ML20009G576

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 810413-17
ML20009G576
Person / Time
Site: Hatch  
Issue date: 06/04/1981
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20009G551 List:
References
50-321-81-10, 50-366-81-10, NUDOCS 8108040438
Download: ML20009G576 (2)


Text

,

j APPENDIX A NOTICE OF VIOLATION Georgia Power Company Docket Nos. 50-321, 50-366 Hatch 1 and 2 License Nos. DPR-57, NPF-5 As a result of the inspection conducted on April 13-17, 1981, and in accordance with the Interim Enforcement Policy, 45 FR 66754 (October 7,1980), the following violations were identified.

A.

'10 CFR 20.203(b) requires that "Each radiation area shall be conspicuously posted with a sign or signs bearing the radiation caution symbol and the words: CAUTION (OR DANGER) RADIATION AREA".

10 CFR 20.202(b)(2) states that radiation area "... means any area, accessible to personnel, in which there exists radiation... at such levels that a major portion of the body could receive in any one hour a dose in excess of 5 millirem, or in any 5 consecutive days a dose in excess of 100 millirem."

Contrary to the above, the following radiation areas were not conspicuously posted:

1.

on April 13, 1981, a general area eighteen inches from the south scram discharge header bank in the Unit 2 Reactor Building read 5 to 10 millirem per hour, and 2.

on April 13, 1981, a manway opening to the sump in the Unit 1 Radwaste Building read 50 millirem per hour at knee level and 600 millirem per hour in the manway opening.

Radiation levels at the gonads and the chest were greater than 5 millirem per hour.

This is a Severity Level V Violation (Supplement IV.E.2.).

B.

Teunnical Specification 6.8.1 requires that written procedures be estab-lished, implemented and maintained covering the applicable procedures recommended in Appendix "A" of Regulatory Guide 1.33. Regulatory Guide 1.33, Appendix "A" states in part that radiation protection procedures should be provided.

Contrary to the above, radiation protection procedures were not established, implemented and maintained in that:

1.

on April 15, 1981, alarm set points on 16 of 25 RM-14 friskers were 50%

to 150% greater than 200 cpm above background required by plant proce-dure HNP-8114 paragraph G.7.d.

Background radiation levels on April 15 were within 10 percent of levels recorded by the licensee at the time the alarm set points were determined.

8108040438 810727 PDR ADOCK 05000321 O

PDR

s l

Georgia Pcwer Company 2

Docket Nos. 50-321, 50-366 Hatch 1 and 2 License Nos. OPR-57, NPF-5 2.

on April 13, 1981 a Plant Equipment Operator was observed exiting the Unit 2 Backwash Receiver Pit and was not signed in on standing Radia-tion Work Permit (RWP) 2-81-650 nor was he wearing the proper protec-tive clothing specified on the RWP as required by HNP-8008, paragraph H.

3.

on April 15, 1981, 13 of 15 workers exited the Unit 1 Torus and failed to perform whole body frisks prior to leaving the Radiation Control Area as required by HNP-8005 paragraph G.3.b.(3).

4.

on April 13 and 14, 1981, a contaminated area at the drum capping room in the Unit 1 Radwaste Building was not conspicuously posted as required by HNP-8003, paragraph J.2.

This is a Severity Level V Violation (Supplement IV.E.2.).

A similar item was brought to your attention by our letter dated September 12, 1980.

Pursuant to the provisions of 10 CFR 2.201, you are hereby required to submit to i

this office within twenty-five days of the date of this Notice, a written state-ment or explanation in reply, including: (1) admission or denial of the alleged violations; (2) the reasons for the violations if admitted; (3) the corrective steps which have been taken and the results achieved; (4) corrective steps which l

will be taken to avoid further violations; and (5) the date when full compliance j

will be achieved. Under the authority of Section 182 of the Atomic Energy Act of 1954, as amended, this response shall be submitted under oath or affirmation.

Date:

i i

i i

1 i

i

--..,...-._- -,,,-,.,-,-...-.,.-. -