Amend 61 to License DPR-62,modifying Tech Specs to Permit 72-h Temporary Exemption from Oxygen Concentration Limiting Condition for Operability Requirement
ML20009D281
Person / Time
Site: Brunswick 
(DPR-62-A-061, DPR-62-A-61)
Issue date: 07/14/1981
From: Ippolito T
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20009D284 List:
References
NUDOCS 8107230336
Download: ML20009D281 (4)


Text

.

o UNITED STATES g

NUCLEAR REGULATORY COMMISSION c

o h *-

WASHINGTON, D. C. 20555

[.

k.....,/

CAROLINA POWER & LIGHT COMPANY DOCKET NO. 50-324 BRUNSWICK STEAM ELECTRIC PLANT, UNIT N0. 2 AMENDMENT.TO FACILITY OPERATING LICENSE Amendment No. 61 License No. OPR-62 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A._ The application for amendment by Carolina Power & Light Company dated June 29, 1981 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The " facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied..

C

~

2.

Accordingly, the license.is amended by changes to the Technical Spec-

-ifications as indicated in the attachment to this license amendment and paragraph 2.C.(2) of Facility Operating License No. OPR-62 is hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 61, are hereby incorporated in the 1icense. The 1icensee shall operate the facility in accordance with the Technical Specifications.

8107230336 810714 PDR ADOCK 05000324 P

PDR j

1 2-3.

This license amendment is effective as of June 29, 1981.

FOR THE NUCLEAR REGULATORY COMMISSION m

Thomas A. Ippolito, C ef Operating Reactors Branch #2 Division of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance: _ July 14,1981 g

ge O

g

)

ATTACHMENT TO LICENSE AMENDMENT NO. 61

~

FACIt.ITY OPERATING LICENSE NO. DPR-62 DOCKET NO. 50-324 Remove page 3/4 6-29 and replace with identically numbered page.

4 r

l l

l l

l l

l

CONTAINMENT-SYSTEMS 0XYGEN CONCENTRATION LIMITING CONDITION FOR OPERATION 3.6.6.3* The primary containment atmosphere oxygen concentration shall l

be less than 4% by volume during the period from:

a.

Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after THERMAL POWER > 15% of RATED THERMAL POWER, to b.

Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> prior to a scheduled reduction of THERMAL POWER to < 15% of RATED THERMAL POWER.

~l APPLICABILITY: CONDITION 1.

ACTION:

With the oxygen concentration in the primary containment exceeding the limit, be in at least STARTUP within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.

i SURVEILLANCE REQUIREMENTS l

4.6.6.3 The oxygen concentration in the primary containment shall be verified to be within the limit within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after THERMAL POWER

> 15% of RATED THERMAL POWER and at least once per 7 days thereafter.

l l

  • For the period commencing at 0630 on June 29, 1981, a temporary exemption is allowed to operate BSEP-2 in Condition 1 with contain-ment oxygen concentration exceeding 4% by volume for 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

l l

l L

BRUNSWICK - UNIT l 3/4 6-29