LONG ISLAND LIGHTING COMPAuNY JLd'O SHOREHAM NUCLEAR POWER STATION unnaa
_- J P.o. sox es18, NORTH COUNTRY ROAD. WAOireG RlVER. N.Y.1178.,2
- w
,, 2-2 July 17, 1981 SNRC-596 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C.
20555 SHOREHAM NUCLEAR POhTR STA" ION - Unit 1 Docket No. 50-322
Dear Mr. Denton:
Enclosed herewith are 60 copies of additional information regarding SER Open Item No. 59, control of Heavy Loads, which was previously identified as requiring clarifying.information to complete NRC review.
~-
If you require additional information or clarification, please do not hesitate to contact this office.
Very truly yours, i
N#
4 B. R. McCafff y Manager, Proje t Engineering Shoreham Nuclear Power Station CC/mh
~
Enclosures N
cc: J. Higgins 8107210327 G10717 PDR ADOCK 05000322 E
--_y
Item # 59 - Control of 11eavy Loads NRC letters of December 22, 1980 and February 3,1981 requested information concerning the handling of heavy loads at Shoreham. Specifically, the
~-
reference letters requested information from operating plants via Enclosure 2 and from applicants for operating licenses via Enclosure 3.
This response _-~
is intended to address only paragraph 2.1 of Enclosure 3 as required.
Information required by paragraphs 2.2 and 2.3 will be provided via a separate report submitted later.
The following is provided in accordance with paragraph 2.1:
1.
A review of all cranes, monorails, and hoists for the Shoreham plant was performed in order to identify those capable of carrying a heavy load (ie., greater than a fuel assembly plus i
handling tool,1000 lbs) and which could impact safety related equipment if dropped.
For purposes of this analysis, the load was assumed to pass through a single structural boundary (floor) and to impact equipment located at the next lower elevation.
Only certain areas of the plant contain both safe shutdown equipment (SSE) and overhead handling systems (0HS) capable of carrying heavy loads.
These areas are the reactor building, screenwell, and control building (including diesel generator:
areas). Overhead handling systems in other buildings are separated by extensive distances and would not impact any safe shutdown equipment or structures following a load drop.
The cranes, monorails, and hsists located in buildings containing safe shutdown equipment are tabulated in Table 1 (attached) and are defined as follows:
a.
Overhead handling systems whose failure could impact safe shutdown equipment - Group 1 b.
Overhead handling systems whose failure could not impact l
safe shutdown equipment - Group 2 The list identifies overhead handling systems having potentially adverse load drop consequences irrespective of probability, safety features or single protective barriers / structures.
4 g
2.
As outlined in response 1 above, only overhead handling systems located in buildings containing safe shutdown equipment are considered due to the large distance and/or multiple barriers between the OHS and the SSE. An example of these are the turbine building and radwaste building cranes which are far removed from SSE in the reactor building and the control building. A heavy "~
~
load drop by either of these cranes would present no consequences to essential equipment. OHS located in buildings containing 4
SSE but which would not impact that equipment are defined as Type 2 above and in Table 1.
A separate listing of Type 2 OHS includina the nearest (vectorial) distance to SSE and physical barriers, if any, is presented in Table 2.
3.a.
Equipment essential to safe shutdown (SSD) and decay heat removal is located only in the reactor building, control building, and the screenwell. The majority of the SSE in the reactor building is located below el 175-0 and is shown on Figs. I through 7.
The spent fuel pool and the area of most heavy load operations are located at el 175-0 and are the primary areas serviced by the reactor polar crane. Note that safe shutdown would still be possible without certain equipment where sufficient time exists for manual operation.
For example, valve operators for long term cooling could be manually operated even though the Motor Control Center (MCC) might be lost. However, no credit would be taken for short term operations.
Concerning SSE in the re' actor building, the safe load paths whe e Group 1 overhead handling systems are utilized are shown on Figs. 10 and 11. These drawings outline the monorail locations above safety equipment for these areas. The designated load handling path is defined by the monorails' location since deviations would not be possible. Group 1 heavy load handling operations within the containment aie generally limited to valve operator or recirculation pump motor removal. Drawings defining the monorails' locctions are shown on Figs.10 through 12.
Heavy load handling operations on el 175-0 of the reactor building are outlined on Fig.13. These loads are generally handled by the reactor polar crane over the operating floor in a manner which passes the loads as far as practical from the spent fuel pd. The spent fuel shipping cask is the major load carried near the pool which is inserted into one corner of the pool during the spent fuel shipping operation.
In addition, the cask must eventually
~
be raised from th-entrance at el 40-0 yp to the operating floor.
This operation requires the cask and other possible loads to
pass over certain equipment located on el 8-0 (Fig.1), which is protected by the reinforced concrete slab at el 40-0 (Fig. 2).
Handling of the cask during this operation would utilize the hatchway connecting el 40-0 to 175-0 as shown on the respective figures. A safe load path concerning movement of heavy loads by the polar crane will be established following development of the specific operating procedures.
In general, the crane will not be permitted to carry heavy loads over the spent fuel pool. However, the dual load path (redundant) design will greatly limit operating restraints on load movement over other areas.
SSE in buildings other than the reactor are limited to the path of the monorails and associated hatchways at these locations.
- 3. b>
Safe load handling operations on el 175-0 utilizing the polar crane will be controlled by specific administrative procedures to be provided at a later date. Safe operations at other buildings will also utilize specific procedures and will generally be limited in that load moving operations will be limited to.the specific load path established by the permanent monorails. Note that load handling operations within the containment would generally require an extended interval with the reactor at cold shutdown conditions.
For both Group 1 and 2 cranes, (Table 1), the primary method of safe load handling operations will be in conformance to the specific maintenance or repair procedures to be provided.
A listing of the overhead handling systems used in areas with 3.c.
safe shutdown equipment,.the OHS capacity, the designated lifting device, and the weight of the load to be carried is presented in Table 1.
Specific proc 6dures in compliance with NUREG-0612 Section 5.1.1 (2) will be provided for all Group 1 cranes outlined in the table.
These procedures will be developed prior to heavy load operations whenever safe shutdown equipment is required to be operable. A list of special lifting devices used for heavy loads is provided in Table 3.
3.d.
The lifting devices utilized in 3.c. above are separated into those utilized solely for the reactor polar crane and those used l
for the miscellaneous cranes and hoists. The specific devices i
used for the polar crane are presented in Table 3 and meet the requirements of ANSI N14 1978 or ANSI B30.9 - 1971 as applicable or meet the conservative design criteria outlined in Table 9.1.4-2 of the FSAR.
The remaining OHS generally utilizes slings and integral load connection points. The lifting slings meet the requirements of ANSI B30.9 - 1971 as appropriate.
.-- -- = =
N e
4 3.e....The only Group 1 crane for which ANSI B30.2 - 1976 is applicable is the reactor-polar crane which does meet that standard. Other miscellaneous Group 1 cranes meet the applicable requirements of the purchase specification which generally relate to ANSI B30.16 and B30.11.
As stated in 3.e. above, the reactor polar crane is the only 3.' f.'-
Group 1 OHS required to meet ANSI B30.2 - 1976. This crane does mee rthe standard as well as the guidelines of CMAA st acification 70.
3.g.
Specific procedures 'concerning operator training, qualification, and conduct have not yet been developed for the Shoreham plant. At this time there are nt planned exceptions to the requirements of _
ANSI B30.2 - 1976.
4Property "ANSI code" (as page type) with input value "ANSI B30.2 - 1976.</br></br>4" contains invalid characters or is incomplete and therefore can cause unexpected results during a query or annotation process. t.
E l.
i l
L i
l t
I i
s
i TABLE 1 2
OVERHEAD HANDLING SYSTEMS CARRYING HEAVY LOADS IN SAFE SHUTDOWN AREAS
\\':
Capacity Buildina.
Crane Mark No.
(ton)
Load Carried /Eouipmeat_5erved
. Approximate Ucicht(1bal Groun Crane T_m Reactor 1T31-CRN-002 125/30 Sote l'(Polar Cranh)
Note 3
.1 Polar 1T31-CR'i-019 1.5 Varies (RB receiving area crane)
Varies 1
Mounte:1 Ji%
1T31-CRN-037 24 -
Rocire Pump Motor 42,400 1
Monernil IT31-CRN-044 1
CRD Levoling Tray,
Note 2 2
Monorail 1T31-CRN-045 24 Recire Pump Motor Tran::for
~d2,400 1
Monorali 1T31-CRN-048 1.5 CRD Ropair Area Jib Note 2 2
Mounted JiP9 1T31-CRN-078 2
CRD Pump Noto 2 1
Monorail 2T31-CRN-079A&B 6
Equi,m. cab Hatch Noto 2 2
Menorail 1T31-CRN-080 10 Equiement Hatch Noto 2 2
BridgeA: ens 1T31-CRN-081 4
Equipment Hatch-Noto 2 2
Eridge/Mone 1T31-CRN-082 2
SLC Pump Noto 2 1
EridgeA!cnt 1T31-CR!I-083 1
RBCLCil Ropair Note 2 1
EridgeA:eng IT31-CRN-084 2
Personnel Hatch (inside containment) Note 2 1
EridgeA!cnc 1T31-CEN-085 4
HPCI Noto 2 1
BridgeA: ens 1
1T31-CR'i-086 2
RCIC Note 2 1
EridgeA:ono{
IT31-CRN-087 2
CRD Loveling Tray Note 2 2
Pad Eye
.I.
I 1T31-CRN-088 1
TIP Cask Note 2 2
Pad Eye 4
1 of 3
TA!3LS1(CONT 8 D)_
OVERliEAD ltAt:DLING SYSTB1S CARRYING HEAVY LOAIS IN SAFE SHUTDCW'i AREAS Capacity Approxinato
'uildinc Cranu Mark No.
(ton)
Load Carried / Equipment Served Voicht (1bs)
Croup Crane Tvie hactor
' 1T31-CRLO89 1
R'4CU Repair Note 2 2
Mounted Jib (cont'd) 1T31-CRLO90 2
HSIVs(Main Steam Tunnel Note 2 1
Menorail 1T31-CRN-091 2
MS SRV8s Note 2 1
Monorail 1T31-CRN-092A&3 4
MS SRV8s Note 2 1
Pad Eye 1T31-CRN-093 1
Varies (95' Equip Trolley)
Note 2 2
Monorail 1T31-CRLO94AaD 2
MSIV's (insido containnont)
Note 2 1
Monorail 1T31-CRLO99 1
CRD FLT.
?!ote 2 1
Monorail 1T31-CRN-100 6
R'4Cd Ibc i
4.5 (NRHx) 2 Menorail
,G Room 1X39-CRN-040 18 Motor Generato:-
Note 2 2
Monorail 1X39-CRN-041A 18 Motor Generator Note P.
2 Monorail Control 1X31-CR L104A-F 2
Diesel Generator Note 2 1
Monorail 1X31-CRN-105 15 Diesel Generator Note 2 1
Monorail Screenvoll 1U31-CRL116 7.5 Trash Cart & Misc.
Note 2 2
Bridge Crane IU31-CR'!-120A&B 5
Screenwash Pump Note 2 2
Monorail NOTE la List of heavy loads for Polar Crano Iten Weicht (tons)
.I.
i.
Shield Plug - A 103 B
87 0
97 D
76 9s,
n.
4 OVicthEAD ltAUDLIr!G SYST!cIS CAlmYING lit'AVY LOADS IN SAFE SHUTDOW A!'EAS s
Capucity Approximate J d i rn-f ane Mark No.
(ton)
_ Load Cariied/ Equipment Served Moirht (Ibs)
Croup Crane Tyr,e E
85 F
100 D7well Head Lift Pig 6
Dryuc11 Ecad 43 Dryer & Sep rator Plugs J
50.6 K
55.1(cach)
Refuelini; Canal Plugs L
7 M
9 (each)
N 9
Ex Prescure Veccel Insulation Frame 4
Head Stud Rack 1.5 P2 Ecad Strongback 5
i R.c Prescurc Veccel Head 68 Ser rice Platforn & Support Ring 5
Dryer & Sep.rator Sling 2
Steam Dryer 29 Stes: Sep.rator 51 Stud Tencioner & Frano 6
Flu c l'onitor Shipping Crate 2.5 Shield Plug Lifting Rig (J,K,& A,-F) 9 Spent Fuel Cack 5.8 Cack Restraint 7
Port 2blo Acrueling Shit d (later)
Portablo Refueling Shic d Lifting Rig (later)
Shield Pluc Lifting Rig (L,M,N) 2 NOTE 2:
Equipnent weight assumed equal to erano capacity.
t
.l.
i 3 of 3 O
TABLE 2 6
GROUP 2 OVERHEAD HANDLING SYSTEMS Building Crane Mark No.
Function. - _.
Approximate Distance to SSE Remarks Rtactor 1731-CRN-089 RWCU Ifaintenance 90 ft To fuel pool cooling,PPs 1T31-CRN-048 CRD Area Jib 75 ft To CRD HCU.
1T31-CRN-079A&B Equipnent Hatch 75 ft To CRD HOU 1T31-CRN-080 Equipment hatch 75 ft To HCU.
1T31-CRN-081 Equipment Hatch 50 ft To HCU.
1T31-CRN-088 TIP Cask 25 ft To CRD centrol station 1T31-CRN-095 el 95-0 Equip. Trollr 1T31-CRU-100 RWCU Heat-Exchano.er 15 ft & vall To aCC.
Scr:cnvell 1U31-CRN-116
'Trashcart & Misc.
75 ft & outervan To service water pumps 1U31-CRN-120A&B Screenvash pumps 30 ft & outer r To service water punps vall Control Room 1X39-CRN-040 MG Set 75 ft To diesel generator 1X39-CRN-041A MG Set 75 ft To diesel concrator Containment IT31-CRN-044 CRD levoling 75 ft To Misc. or Redundant Pg IT31-CRN--087 CRD 1 cycling 75 ft To Misc. or Redundant Pg
'.l.
i l of l m
TABLE 3 LIST OF SPECIAL LIFTING DEVICES TO BE USED WITH POLAR CRANES K-rk"No. of Liftine Device Eauipment Cacacity (ton) 1F11-T(M)54,055 Shield Plugs K, K, K, & A-F, J 104 3
4 Inl-TO-051 Drywell Head 50 1F11-TO-056 Shield Plugs L, M, & N and the Cask Restraint 9
1F15-SH-003 Portahle Refueling Shield (later)
F13-E009 (GE)
Reactor Head Strong Back 80 Dryer & Separator Sling 52 - 194.25 in, spacing 38 - 204.5 in, spacing 1 of 1
e 4
sesGM PRES 3URE COOL ANT eN215 PML-034 BNJtCTION EMPC0 PUese
\\
TUReant Omevtu
\\
,0
"'2'"**8*
n.ri. Pw Oi?
,,,c, too, g 4, h.
\\
AAEA Poe CA8LE TRavS y--,,,p-i \\LECTRE DUCT'S' eseH04 E
cm h
-i m
-~
Re uTOR Co.
..m.7,0,,
[_ COOLING f 4CICI PUIAP I
q g a s.-
Tunsi=e ORivt=
iO see4-oom, af.C.A.O Ti.
[i?".141."
..,L.0,.
oa
[ r$+g *o's 4.-
Or&
'G
-Q
- N
/
e-su O
-O s
i 9
sEss-f a+s-scie 4
CQS* GAY QQ
% y",..
e' G?
- ~ ~
,,. s,. P,,L-On
.] O g
nd-a co.e m T m,*PaAv U. :
t':. U."::..L c
- A E L p
i.R so-040tal ac 4GER
'," uni O'
- oj
.ti.nf.03.R C
o mar-Oseia I
e e
}
s.
e,
RrS10UAL eqEAT g attaDual Def AT*
- E.
at sysTIM R
mL sy s -
p g
n
- titir4eed A AnR IhST RMR INST REmo Rusa anz t s *E-Ost
- 2'8 PL42 8,,, "
IT44 e UC -002 A bye 4 #UC-003A
- v.'s' meCLCw atAT ruCnAmsta IP42 e E 408-O I TOPI A o07:
i i
l l
PLAN EL.8'-O' l
FIG. I PL AN VIEW-RELATIVE LOCATION OF SAFE SHUTDOWN EQUIPMENT E L. 8 '- 0" SHOREHAM NUCLEAR POWER STATION-UNIT I
e-18 0*
l.
IR42MMCC-OAl IR42 M MCc-obi MAIN STEAM INST. RACK D IH2l
- PNL-025 IH21MPNL38 l
ELECTRIC CONDUlT
& TRAYS I
,\\
IR24M MCC ll17 IR24 MMCCll27 i
R24MMCCll21 g
IR24MMCCilli
'/
~
,6,,
lE41-3"S HP-6-9018
.. i.'.ig g lO'SHP-6-9018 l I**
RACK No.lH21 PNL-35 Y.
IEllM E-034(C)
IGilM E-034 (B)
[h g-O g
+
7 s::
g
~
IT46M UC-OO28 1
IT46 M UC-OO3 E f.,
Ti g
- t
\\
/
\\
R24MMCCll29 l
HATCH OPENING m IR24MMCdil19 l
(ABOVE)
N
/
N
/
MAih STEAM INST.
RECIRC. SYS.
lH2 L-Mi k\\
2iM PNL-022 l
P L AN E L. 4 0'-O" l
1 FIG. 2 l
P LAN VIEW-RELATIVE LOC ATION OF SAFE SHUTDOWN EQUIPMENT I
E L. 4 O'- 0" SHOREHAM NUCLEAR POWER STATION-UNIT 1 l
l
e 180'
'" *' U "" 70 DUCT OPENING l
- F' '"V (H2M PNL-PO73 g CRD MASTER ELECTRIC CONDUlf
'U AND TRAYS MIS $1LE ELECTRIC CONDUlT PROTECTION WALL AND TRAYS
--jp--
dT 24 jR24*M Cil31 EL 62' 8"
\\/
l
.s n :
s.
,; y,
3"-SHP-6-9018 LRCIC IESI-re, -
{f.
_ p _
i HPC E C SE
'e -
- ', ' # PIPE AND VALVE AREA re, I g _ 'j!NE" I Ni /ALVE AREA I
trH'f EL 63'-O*
\\
l'*
l D "
(.p'
)
k')
s f
a v
-ELEC g
p
/
OPENING EL 63'0" ELEC R
OPENING -
t,
-PIPE CHASE y []f "
.p; d
u-m :m r
_emma ;
g
+
s
/
HC~6 ELEC OPENING
/ HATCHWAY s
ELEC OPENING
\\ ABOVE HOIST
\\ AREA tf N
/
E L 40*-O" HC 4
\\
[
HC-5
\\/
ELEC OPENING h
r*
r.. x wo O'
PLAN EL 63'-O" l
l l
FIG. 3 PL AN VIEW-RELATIVE LOC ATION l
OF SAFE SHUTDOWN EQUlPMENT E L. 63'- 0" SHOREHAM NUCLEAR POWER STATION-UNIT 1
.l
_. -+-
-g~-},..
l ELECTRIC CONCUlT
~
AND TRAYS S
N" l
l
%g N2 SUPPLY IR24M WCCillY Y
y A !I '
I]
Nf POWER SUPPLY W
l $77
- l FiWR 7
r'-m.
dg '*
i IR24 M MCCII2 K p
y tu w
~
1 en 1
/ K
-[ <
4
'<, ']
g INST RACK lH21M PNL-26
\\-
gx$. :
d' t
?'
fY j
r
,.,8 l_k
[,\\ ACCUMU 0'
I TORS
_.M.
[]
I q
Eh /
(TYP)
JET PUMP RV. LEVEL L PRESS 123
$2 INSTR. RACK A O
v'-
p 5
4
~
_g 5
7 5-8 l' -
ELEC H2
',i.
.s' N'Q -
/
7 -I OPENING (
-j-
.s 2
~
c' c.CRDeiPE
['
E:
- /
BUNDLE (TYP)
/
' mmc..
3-
}
-?
FIPE e
,'T
.. ~ ~ 7 C.4ASE IR24 MCClliA
,\\
m PIPE j
I i -
CH ASE(TYP)
\\
IH2 7031 r 'T ELEC RV LEVEL L PRESS
\\
INSTR ( Al lH21M (DIV -BRKR-A l DIV 1-BRKR-B-PP OPENING
'P PNL- 04
- HATCHWAY OPEN l
k JET PUMP (TYP)
DUCT SRM lRM DRIVE RACK
,p lH21
- PNL-08 PLAN EL 78'-7" FIG. 4 PLAN VIEW-RELATaVE LOCATION OF SAFE SHUTDOWN EQUIPMENT EL. 7 8'-7" l
l SHOREHAM NUCLEAR POWER STATION-UNIT 1 l
l l
am M
a ma neswn-s a nm7 s
i ag
+ _ /...,:. '
n
-.w
~
- K
, < r c - %
I r " *'+"
j, y
V
..Y' Q"R h
/ S-
?
j q4
~
w i
..\\.
bd
--E';/
1-y g
Q[,[hh 1h a'
r f~mp h" 4 ffd
\\
\\
j 61,N necu cueica..
s f
5 U
h 5
L iE a
I k
!=
1 s-A_,
_v M
yg sei...
f; I y'.[l r-L~,.J p
Ni i
=
cast:c-k f
I.
I e
\\ sc w
yk
~
ife Q
I,y'3ft M
f O'
g, <
lih t f<r. 1 r
tri
+
lH fii' h H tli I_
f
.t iM219 cm.-02 Attwwar
~
"N
,. -- -- m e
4 H2 F4PiuL-61
~%s
', Tav
.de-agg PLAN EL 112' - 9 FIG. 5 PL AN VIEW-REL ATIVE LOCATION OF SAFE SHUTDOWN EQUIPMENT EL. l12 '- 9" SHOREHAM NUCLEA" oOWER STATION-UNIT 1
a ira -co-O h
elE a "J. _
nu n.h
/-
-d
==
mm[t x
wascce.
mer ep-oos ggtg aarmic causet
[
nnICM '
l p
m2..ua uz.
N%
/~
T gn SPENT FUEL PO)L C00 Lap S'EW ff t*
,} Ah
-'~
- r A
~E (f ' Y
' " HE AT EX(HGT PuldP3
~
p o a 3-
+
- @....,2
.cY.+..,p.X 5
e '.'
, i-q-y l
- - y--__
f,[
-[/
/
-?
m l
-P((
.f '-
T j
a.
. 31.-
-w. nr. trnt en.
4
,__+.____
== c
,~
'c
.? i e
,II N
n,'-
u/
h ~- 4
~
, y l
dk
\\ I-
[
l Y
(,
Y f
L{D
~
^
h" -}fi
[h.lOMl).
o
- ~ A' N
- JMip,
~
/\\
N e
J HATCHWAY llllllllllll!
OPEN d
4 l,
il K
~
J w
- ,*k.
PLAN EL 150'-f FIG. 6 PLAN VIEW-RELATIVE LOCATION OF SAFE SHUTDOWN EQUIPMENT EL.15 0'- 9" SHOREHAM NUCLEAR POWER STATION-UNIT I
9 S
s a
/
\\
(T~Y'n t
a L
j 825/30 TON POL AR CRANE t
y.:., ^
~**
.,.,m CAS l-E LE sHAF T
_ __ECONTAMihAfl0N ARE A gg gyg.ga 0
a CURS l T
__Fr 6l 1i I.)'
FUE l
RE ACTOI4
'742 7 00834 SHRou CLOSED LOOP wuL e
e f
COOLeeG MATER i
l 3
NE Ort g
L yy.J l
[
Ck TST
/
l l
[
" T]
I IL Y'I
...r.
n.
,[
e
~..
ar.u., u
$1180-0Y LIQul0 CONTROL STS g"
vtSSEL STANDY LIQ CONTRO g
edSTRACK
.p
-fa g,7
,c....3, Il "4'-#*
[
l ACTIV.E l
.)
^
'...'a
~..
- m. v lPm. z0 ;
g
[s, kke -
)
L..'... J
'5 v :..
.s;:.
- r~m n
?M, s
i a
'i
' ' ' ' PL*l3DNNEL G
' d' '.
CON m0L 4
scP cypsLL 4
- s. ~
4 a
Af. Pain y
A17
,_"M.'_
k '*
dA CR 0 EguiPM E N T MAA STE AM e - - -
i MANDLM PLATE U
- k g*",;
Tuhat.L PENE TRATION ORywELL c---
-s
~
[* j ',,'
ARE A
)
i
-C0ams unit t__mm.
a
=
-CR0 MASTER ChumER ygr
_dm' YWEL.SEALN
,9, s,I Ul Ff 1"E U
f!T 3
'll iii ii s a, P
n'
. [J ij.g.
- a, k,.,
n' * "/
=
~
L.i'
- h.
- f
--CMASE FOR MPCI ENCLOSED P PE J
l ACCESS
-~-*
l
-4NST RACK STEAniLINE l
,a MS LOCK l
ol l CR0 PUMP/
m4T, -
e 5"
8 1 40 -0*
h (1 TP) r
$' CLOSED LOOP W
C e mi EECM l
MPCI TURetNE i=4i-E -ois
/ MooutE
- u-r c
p nm sSM u/
$gD*
(ED-
_l n
I;
?'
1 GED-Et. -
pi:
- q9-
- '. : r FIG. 7 ELEVATION-RELATIVE LOCATION
.TE-TO MPCI TUR8eNE OF SAFE SHUTDCWN EQUIPMENT SHOREHAM NUCLEAR POWER STATION-UNIT 1
e o
+
Ir----------.,
)
JRANE slut g* g*
e I
N
<[g l
j l
y f
caA
q o
-- t TH ASH CART
, q ', yJ,gg gg_
'L CIRC. WATER Puups e
rnacus wuvtft) 5 a
i l
l l
r, I
g
_,. sit r.
w.vr s
u nr wo 2
nr
~,
__ - -._ _ pJ__.g_,___a
~'
~
It< m l ','
U
- 7...., :
n s
~
l
-~
u
'o 7-I I
l.1 y
'O 7+
m 04
+--4---
FLOOD PRC'EETicN II
!$k
(:. Th--
EU'E" 8
__.J T
i
- f 3,;
c---
9' ~ -
. SET g
,a
.,I --
g
' ' [g -
,- - --- - g I
I I
C R Aast i
i I
I l
~~-~
m+j 9
l'
,,c,,
- sL Aes L
i a
j l
i n.
ScRIEN WASM Pund>5 g 7
g i
i O
f
-g--.
'c h
'd
- o l
. f_-7r',">' "
s i
ag Y
l; i
r---a
~
I
~
4 d
OF f PED j
(,-
I
- ,_._;_.-._.,'-6 -6*l Lee t.c-3--
---.1_ _ - _ _l
- = - _. _
-?
~; ;.. '7'q i j y j
,' FISH A5AETM ii I
Il
f
~8EWDAL AAEA
{j
(
),
';7
-'3
- s w
wet e,s
~,
l
. M
, l
'" '2"
-Ma '5fs[h
--~~-
l M2}
F19 **OLDING TAN A s c
r GRAT'NG SMPT L E PeGT>s s 2 7.*3 h, j
l
~
//
.,Ano RANE AREA
/
rouc.
f-
/
_j 20 Access, /
t, g
j u.
c f
[
g 34 istc
\\
I
/
_rs ranua 4 sor.c,v.E.
l owP EL 19 7 nor ci rac,.c
- u. ir.ie gg.7
, q/ ETENTON P@L R
c:::. _
- v..b W:g n
PLAN i
\\
l.
r afod ocr I
so orN r
jj ggggy;y r*
A u,2Lo 7 wm u.,v..-o,
i y
Ar%
=
p 1
=
0
...,/
pgMrh
=
x U
,j A
49' ? 3 i
Tm rts Jiil
/8_-
p a
hi$ f 5
- E?? '"
}*T%4
=
p k
N;h
+
i w
<1 =< ~W g
4 -y h
24?I*
b,
< RE EN* ELL d
uW
- [pwg 9"-
W' ' -
-F---
A I
j!
Ahk d
a i
i kl N,v7d c h
.y "'.. g,*' C" bb:
M
~
.' %d QQ
, nm i
"*/ l,
((
.j.' 2,, '"[
"2
[
FART. PLAN EL 20-6'& 17-O, i A **ca gy,w CHLCR!NE ROOM VA1.XVAYS a
E6 t CCP44 l
I-.
_.. n g;,
{
U r
!) P,
' 3't$ i-dm 4 d
- MQ, -4 0'= n d= ws%
i..
NOTE 7 4
-c's l
l} ' l g
..~2
. +
U.-
' Il t:
CTE5' SCREENWELL WALMW Y & REMOVAL AREAS PLAN
.,,,,,,,,,g m, a ow EL 20'- 6" h,
av e ei.w,. veuss cr ceassE mrEo 7"'J 74 E::rT NEmaLAaw.amA owNsds,
' ^ ' ' *CCATE APPRGA SCE C# sPmCE ENwELOPE NEQvlef3 PJ EG'T #98CNk.. ARE A GEtow LETMi ETE 5 CAM want smVLD M CLE A# 8t* 8h0G8NG WCe* 5
% f #e~LUCED es st%CE Ea vtLCPE s
f FIG. 8 PLAN VIEW - SCREENWELL i
SHOREHAM NUCLEAR POWER STATION-UNIT I
f l
l o
le
'\\
l o
9 s
I l
T W s' gy si'M irm j,Wh?Y$
Y
'w EL MEL 374 l
'ltyt by S3
. gt g fj N
filil h*T COMPUTE R 900u EVE *4 h, ha9sy.
.0 d 54 Net yq$
Ertl6ENCY SulTCHGEAA Ro(m n IR*weA42-NrYT
'AhN L
/
I IReaA-As
'~'l f-'f.-
~
e--
~ _ _ _ _ _ -
rari lq sArfte S
[
j80uRED CONC nm 2
"J L:.j l 7 A e u.
1CP EL 34-3'
[j._uoyg REtav o004 1
3.21 1I i3 M
f f'
[
EWEAGENCY Sw!TCHrlAR R0cy pc3 o
f"'
.l
.'4 l
e-(-
(-..,.
l i
e I
I f
saris =, g cout ex 7,atmEn usc 3--
N g
i g AY
'o ST j
su i l
' f'-W5'*
I we
_..sa F BATTW,,,
.C(Mgg (y[pr(q(y $wef(Hg(gg g00u 102 TUR9iNE
- O t
%/
BUILD M
EUlEiNC'*[U,14 kmn te l
LL33' 9-K-
4 ed DN I n ds t F N-29A g
O (L 44 0*.
W
[
g l'
Egi bY^ f N e 'EL 2hd f
pgw l[ llMig R-i 1
m
' -tDil4 PNL-0269 iossap w c25e
",4E EL25'-(f CRRIDOR fi o
i At M.,
IIIsll4 Y e W
/j [Oll*PNL-026A/ \\otimpNLo2SA r
I i
I
~
I-N,3_
tr o
iA 6 b ~
~
E W
s rWe t
M N00u
' *Nrg
,..g o'lE-026A
'g'.
Etsc L
n
.w-e2ee 29
%w
! ! R o'- s" l
l
... Ace 3
- T h ~* h wr 6m a +._
Q g
j i
a w
L""
l JN L<
4'
- M N IR 2
~
g y
' 2 2-10*
r lNtg1 Tk
-~~IM (Losung i m4Hrm(,,4,,
WM f
' MA g3'..f AC U.14 8 gy., p g.y l
O 9 '
I N'
M6 P-1, %
M O
L-
, _ h P-stoa - /
E-g r.
N~
- 3 y
a q--,., w FLOOR EL.22-6*
SUCT
~
%'*..*2'
~
7 t'" hJCT
-4HIGH RedTTY b I
C Rw IW60-P s )5 4 8 t
7.- PL ATFORM
-,,,,,,,,.l1,
"*" - Q A xg A
OfSCH.%4 T"1 as40- 054A R?a 10'-
-l t T y P) e ---s-=-eb.
M Of E
IM60-4M-086~
LOUW %%O DelsM2e-est-sO4 j l IN,6g-P-O%
/
CC d
g MN IR434GIO!
9,3 4
Ana
. k b * * *A-( Il $7 T T
ION
~
I
, ~404 3 b
',C#
eg60-PNI a
l (HsLLED-WATER
- 1 # t u
r h
9 hjomm e em -p w,
@6-w.=
SYSTEM EQueR
-m g,.
g M
g um u
me4 rA qui 7-
- CON [L N0h z
i MR l5 TCN l
b
- ~$
cap (T YP 6 PLf;)L -BEAM (A80WE) hrW
,;, = 96*
t M
(
~
Annop i \\
a I
]
O l 5f5gCgT IE5fL G N ROCM a-DAMPE R g "
l[
F
- J iH2tewie a
a=
-TfA VLA8 LOC rr i
an an an 2
ys i
Co.,or,c,,
. uu c.co
. w j,R43'g yg.j5g v y,
L Ale TYP L
gIM6WdL-MCP 'M60-PNI.-ODIS,,
- am_,
y-
.,spgh-. m., h, g
_. EwT hyp
-p is AUK 8 0iL( R' M.)CM
- g g
g,,,
l f
j j
(DE TACHED PLAN CONT
't i!
- , stacg g
PLAN EL 2 5 0
!O
- PLAN EL.44'-O" i
(
& EL 2 2'-6"
-a'**
w 3 1 k-o
,t n l-os m.
DIESEt GDsERATOR Idou
[
(otr404to eta cont uar-67 p2d]
4
,,, 7 I
0 e4mnux i
, m..o..o..,,,,cJg
-c.,.Aqd r
{-
.w. s.
/ aonia, -a ao=
t_ _
y
- xxD i
scua "l'iW.\\IAp=.1 i
l
..w -
-p' e4&e cosa tw p;
i p-
- c. s g wom-ma
... rm wl g
~~ m = r m./
[e
+e
- e,2
- ll
% Ag 39 -)JJ
-,a now g
I x
cs
?.
_ _'qs*R*cL':g.F s
eoue i
.~.
l
'.9 2 c :. q L.'
r,,,, -,n
, J,
+
MOTCdiCONTRd GkIE l w-wr="~wd w j
isuur ooiagf l83tP-128E-L g3,-
6 t
. a o,,, g rtvo-gg%;-
.oro, r l
-...q q ou b
j
/ g n ; > =- l N
0-
= >c =a sta y
H m,o - sexe, as.-
lm g
_ #]. t.} gi
/
- -?
e
>-etc y
paNas w
C a
- no ;
4 N
! brour(
, I' l
'. 6i.
5 rhl 97'*
stoau
- 3 **'8 1l re-aE-ow ru,,,,o M
c
- k f.~_-.
etu.o L-n <ie" e e wj b --- ~
on;vr
..A-vorce
(.,,-30 4 j crN
@~
Oc
...l DN y,
u e
g's _
<-on-
.. n o,
- au2e, 3
,I n WMTVF'l S
ti
[
PLATF EL32 9
- a$25 s.gy 4
7' l"'!";p'//
"!,7@
L'_
.[.m.
w1. -M3et 22 r l
,p,, ]-
- g a
8
.a 7 y g,
8 7
i_ p y y g_
E 'L o
f o8tB l ouTLE T M
[
o O
o 1;
g
[*3h b
ta 44-FN-o37B d.. _ _.N, 3'636i Kf;6",
{P-128F
~
r,
{
},
gg
,g33 e
,y.3 gf
..l h81P4200 n.
s i2'4' ins H l did,j g
y g N
~~~e g
j I*i DINTAME HOOO t ime-ren y PLAN EL20:6 M
' u..... r
.m i
@ -Ek......,,N%T
O G,,,,<,,
8 W & NTg4 ergo
~
..... wo
, fMovaatt St AN
.-REh40VARLE D
R Nc i a'^uaieM!" M M,
6 Lo 63-o'y!!
- rnts HANCRA,L
>. J at y i;
q :
x :V:
s
- ',"'y.v :
r,,,;3J o;, !=so e=t-o4ag. 4 :
W p
..,u
,,.~ s 3
.., k.
1 -
w 1
7
-tco,o
-r F
i i
l t L
i n***f
,,3o.
i f
"u's*.rees.
=c-",,o ;
3
- i. 30 r
.,0
. 3o.
d we-co4e wc-oose sc$o4A o
,,g)
O_,__,
wg ={g 8,d
. u z, p *, cl
-J 1
,.a f.} g g
Q.
[
O'
,gMSo*f u-)
4 I S o l 6 6'.! "f 0 l No~'T L.,c
.,3.so.e437s1
[- Imso.~ p-isia 6-dyl l S 71 6-6
. $-7
\\
j l
"88 '
FIG. 9 PLAN EL 63'-O; CONTROL ROOM BUILDING SHOREHAM NUCLEAR POWER STATION-UNIT 1
e I/
gr i T ae frdktty s T W.W>n
/
"6AEviTRsC (CNC &
ELEC CONCtaT (TRAY $
v&C PUw FLOOR ORAlg
.[
/ SuuP & puup
,.ATo, f
e s..
/
RE W CCRE SPRAr/seCi Ga(x m
-[g/
l gg r--~M P CI LOOP LEvil i
9'-(
i3'-v'/
PUMP
' GAAT ANC,
/
l1
-MPCI P= tup 4 TURB!N(
\\
MiMRAll 1,
f W
47 ThNET E WT i_
%s,'
[V ALVE My*WOWO37) en23 y
EL 20-0 Tme r s
- ~i NCTT2)iT33-GN-065 s
6
> g RC:C W579. A(x
% -h'c,h)lf we4, 7
\\
f N.
k N5,TW A m y-IE - E M
. K5 EIT 6f/
_q
- )'r l$ l*l M, 9 4 es 3
- /, *h--4c- " X y *===n ='W ++=n N:, !,h,9,%
W
,1 & %q'.
e-2 TON TROLLE14 m
- noe,
//
jn\\
.~!
ii.__ a /
s ar mt rTss-cm
,9
', q
~1 f
- '6 sj,*
,q ct/
f%J
.R 'd(s r'\\ - \\
acet Ptar Ii = r
'N
.i
& Tve se.E r
N b\\
kl.T
' '.a
/::
~%/ nraioR q-E D'
CCRE SPRAi q:
x lh, i
LGCD LEVEL
, g, -
, j y
j p
- y.,
P'JuP m
. g
- p h
"#1
.h' CORE $ PRAY PuuP
,y m33,,
N N
C ao f TOUR EL 9-C'
,g m
H thq b
a
- b. E. ityp CORE SPRAY Puuo J
l
'=1=* N_
T-Aw
[
f *- FU mAe O'
su,o m,.y g,g REw BLCCd Ms}{e
?l,
uGNCNa
~,
SEC' f
d '.
]'y-
- 3. AT:
l Ta & OJ NL'eq[p(;AtN{
-g
,g g g
- T E s:M e25 ((I4 i
\\'
IS 1 A
h E
.4 L /,, &
yUU'$
lK f.}
rPwca 4tr 44,:,rne m~ 'n*
[
ELEWOR
- ; 'i-??
.fi e
-m-nt v;w/ ---et.r e..
- 9epr f
.-. r, 3,
EL *- i
+ rw at_cv s was
+,
i
- ,e j/
EO I
f iT h-CW.-m' 0 b
?
./
-5 esLO saug ear-qc,g _ _ ['Nt--l-
~
.',f Ew NT5 N.#
E'. i#- 9" iT-k.:=- 21 v ugG,
,s s
f (
g, s0f t. w ;st E t *Ew0s(C a
.s.r D ce ai. _ A4.
- ~~
WCN%AJL5 Ps TF r
mq k
ARE sHcws ON
_ n.[%
'[
J^W
[.
/, -
-.c
- ~ = -
E C0"2 ^"
CON TA84uf NT ei.NOLE ervo t
[M FW PLAN EL126'-9' k
/
o
'2FJIO M.ndr SUCT FLTERS b
I "*
80% ie" /
{
uoNORAIL t
I
% AA.4-Lb 12 I 3. 8
\\M s
I 2 TON TOOLLEY & Kuif IfitM ia}ll '
h f t D COsk.
\\ syn)o*
IT3f-CR N - 078
,/D g.3 r g
=
h 4
yh 1
/{\\ '
PuuPS h, g,* *c
'{
- ELEc Cco.sT a rRAV5 6
CRO 4's g
g i
/*.-,
?
g fy , [d->,
b.-
3 i
rv e"
.;(.Cf rgo x
C1
- s,j y p$ -
I
/:/
m%
lNSTR GAC4
/
/
t= 216 84L -i" A
s REACTOR RECIRC 4(f-50
, uG SET FLutD CPLG
, COOLEE AEClet PUMPS l
I grES:
CO
& EAa itAT !E nLI.;ED fe IO1GtkLil4 IGAA Cf 4.L3B
\\
CLIsaapa FOR 40LLET3 J. apenalLS F3 E ta5T4.LE3 *a*tLJ EL T3 C L 7 untn sTram watuts. Pin.3 rs =L:Na s utnery P:sitit*e C8r g
Ly (w
4, tw1 inattsys,essTs grattare F3r Enos east a
criTatacht p[
m nr g(L REACTGt UWNN
,cg
-'j
~
Lh % __
_ m am a m-e man
'neennf gyn*
Enl ORAse F PUMP ed*S&W CL MAlst STf AM VALVES D O@T CL FEED ystTF80 %mLVQ y
v
$*!$(43ilH*14 M foi Etsi-Sf At sea 3.s G Toes CAMity vagg 37'O*
/Ji
'II' "h%
f 7J EL T-F*
MALL
_ ' M' d,/ !
-CISPOSAL CASE STORAGE 3-\\-
- _ w gfi-
't I
3 ' '
AEM== NOEL ANO meCA PLATE f
Ast to49T-2*
I
!, *Q6 g, '
1 kj I
t
,l l
1
$4 2 5 s s'- s LG 3
- g
, 4 rosy rg3LLED 6
- Ell 5T g,y
.h
.L 8r'-tf f
N
}'J
'\\,
j k
D 3 / l. 5' IE 3 iffft
& TRAYS t
l
- O(JHIL Yp
-H[
s I
l:
upp _/*'
.L..' ' b
[
J.
b 3f 23 # T ME93 Pk
'*i'l'dm ef m
= "
N.
QQ, N,~
EL KS*
SIA' sway starF El aC4 #
- 4 [' e-
. ih i.,'
!i
- '6 AEw 9TG L W m
,y
,h.,*"
d Ij u-H
' Tag m.
a
. se cowtsy b
\\
CC'4TLNME NT
/
-C L RE ACTOR
_b pIM reNQRL ANC El(E PL ATE ON EL H2h
,r FIG.10 am arfre. vi-uf MONORAILS ARRANGEMENT-REACTOR BUILDING-SHEET 1 SHOREHAM NUCLEAR POWER STATION-LillT 1 pe < -
e ed -
M
8 9
}
b L MAes STEAM kVE,
(
g MONORAES 105 ELP^-l' l
noNonAt.5 Yos. 64[
'x T 54 4 FIG.10 bO 3 2 O
I f
N g
(Stf Ht"E 2 4 4 f4
\\
08'B FIG.10
,1 Coh',
2j6*
P.')*!!' #p.
q.
=[
M..
r s
\\ le.
)Q' e
/
wWeAsts TOS 90'4h' by /
//
- 59 X 23 C V M k
/,
N5f t NOTE 3 4 4 FIG.10
,-- D i
\\
,,i% '
~g, c-'.'8,. ]. -
I II.
s
>O5' ATROLLiv T3FC A4094 i
s
?
3 g
z w nAst
.i
\\
\\.
/$
- /
m
/
\\
N / i s/7 i i
-W4 N\\
7-
'e cm s
ro.
s fpniuAny s
/,
a\\
h e7
-. S /[ \\p'
[.i f /ll pa, 7
p
\\
V
\\
q
, f '( \\,.l\\.p f \\, ! 'j
,j
%. ',N 1"
1
.wn>u y.a
\\
p,
- a.r.,e.s m
/
./.o.onu T
/
,g_g wN n\\. d[L-
', 2. a.
- -(Tm 5 l/
i l.
x/,-
c( Rtac
[
se x 23* n 6-o*
,Nl ct M K l
\\ _,,,
s
..s,.-T..T
/
w,,
o,,.
f
-,s. 3p_ m 45\\/ y
/
,\\
j rtus AT cAww
/
"r!?"^*sRJf? nG. io risT=~T 'u s
/
cettivaton F (2 To Taoan nwmoe4 i
sREQO s
s e-rRlWART $HifLO DALL [
cL.#144;. TOP _
270 PLAN EL 67-6*TC EL95'-C' h
N 880*
MON 00AfL 105. Ell 2(O ti-6*
s'-0*
12
^ sanzfa Tom TeoLLrr sTAstav LIQUO CDNTROL STORAGE TANK A
- i. asosi iT3i-enu-os f
V srtmoAny cc,TAin Env x
\\
+
l
/
mATcw !
a g
s-Is t t
.f k, _ DiscM j
("i f
GR ATING.
SLC TEST TANK
/
i
.j g;,
y g
c J
/
/
pe=A=Y cmTAu4 w,
/-s (Lterol
?
li g \\
taw 3
IL p
D60' sdd err i
Ei,
4 4
f4 4
k pygt po SECOND64V CONTMT ur A= u ol
/
,j evos 4
i
/
I
- b. ct neActoa N
e ~Lar T
PLAN EL il2'-9' k
i h, Rwcu wA ATAta.A* O mA L MovhTED jib CEAM l j't 5% 18'-O' TOS Et 6-*i 3 L e - REu: it3pt .o ~ PLAN EL 175'-9~ l
F !?. e s J g$? E IS.3,n,... w P-B YOil 780LLEY 4 *0r57 Y 93* p.,. ) H-9 IT31-CR's-063 g', - %'I,, jy i p VENT x y 45 e s' 19 8.CLCh pun #PS \\ p ATCH g'-O A A0 's l (STEEL l \\ ,,AAIINGi s 's u , [.!, [;,v,,,:s: J " - r '> \\bs.x I Y C A Math? $ PENT FUEL jT EXCH O 59 $ SPENT FUEL POOL i G d $3'-Fd TO CL RE AC Df ' '8j g L. RE ACTOR 5 p sTonAct p. gaj ' 5CLZ I f PLAN EL 150*-9* k7 p x ~ 5 .h,p 28 MAIN STEAM (TYp) l /,- ~ 1 'at'N 26 V ENT ' E FT.EDeATER / s SAFET, GEUEF v4tvE f vPitt PLA(E$ -[~ \\ f i.28 aEcinc "S*$ " " "3 #" *
- '*"S' (Eemati
/ ~ r ,s sa s , T= mmE..T ns, ca,.. \\'
- I RED PER TsAIL
\\ \\ gg gg y 'T NU\\\\\\ ~ ii!.LES, [/ k\\ ~ n A '.c . a.n .l { $*'"R;j, )ct mEacion l iN s ~ sc, W h\\ l \\ -c'.?;) \\ m ( T.4 / Nea.Aav Mitt'a.Au IIk'zT Mod M I!JfE'J'E A" " / / iL51TMDrif#!saR" g, l !7:3QWr? Nn, / ,%r,.. / (om To M-5} ptATO o w
- t /
ffvP1 PRIMAAv (ONTAtN4ENT - PLAN EL 994TO 114 O' 1 gE c EcaEaEsPLATE FIG.11 I MONORAILS ARRANGEMENT-REACTOR BUILDING-SHEET 2 i SHOREHAM NUCLEAR POWER STATION-UNIT 1 I
.r- ~ 4 g e \\ l CL EQPT HATCH ELtC BOXtS l (L RIACT x_ CfD.8LNLt I s x-t \\ 'N j 9 l a's ? - -._+ l l M f N g.j g ( ORYWEL EQPT MAT (N l g [ g u-amen l s I TAINulki ,~ [ Y- .t fCSITION 4 ) s g* 24'-O*- f S'-6*D(A PERSONNEL
- NATCH-u-totSJl -
+-- C3 h y Roor dor,swows--
- n'enin o *
.T ~.A
- ?**.
M E e g-y y
- '}
~ ..w,- 90sttof2 . -l g /' V - UAA.. = Tom - O ,4 i e c. r -.ap ,s e s .r .g-g 5 M'& V VUCT-Q j ' ". ~.. ' Q 7,g [... ua i s.- E .MCASE gg. 6" R AD ,(A,; F ' TO CL RPv- ', t - -Y y 57'0*,g AOu CL sPV,_ M i e i ,=. n-- -.)-, y W ~ G ENTED TRACM RUNWAY a i .. v + q i-d Br MCDdORAL Caug ma s ..h.
- y'p,~,g
'T SUPPLER (TYP 2 PLACES) $ 8 ' *-*; =.J4's 29-CfLGfpET), ;. BACE CANC AT34-CRN-06
- C-1 (aO TON CAP) a:'
..rCL E(PT.
- [. HATCH
' C-3
- ~
- ~r. ;,
- .. L...
.. MJ 1. M - -R*?,,r e.r-2 4 -..:.M.- ... g(.-.- I n e. -eN. 5 4 FLObn DeAIN' f 107J9* - ~ h rC b.. C !.. E I p l5 1 i 1 i. 97 \\ ... *e l -l yM ;*, j D *2 ' U E ! R* g st : I EL.99-sob, .. 3,. a m a a g. s gag eg;y Jje-g y. La a f REuoVASLL bMIELD M e
- s;*
~' - {' d ~s L BLOCK STORAGEnN.' .- j. A Y' - 7' "g ..' )( ..k-i/- ,.Aj sWd H&VDUC' ,N r i ~ ':- I rTD-CANg - /. ' '~,N.-- I $ 5'42.9 s a2-0M N j GASED NT ~ g fi 2 HOIST EiOO TYPE f . d. / 6 TON RREQ*ES - - -. j [~ l p-fMa d 1 4 ey g5 \\ IID *C FN-Oel 3 4 l 4 i \\ w i m- $5 ~ ~{ l ) i I \\ $n J
- p. \\.
/ .s g I r'-e* sY / e / SECTION 2-2 rewroN *s sHowN)
"W m (a,d-e f TO CL Rf AC .J f5*00'00* l l. su., g ..ev 4 df i 33 I I II e==V I I g n I m.r i D I l EL' -C' s l ,,, -tLIC T 4.75 NMS CR0 BUICLE stuomaLE g.3 s y eLOCK \\ f i I -stm 8 CONTApseeL3sf i . SeaTCn I% EL 9[-S* j, .. ju.c.- f g 2 75",2 g 7 1 \\,14iH i . _ : rm - i f j f " L PTS
- FCA RE MOV&J, j,,
g 4=l g. 1 e P JRC CART CL $
- --,%U l
2 '\\ a.. ' L-- '\\ re k ;' aru REMOVASLE VENT ttda. IP y .f '.) y'f lN 'A m lNTED T9 ACE g s$-S(To CL REAC si.ifo Ct arac u PLAN EL' 78'-7' LEVEL ..<a ,~ SECT m M - ecsana a sioso 6 - C-4 -J .. 'l 'fEL ll2'-Y ' '7 - 16 : W . seen e maan..s mass is = mies amm iet:T cam > e L e 3.. 'r. siam a amas su any me e a eLas as sum.
- 3. gesECT seasTS m cus473a. 9 10 uns St. ObsECT TRELET W
,j candet 10 um m. TmE a ETuale a stle sessf3 ase TilELIT e-m TO Epput Land Fuse leafDs AILTS. IEtett einfoe SET 1. " 1
- 3. tout alsTEM GrFRefD lafflL ORD.83Bf IEaSES ITS artWI Llett W
- . h e1.. I s.'.,,,
5 TamugL (Pastfest I). PtlBITIGI DS887 F tsu.000 Ouga ase ? geest? TO um M. DennestT ties 4st runt us S. t 1 i - -ELEC TRAT5 [, < 4:
- 4. samE sinius arvaam estret aus47sa.s saapi itEla aivan Lime?
. r-W Thawa (FIBITIGe N3. FUE SaEEK E8Em3 ItaTDI tafmL [ l '.h,' .-cg-as emm me sista.Etf cm-eso e== um m. set cam. ass sumas terrik ett sees? IS OutB fit tJ. W IDE 8:a108 amT. (SeGET Cus-SEO 10 UM N afS US S. Dt9GBsECT ,,t ,3 i-+e a v ouCTs smi-even.e rumm uns ei. f S. sgut sinfue artnam W fulfsam a ese LIFT TO CLEAR 91tP af s s Tg*.T*. tartises W 48ut Ianti31 enWNB isfrik Wilm .l'g samen er cum.ase uns W esin smanan *aa. Tneserts seis? '-CRD suscLE y casase aura mesmaat an= me sums amine so uTamm /,tE i teIE IEEMaAT. FUltrF (FWITem M3. safat age Sam W E SYafEDIteEMilf } f s Pins ./ 9 j t wo00 SAOC1.E SLOCK EIOTH ENDS) FIELD OESKsN AMO FABRtCATF i 4-wuo u / SMIELDrers GLOCE ,j STOnAGE s' f,l ',e g.,, FIG. 12 g DRYWELL EQUIPMENT HATCH 4 REMOVAL qua SHOREHAM NUCLEAR POWER STATIOM-UNIT I
t % % T %.cR.o.s rim tert PoslTioN l I REMOVABLE WOTOR LIFT DEVICE G.E.14S C 6465 l 1 ( atac Ton un asa%[ PUWP WOTN G E. 116 D 8931 AB 7 x 7 EQPT MATCH 'O-T '.. 2*i,l'*PTEAs4 AT ,,, woe". C3 EL 95'-61 .h / 4 uC>d0stAtt las EL'd8he \\ a gy.9 G &? F --1.,,, e ( oRTwEtt E s '*1 s -4.g. s I t 3 7, ! -t tc \\ 'N ~ 7 eq,i 434,,,. ...E.m POLL PT 8 / { L r EL 76'-F* I k l= LM -! lI l /:\\ ns_ .,3~ f f j j'"W - -y . a W.. ,--.y, ') 1.. 1 W :,,,,,,..... :f - o } { .J % p,,.., - i} (\\ j l l /j j ~*h ;. 's /_. t -&t *
- A.-
i M .. :V_, l RECIRC PUWP CART [.y D s -4 g; g i TEMPORARY CRIBau4 ( k k >2( PUuP Of5CM.RGE EL69%l0{ PLMP SUCTION -( hCTOR & PUMP EL 6I-6, RuCx msm/,;.s:,- j. }.A .. -. = '= a-* CONT AINWE NT FRiuARY a '. . g I-L 24 FAO SEAM s4 TYP WAX HOOK EL tr9'-4* M F3102C SF1ENCE OF OPERATEM 5 SLEGESTED RR TE N & RECM W WOIDR$ $ I YM EL 95'-Oh ', t scfEs:
- s. EETacu Pise coauas unit a cssEasit soE ritmo sEmm.
ggy, 3g*
- 2. ATTape LIFTiss EEvim (8.E. BentnesS) ase LIFT IEL11E21.Af ttS Pur aCTtut BITae@ ftm sEss3Ialt set 3T.
g . a. aEm esto Possrimi at ses as.o. me marsr etmut. e
- 4. LEATE IS* Mead TDPtgleNF EPPGITS 63EEE semel.
S. L!EEE tEmE. DIsExpeECT BENgtait 2831 FIEN BEm3 age aENE tel57 4-L b* ARAY FIEEE Sat * ($.E.).
- I
. } 4. EL 66-3 = T..aist Emm.im T=urv sui, ie.if.=== TDP aan.Emm ,. on,,, RPPWITS #C tid 5 TALL TDPWlan GemisG.
- 8. tC et VEHet11 estfD PCSITIGs LSHS PIA.L PDillf (5) 82 EE.JE atmR 10 VDetG.E. ($EI16.00153)
- 9. IIDEM WEMit1K ase leTGt FIIGI PWiseMIT CEBIYaspectr ISits MAL
8 POHff ES.'. no. aime casTEns To Pam ses me umE VDHCLI aupe Pam (C) ISHE Pu Powr esi. = tl. IE&spe Ca5TElt5 TO PLM (S) afe IEM WP810.1 ADS Pam (85 pgg gg g-6 usna Mal Poiar cri. 4 II. fEEIGs CaSTEst5 TS PaTie (a) age utM VDetl12 40s Path 'a) M$. EL Mr 4 }go tsins Ph Posaff (I) II. PIQt.4P eETIful AT rotsfr (R) withe PIX.aA GIME age IsapE1NEll LP 1644J 844T0E5. 24* uF SEAM 4 2-2 INtilaL Llfi (YYP 2 f N I. 1
MMM REWOviL N f REMCva9LE PL ATFORM RECIRC PUMP IB319 P-000 A ego g 13-lh,TYP iPT H TCH 00 0,lA gggg p RE ACTOR PEM$TAL L PT S 8 PRauaRY CONTAINMENT g .\\ ^-k RECfRC PUMP WONOPAll 3-24-iO'A9 133 e P.cos B r, COOLER HOUSING e eC0%Dulf DOI f f d. ,4a.. -y p gy
- [ 'Y' q y I
f p AEACTOR VE5SEL I THl$ AREA CETWEEN ELN-6). TOR TEMPORARY ,/ Suppyt, )* NtGM .j' 13'-3[ TO BE KEPT CLEAR OF PlPE S AND EQUtPuf MT g' $) _ (FINAL LIFT PO4NT) 4 f ) r-p I. RA.LPTt. gg s' ~ f b\\ G VEMICLE PATM A i g 4 .-w e. ep ~ d' - h.N '
- b' ELEC PEN.
- A.
fu-H0631 a, y-2.* ~ REuvvASLt,0UCT
- h. -
M) 2'Ji' .? TN WW NTOt B ' LIFT PT R [ d.'s -s. / ! 'e (>ROvt0E CRIB 9tNG ' siEu%ABLE ECTO' STEkL 70 SUPK)RT 43 KIPS) / PEN R 26 tt gf4 (g-124441 =- '/ .*I-H&V* { WM gAcx (ART g pyup op l','-[* (#1 'I JNSTALL CRISBING ,5 j RAL M 2 C3 M ,.h 30'5wn 1 OPEN MATCNWAY J Yuo,na. e ll [ \\ * .\\ r 't 02 i T wiTM FOOPOLE iiEETEN b ?".- - m; ITSt-CRre-09 .s \\ s WM- \\ gg3 oggwR 34/30$m - . ARgA '~ Q.E FPTH C Klf N 8 CRD N.-uosCRAIL SUPPORTS ST@q PT 4 ' AREA PT 5; p g ,f'_ T HATO4 t
- 9..
- W p,/"
- * # 1'.,'
- r. *p s-CR0 LEVELING TRAY
~b N O ---+ T.5 e i 1 sw) 3s3'3015w) PLAN EL 78'-7~ ic a 3 PULL PT F - - -l--- 5 7, (screw ETE IN FL) NOTES: 34rcsw) 4 E l 2 ne+90s WOK 9 wGT 42$30 LSS ,To aE 3 coxEs awc,Cocups A cmEur aos REMOVED FilCM MCTP BEFM TRANSPCETPG. MOTOR SUPPORT j s s \\ / I N i REACTCR PEDESTAL L,4 s) FIG. 13 RECIRCULATING PUMP MOTOR [ REMOVAL f SHOREHAM NUCLEAR POWER STATION-UNIT I 'l
'l 'R'[", - ow. oucT r a1 xa_ (ell 84 9 M' TE APD #6 iT 2 CONTW3 :4NEL CART-I ',F - O DIA [1KT En AD'p' f W T OK/ FLEL 6LFRE s4AftER,1 Tf4 *= - ~- ._., g a. N9,e-EIC 06% ,t ,v / bp'8. g4, 's,, - via-To mo r- }ll NN,, \\ aer a.. A gc e\\ ,e -- -,s an,; - %y .x: n ,:l', MT* I . ) KgG p \\'*- Q [# WnNU,0 "s / y 4,,.' x y. s . / - w"' e, .sT, ton. m as. = E,.,v, < s ~n s-g. . g LACOEA-.s k ,/ . HATCH 1 g.' 3 - < l>x e \\ !m< 2, N 3. - - - -MS gC /y c6 ),y cc,pf sc 3 . ' aan ai,4cf-N ;U / L, ~ TJ"t e,p. 'w1;f'c'q 4 i 4'%,=.y# s,. \\ . _O w.Tx pro.- ut sT, 7 ,A,,:/-'g;gg / =H twa's /g..=l.=; f _ih-n :m=ninp' ; C ,*^p t_.._.OV'~ ,,TL"L \\ i x _ se ause am. %n m 3 qI e m. _____g<. .a.._ _ w a t=,a. y. un I c n' = pg'T
- ~ w -
hfN,.m1,4C v M / 1 -. sx,ris rm ~m
- a>tevanM, / / ),,hrH*
o%IMA - e j]r l * * * "' O' l I s %.s a ma toms o J[ l or ueLE t e ,8/ i [ 'd ""'" \\ h '2
- F~:
sei rut simace poct e =,,, 4t r rMb lr o e Ibt , g.g+ n w a -m. Te m,
- . ds v Tata,s - m,li; war-g /uo ' N,..r
- c
/wi g.'. 1 nu 2rsGE - k'n;.. %yn ,r qm p. m 1 w cm eaw s m 3 v, % w,ut o.c.J O /. < \\'/ / 3 ;re % m. m, cad n
- 3,
- /,/w y W !$,
/', m\\ 3-s arm s s
- ("r N //
ra r+ w' t, i u__. e I / '5~'* + f,' -._"$,, Jj ' f,i, Q-'5"'Jp h-I l /. 1 ST 'fsOF iw i / d >!4]'D, g %$"J'! / K__.) N7'%j! X', _dp 6 _1 /,' H 4 /t / 4 x = p. m s + a_- , w,.. m/.o kRi ,. metr = s-e e -RALST@ .mAANEt POLAR CAANE womav -au m== \\g a g;6;q g%,goEdf-,- w g g _ psY cHast 4, V- :M s/ ej-i,- 4 [ cm.y N O.Trda /'N. o== - m mt,u 1[. g mo r L n4{ \\ : l //'g 2'8 EDG SERV / 7/, ". s iraA yg.m,sft w.A- - - - - y pg t o,Tms, f 4 Ag m _ \\,# ^]. E . -m,i/ &.. A n,i n -n // j (' i y * ,noug, / k s /, h I A r -4_ 'f s}s_ 4,T \\ 3 T ,,.I E 4 j ww rUEL TRANSrER BASRET f s o.A.LE H N..it s s y. h- 0 / s,. ca,sr, M'>"M* 'g' simED ~, l / 'i.s. / / 7 4 [d' 2 O %^ \\ -~ s euct o,o )7-J N., orcentaue.nToN aata ^*C^**** , sA(ulo uer or coaNr mean ecci s .Su*iggonc\\ q SFs 440 L NT&~CW'KIi HTG s 51a=E a ' ,,og wee \\ PLAN elf 7G9 ' '-'*d"4's Al'JfR" CHAhmEL MANDLemG 800w ifll CRm-074 STORED P05'Tscoe HIGH P38NT OF 12V30 TON T EJL.E V EL 2t7'3", prtan ca4rt / UT5s CRN 002. Ii 's I i -Top OF OpiDGE rest y;;hr I i i i i h-2, gt,2cf;f-wna47, hj89$*i: r _gyo-I{ MO. PCnf lk ) Hacee Pont i t CRANE RA4.t g
- I
( naAn HOCM e Aux tOOM i LOkg yg CF C A g g,9 3. g, ,[L igg'g f,' j j FL ATr elf 94 C'- - L A004 E ,1 -Ti; j,,,,,p;- 2 ; - - i ii .,- n'94 9 -u r# s, --.5 - maa sucxtT i,pt4Tr, ,,,c . y 7
- _?'F.-_.
EL M VENT DLIT p (Typ, cnr e::r s -M / ,Riv I L Atr i: e-is EETRA:TET,[L l960 5 g { j Qg / l ice M,NT Cr 7 a 'l i O l f E i w I I EwiEND 0 Ew 92-0 l B ll l C l J p,* mOCD i - PLYsm 3-3 caii
I i
- FS'C; 04 i
%( l err # ELL SHIELD plugs j ITOR I 7.JEL1,75 9 (IFl4 -TO C2h ,7 e n i w e52 B p g in p g q a y/9 D/ ff FI M E jeu h INMA.ATION M(% . gf /[/ gaygg RE AC TOR F4tfiS , ;EL 165 9g viSSEL He AO ";u fl[N 'O s K - NOTE Tm5 DeMEN50N 8ASED ON AN i / -N / - -- g' Cj M N >( AD IN HOLDhG PO$tice E(FDRE '. LD*EWNG ONTO P8EDESTAL 3 liG(r4D & f' c EU52 4k I I' 'SS EU95 i h[, yrte.Akuq,ifd~p Y, k_g_ )t m! N Eu93.i - e------ e \\s .p i [~. / L exTOR ;
- YDHA*LT SUdP
[ l l } .U '/ 2 WHEE L TRUCM y (FCst STUD TEWCNEDW f p N EL IF5'-h. c. H - EL IF5 9 s t i h +,.. g i_)3 I I 22 am R(ITP) REwMGLE CHECFERED PL ATE
- 2 PLACE 5, g NO PAR T5 UST l kE F 512E 4F T) t (TONS) j
'mE4=T PE00 l DwG LMwXH i A I SHIEL D PLUG [ F V - 31 A 381115X Y l F'} "8; B l SHIELD PLUG lFV StA 3*Xi3-Pj M 3 i er .b C i SHIELC PLUG IFV - 31 A ' 3'K;T-FfX I ! 97
- 8. STORA2 PIL Pusis To at nE*LA:E3 a[TEEk POOLS aFTER
[,, y;fggy smAz y nRvEn a sEmam. n
- ycg D
l. SMTLD PLUG lF W -3tf l 35M i2-f II r. 7fa l
- 3. STORa2 L3EAff315 FJR Sam LES STEuS sist EE IIANIP1ATED A$
- 3. u"rfi.E.3 T3 ".W7. -c"'I'O'a' iTaR[a 2.,tooR, o,,TE, OPE Je g E i6 5HIELD PLUG vv.3E ~35xi2-8[x 5 l 85 l Riss -
To a @c m t3gQF l 5HIELD PLbG TV-3T 36TA118313* ICQ l & SEmaT3R $7DRAGE M NRains PLANT QPEnafiah. 5 4-P'IELlus4477 STDRAGE OF STOR42 P3OL PLUG J es pgevix3 JJ l. G B DRY 6 ELL HE AD LIF ThG R IG 1523 E Wu A4 4-s* 6 j utausE Twis Pus asust K ST3RE3 als Top y PLUG 5 meio aqE entwwang arTE4 iTs RECv4 /. H l5 lDRVmELL HEAD l 317-JJAI 32 Dia R 115 : 43 E. E3LHD H51WUCTION MANUAL (G() MARK NQ (Stt.4 42A t' J l1 I DRVER & SEPARATOR PL UG lF v -34 8 123-Gf E 6 A 6 I A 6 l RPV 51LO TE%BCNEP5(44 FRAMF VPF NO 19e2-IE31 b# I 3 4 0RviR& 5EPAEAT0R PLUGS F v - 318 I258hK6 5 fl5531E Ai E g M flAS. L I lREFUELi% CANAL PLUG F v - 3tC ' 4 -TR4 x E F fu M 2 lREFUELhG C ANAL PLUGS F v -3lC S'n e n O 7 9 TEA) E h 1 REFUELi% (ANAL PLUG FV - 33C S n4 A 6'-f 9 g h hG P i RE ACTOR PRESSURE VE5SEL es50L 122-57 23 D6A X if 4 pg cyngg Q 9 HEAD NUT & WA5MER RACK 5 539-12 2 5 A 2 SEI CL30 EE EN R I RPV # FAD SPRAY PIPING ASSY FP BK 12.5I14.5f f 5 5 lME AD STUD R ACE 5.19 - t3 4 a Tx 5' a5 Y l IRE ACTOR HEAD STRO%BACK 5 06-2 ll6-DE 04 5 U i IREACTOR PRE 55JRE VESSEL HE AD SJB 22 i204 fAA X 9-9] 68 .CRN -006A e i ISERitCE PLATFORW &$UPPORT RING hy4 1906A I f { 5 '10N X 1 (DRTER& 5EPARATOR 5tlNG 22-3 pHTatt-CM2-4 2 Y a l5 TEAM DRYER 5ll-e02 ' 16)iA 318 l 29 Z t STEAM SEPARATOR 516 75 17-dDiA s is-E* Si AA j STLC TEN 50NERS441& FRAbf til .ds 6 650 K (-Cf 6 BB i FLuz MONITOR $MIPPtNG CRATE r woy3 45X 3R t
- 2. 5 WT.
.CC I l INSTRUMENT STIOdGBACK 5.12-2 4tXI KI 5 035 ) CD I SHIELD PLUG (K) LIFTING RG 336-3 NE 3 ]r li 9
- E I
BELLOW 5 SEAL GUARD RING (INNER} 5.14-1 h%%4Tq FF 1 BELLOW 5 SE AL GUARD RING (ouTE80 5.21-3 y @"y V,WJ%"i+R^tBl% _ l wz Mt2 l Go n I SPENT ruu o5. .vi, y m..w Sr l JJ 6 vtNT DUCT 5 ff4.Whl ) j mr 3 1e aa mh A FIG.14 f REACTOR BUILDING DISMANTLING & 1 L AY DOW N PL A N - EL.175'-9" E SHOREHAM NUCLEAR POWER STATION-UNIT 1 r L n5.,- s,, REVISION 22-JULY 1981 _ _ _ _ _.. _. _}}