L-0 for Dresden, Unit 2 Re Observed Inadequacies in the Implementation of Administrative or Procedural Controls Which Threaten to Cause Reduction of Degree of Redundancy Provided in Reactor Protection Systems or Engineered Safety Feature | | | 05000249/LER-1981-014, Forwards LER 81-014/03L-0 | Forwards LER 81-014/03L-0 | | | 05000249/LER-1981-014-03, /03L-0:on 810616,during Scram Air Sys Header Pressure Switch Calibr,Pressure Switches 3-302-99A & B Actuated W/Setpoint Lower than Required.Caused by Instrument Setpoint Drift.Switches Reset | /03L-0:on 810616,during Scram Air Sys Header Pressure Switch Calibr,Pressure Switches 3-302-99A & B Actuated W/Setpoint Lower than Required.Caused by Instrument Setpoint Drift.Switches Reset | | | 05000237/LER-1981-015, /03L-0 for Dresden, Unit 2 Re the Fire Marshall Discovered That the Heat Detectors Were Not Functionally Tested within the 6 Month Interval Required by Tech. Spec. 4.12.A.1 | /03L-0 for Dresden, Unit 2 Re the Fire Marshall Discovered That the Heat Detectors Were Not Functionally Tested within the 6 Month Interval Required by Tech. Spec. 4.12.A.1 | | | 05000249/LER-1981-015-03, /03L-0:on 810618,switch Actuated at 32.8 Inches During Calibr of Isolation Condenser Steam/Condensate Line High Flow.Caused by Instrument Drift.Switch Reset | /03L-0:on 810618,switch Actuated at 32.8 Inches During Calibr of Isolation Condenser Steam/Condensate Line High Flow.Caused by Instrument Drift.Switch Reset | | | 05000249/LER-1981-015, Forwards LER 81-015/03L-0 | Forwards LER 81-015/03L-0 | | | 05000237/LER-1981-016, Forwards LER 81-016/03X-1 | Forwards LER 81-016/03X-1 | | | 05000237/LER-1981-016-03, /03X-1:on 810408,noted That off-stream Liquid Effluent Monitor Had Not Been Functionally Tested on Monthly Basis.Caused by Deletion of Surveillance After Replacing on-stream Monitor w/off-stream Monitor | /03X-1:on 810408,noted That off-stream Liquid Effluent Monitor Had Not Been Functionally Tested on Monthly Basis.Caused by Deletion of Surveillance After Replacing on-stream Monitor w/off-stream Monitor | | | 05000249/LER-1981-016, Forwards LER 81-016/03L-0 | Forwards LER 81-016/03L-0 | | | 05000249/LER-1981-016-03, /03L-0:on 810618,water Level Instrument Surveillance Found LIS 263-57A Tripping Above Tech Spec Levels for Low Level Scram & Low Water Level Isolation. Caused by Instrument Setpoint Drift.Setpoint Adjusted | /03L-0:on 810618,water Level Instrument Surveillance Found LIS 263-57A Tripping Above Tech Spec Levels for Low Level Scram & Low Water Level Isolation. Caused by Instrument Setpoint Drift.Setpoint Adjusted | | | 05000249/LER-1981-017, Forwards Updated LER 81-017/03X-1 | Forwards Updated LER 81-017/03X-1 | | | 05000249/LER-1981-017-03, 3B Motor Generator Set Undervoltage Relay Failed to Trip on Undervoltage Signal. Caused by Sticking Relay Tripping Device.Tripping Device Cleaned,Lubed & Placed Back in Svc | 3B Motor Generator Set Undervoltage Relay Failed to Trip on Undervoltage Signal. Caused by Sticking Relay Tripping Device.Tripping Device Cleaned,Lubed & Placed Back in Svc | | | 05000237/LER-1981-017-03, /03L-0:on 810408,QA Audit Discovered That Temp of Cells Adjacent to Pilot Cell Had Not Been Taken,Per Tech Specs.Caused by Inadvertent Oversight Due to Inadequate Procedures.Change Will Be Implemented by June 1981 | /03L-0:on 810408,QA Audit Discovered That Temp of Cells Adjacent to Pilot Cell Had Not Been Taken,Per Tech Specs.Caused by Inadvertent Oversight Due to Inadequate Procedures.Change Will Be Implemented by June 1981 | | | 05000237/LER-1981-017, Forwards LER 81-017/03L-0 | Forwards LER 81-017/03L-0 | | | 05000249/LER-1981-018, Forwards LER 81-018/03L-0 | Forwards LER 81-018/03L-0 | | | 05000249/LER-1981-018-03, /03L-0:on 810619,LIS 263-72B Found Tripping Above Tech Spec Limit During Monthly Water Level ECCS Instrument Surveillance.Caused by Instrument Setpoint Drift.Setpoint Adjusted.Deviation Rept Encl | /03L-0:on 810619,LIS 263-72B Found Tripping Above Tech Spec Limit During Monthly Water Level ECCS Instrument Surveillance.Caused by Instrument Setpoint Drift.Setpoint Adjusted.Deviation Rept Encl | | | 05000249/LER-1981-019-03, /03L-0:on 810821,main Steam Line High Flow Switches Dpis 3-261-2 & 3-261-2D Found Above Tech Spec Limits.Caused by Torque Shaft Gears Binding on Linkage Gears from Normal Wear & Filings Buildup.Gears Cleaned | /03L-0:on 810821,main Steam Line High Flow Switches Dpis 3-261-2 & 3-261-2D Found Above Tech Spec Limits.Caused by Torque Shaft Gears Binding on Linkage Gears from Normal Wear & Filings Buildup.Gears Cleaned | | | 05000249/LER-1981-019, Forwards LER 81-019/03L-0 | Forwards LER 81-019/03L-0 | | | 05000237/LER-1981-020-01, During ASME Hydrostatic Test,Water Observed Seeping from Cracks in 2.5-inch Rx Head Spray Line.Caused by Chloride Induced Stress Corrosion Cracking.Cracks Cut Out & Piping Replaced | During ASME Hydrostatic Test,Water Observed Seeping from Cracks in 2.5-inch Rx Head Spray Line.Caused by Chloride Induced Stress Corrosion Cracking.Cracks Cut Out & Piping Replaced | | | 05000237/LER-1981-020, Forwards Updated LER 81-020/01X-1 | Forwards Updated LER 81-020/01X-1 | | | 05000249/LER-1981-020, Is Canceled | Is Canceled | | | 05000249/LER-1981-021-03, Pinhole Leak Found on Reactor Water Cleanup Line from Regenerative Heat Exchanger. Caused by Sensitization During Initial Welding.Other Internal Cracks Discovered.Heat Exchanger Loop Replaced | Pinhole Leak Found on Reactor Water Cleanup Line from Regenerative Heat Exchanger. Caused by Sensitization During Initial Welding.Other Internal Cracks Discovered.Heat Exchanger Loop Replaced | | | 05000249/LER-1981-021, Forwards LER 81-021/03L-0 | Forwards LER 81-021/03L-0 | | | 05000249/LER-1981-022, Forwards LER 81-022/03L-0 | Forwards LER 81-022/03L-0 | | | 05000249/LER-1981-022-03, /03L-0:on 810902,vessel low-low Water Level Isolation Switch Had Setpoint of 116.8 Inches,Exceeding Tech Spec Limit.Caused by Instrument Setpoint Drift.Setpoint Adjusted | /03L-0:on 810902,vessel low-low Water Level Isolation Switch Had Setpoint of 116.8 Inches,Exceeding Tech Spec Limit.Caused by Instrument Setpoint Drift.Setpoint Adjusted | | | 05000237/LER-1981-023, Forwards LER 81-023/03L-0 | Forwards LER 81-023/03L-0 | | | 05000237/LER-1981-023-03, /03L-0:on 810511,while Running HPCI Pump Test, Operator Observed Torus Wide Range Level Instrument Reading 0 Inches & Narrow Range Level Instrument Reading Approx 2 Inches & Oscillating.Caused by Personnel Error | /03L-0:on 810511,while Running HPCI Pump Test, Operator Observed Torus Wide Range Level Instrument Reading 0 Inches & Narrow Range Level Instrument Reading Approx 2 Inches & Oscillating.Caused by Personnel Error | | | 05000249/LER-1981-023-03, /03L-0:on 810904,while Conducting Quarterly Scram Discharge Vol Continuous Level Monitor Calibr Check,West & East Bank/East Transducer high-high Level Alarm Tripped. Caused by Setpoint Drift | /03L-0:on 810904,while Conducting Quarterly Scram Discharge Vol Continuous Level Monitor Calibr Check,West & East Bank/East Transducer high-high Level Alarm Tripped. Caused by Setpoint Drift | | | 05000249/LER-1981-023, Forwards LER 81-023/03L-0 | Forwards LER 81-023/03L-0 | | | 05000249/LER-1981-024-01, /01T-0:on 810914,ultrasonic Testing Revealed Water in Steam Supply Line to HPCI Turbine.Caused by Low Point in Horizontal Section of Pipe.Drain Line Installed in Low Point & Routed Back to Same Line at Lower Elevation | /01T-0:on 810914,ultrasonic Testing Revealed Water in Steam Supply Line to HPCI Turbine.Caused by Low Point in Horizontal Section of Pipe.Drain Line Installed in Low Point & Routed Back to Same Line at Lower Elevation | | | 05000237/LER-1981-024-03, /03L-0:on 810513,monthly Surveillance for Standby Liquid Control Tank Sampling Found 3 Days Overdue.Caused by Lack of Personnel Attention.Personnel Admonished.Tank Sampled | /03L-0:on 810513,monthly Surveillance for Standby Liquid Control Tank Sampling Found 3 Days Overdue.Caused by Lack of Personnel Attention.Personnel Admonished.Tank Sampled | | | 05000249/LER-1981-024, Forwards LER 81-024/01T-0 | Forwards LER 81-024/01T-0 | | | 05000237/LER-1981-024, /03L-0 for Dresden, Unit 2 Re While Conducting Routine Review of Surveillance, It Was Found That the Monthly Surveillance Required by Tech. Spec. 4.4.c.1 for Standby Liquid Control Tank Sampling Was Three Days Overdue | /03L-0 for Dresden, Unit 2 Re While Conducting Routine Review of Surveillance, It Was Found That the Monthly Surveillance Required by Tech. Spec. 4.4.c.1 for Standby Liquid Control Tank Sampling Was Three Days Overdue | | | 05000237/LER-1981-025, Forwards LER 81-025/03L-0 | Forwards LER 81-025/03L-0 | | | 05000237/LER-1981-025-03, /03L-0:on 810518,during Plant Tour by Operations Personnel,Low Pressure Leg of Isolation Condenser Level Indication Found Valved Out.Probably Caused by Valve Not Being Reopened After Sampling.Valve Opened | /03L-0:on 810518,during Plant Tour by Operations Personnel,Low Pressure Leg of Isolation Condenser Level Indication Found Valved Out.Probably Caused by Valve Not Being Reopened After Sampling.Valve Opened | | | 05000249/LER-1981-025-01, During Automatic Depressurization Sys Valve Operability Surveillance,B Electromatic Relief Valve Failed to Open at Rated Pressure. Caused by Excessive Leakage on Threads | During Automatic Depressurization Sys Valve Operability Surveillance,B Electromatic Relief Valve Failed to Open at Rated Pressure. Caused by Excessive Leakage on Threads | | | 05000249/LER-1981-025, Forwards Updated LER 81-025/01X-1 | Forwards Updated LER 81-025/01X-1 | | | 05000249/LER-1981-026-03, /03L-0:on 810915,while Shutting Down,Rod P-10 Showed Wrong Position on Rod Worth Minimizer.Caused by Several Diode Failures on Two Digital Output Printed Circuit Boards.Boards Removed,Repaired & Tested Satisfactorily | /03L-0:on 810915,while Shutting Down,Rod P-10 Showed Wrong Position on Rod Worth Minimizer.Caused by Several Diode Failures on Two Digital Output Printed Circuit Boards.Boards Removed,Repaired & Tested Satisfactorily | |
|