__

~_

~

~-.

-i 400 Chestnut Street Tower II h!'

[ g >/

s June 26, 1981 _. co BL 54438 1-41 A

~

TD BL 39.1-43 h*r $gbIb g.

O JUL 0194 g gg,[ M l

Mr. Jane P. O'Reilly, Director l

Offios of nspection and Enforcement l

U.S. Nuci Regulatory Commission

/c8 Region II -

ite 3100 G> '

101 Marietta 3 t

N I' Atlanta, Georgia 30303

Dear Mr. O'Reilly:

BELLEF00lTE NUCLEAR PLANT UNITS 1 AND 2 - BOP ISOLATOR CABINET -

BLRD-50438/81-41, BLRD-50-439/81 FIRST INTERIM REPORT l

The subject deficiency was initially reported to NRC-0IE Inspector R. V. Crienjak on M-. 27, 1981 in accordance with 10 CFR 50.55(e) as NCR 1472. Enclosed is our first interia mport. We expect to submit our i

next mport by September 17, 1981. We consider 10 CFR Part 21 applicable to this deficiency.

  • l

..f you have any questions concerning this matter, please get in touch with D. L. Lambert at FTS 857-2581.

Very truly yours, TENNESSEE VALLET AUTHORITY L. M. Mills, Manager Nuclear Regulation and Safety Enclosure oo: Mr. Victor Stello, Jr., Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Crummiasion W==hin e, DC 20555 l

fSI4

<,y 3

L81070 2 0y3.3 e

~

..J di s a.,

, n::: a e

i a

ENCLOSURE BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 BOP ISOLATOR CABINET BLRD-50-438/81-41, BLRD-50-439/81-43 1

10 CFR 50.55(e) i FIRST INTERIM REPORT Description of Deficiency I

During receiving inspection of balance-of-plant (BOP) wall-mounted isolator cabinet 2IX-ISOL-262-G at Bellefonte, TVA employees found that a conductor was pulled out of terminal lug TBA-5A-5 The BCP isolators are used to effectively isolate electrical Class IE from non-Class IE instrumentation.

The conductor in question is on the Class IE (input) side of the cabinet.

This condition has not been noticed on any other isolator cabinet. It is apparently caused by interference of the door-locking mechanism with the internal wiring. This defect may be generic to the other wall-mounted isolator cabinets at Bellefonte.

Interim Progress The vendor, Consolidated Controls Corporation, has agreed to examine all wall-mounted cabinets for interference of the locking mechanism with the conductors. The vendor has agreed to reroute conductors, shield conductors from the locking mechanism, and/or modify the locking mechanism as necessary to prevent interference. The vendor will ailso reterminate the loose conductor.

l l

l l

l 1

l l

1 0

hI I)

  • 9 g

pv g 1

}

e

-"p

)y p

1 B

0

'hg

[=

4) ga e 9

yg g

y