05000316/LER-1981-028, Forwards LER 81-028/01T-0.Clarification of Reporting Requirements Per IE Bulletin 80-24 Requested

From kanterella
(Redirected from ML20009E629)
Jump to navigation Jump to search
Forwards LER 81-028/01T-0.Clarification of Reporting Requirements Per IE Bulletin 80-24 Requested
ML20009E629
Person / Time
Site: Cook 
Issue date: 07/20/1981
From: Shaller D
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20009E634 List:
References
IEB-80-24, NUDOCS 8107280323
Download: ML20009E629 (2)


LER-1981-028, Forwards LER 81-028/01T-0.Clarification of Reporting Requirements Per IE Bulletin 80-24 Requested
Event date:
Report date:
3161981028R00 - NRC Website

text

h

  • ~,;,,, INDIANA & MICHIGAN ELECTRIC COMPANY DONALD C. COOK NUCLEAR PLANT P.O. Box 458, Bridgman, Michigan 49106 stD M"6) 465-5901 4

3

,n'

%h B

July 20, 1981 6.' L U

c.

L JUL 2 71981* 79 Mr. J.G. Keppler, Reigonal Director h 'A@m h

Office of Inspection and Enforcement

%'b W

United States Nuclear Regulatory Commission s%Q. D '

Region III

/99 Roosevelt Road Glen Ellyn, IL 60137 Operating License DPR-74 Docket No. 50-316

Dear Mr. Keppler:

I have attached a Licensee Event Report (81-028) which repor ts a small service water system leak which we found in the Unit 2 Containment ventilation cooling ccil drain valve.

The leakage amounted to 3 drops per 5 seconds from a bonnet-to-body leak on a 1" drain valve. Upon the advice of one of the on-site NRC resident inspectors, I reported this to you within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> on July 10 as required by IE Bulletin 80-24.

We have again reviewed IE Bulletin 80-24. We question whether the NRC Staff expectsd that minor leakage of this nature should be reported under this Builetin.

The purpose of the Bulletin as we anderstand it is to require the licensee to promptly report any situation where a leak i

could develop into an uncontrolled leakage into the. Containment Building.

We have reviewed the design of the 1" screwed bonnet drain valve. We believe this reported bonnet-to-body leak could not have developed into any further significant leakage. Therefore, it does not appear to us that it should be reported for the purposes of IE Buleltin 80-24.

t We request your clarification of the reporting requirements of IE Bulle-tin 80-24.

Licensee Event Reports of this type cloud the real value of a safety-related reporting system.

In addition, manpower is expended which could better be expended on more important functions.

Sincerely,

[ [f D.V. Shaller Plant Manager

/bab cc: See Attached Distribution 6107280323 810720

~

yW PDR ADOCK 05000316 S

PDR 4864 ?>.g

r Mr. J.G. Keppler July 20, 1981 Page 2 i

cc:.J.E. Dolan R.S. Hunter 4

R.W. Jurgensen R.F. Kroeger K.J. Vehstedt E. Swanson/N. DuBry R0:III i

I R.C. Callen MPSC i

G. Charnoff, Esq.

J.M.. Hennigan W. Lava 11ee EPRI PNSRC J.F. Stietzel l

E.L. Townley i

Dir., IE (40 copies)

Dir., MIPC (4 copies) l f

l r

1 I

i i

I i

h I

1 a

3 m

,.......,-..;+,,,,.,