ML20006E920

From kanterella
Jump to navigation Jump to search
SER Accepting Util Responses to NRC Bulletin 88-002, Rapidly Propagating Fatigue Cracks in Steam Generator Tubes
ML20006E920
Person / Time
Site: Sequoyah  
Issue date: 02/15/1990
From:
NRC
To:
Shared Package
ML20006E785 List:
References
IEB-88-002, IEB-88-2, NUDOCS 9002260544
Download: ML20006E920 (29)


Text

.

1 4 4

,a N l

.i j

SAFETY EVALUATION REPORT EVALUATION OF WESTINGHOUSE METHODOLOGY TO ADDRESS ITEM C.2 0F NRC BULLETIN 88-02, REVISION 1, OCTOBER 1989 j

MATERIALS AND CHEMICAL ENGINEERING BRANCH i

DIVISION OF ENGINEERING TECHNOLOGY l

j e

1 INTRODUCTION i

On February 5,1988, the etaff issued NRC Bulletin 88-02, " Rapidly Propagating Fatigue Cracks in Steam Generator Tubes." The bulletin requested that holders of operating licenses or construction permits for Westinghouse-designed plants with steam generators having carbon steel support plates' implement actions L

specified in the bulletin to minimize the potential for steam generator tube ruptures caused by rapidly propagating fatigue cracks such as occurred at North i

Anna Unit I on July 15, 1987.

This Safety Evaluation Report (SER) ecdresses the program developec by Westinghouse to resolve item C.2 of the Bulletin.

Item C.2 is applicable to Westinghouse-designed plants where denting is known or assumed to be present at the uppermost carbon steel support plate in one or more steam generators.

Item C.2 of the Bulletin requests that a program be implemented to minimize the probability.of-a rapidly propagating fatigue crack such as occurred at North Anna Unit 1.

This evaluation specifically addresses generic aspects of the program described in WCAP-11799 (Proprietory Version) and WCAP-11800 (Non-Proprietary Version),

" Beaver Valley Unit 1 - Evaluation for Tube Vibration Induced Fatigue," April 1988(Reference 1).

However, similar programs are being implemented at a number of other facilities besides Beaver Valley Unit 1.

Thus, the conclusions of this SER are applicable to other facilities which have implemented similar programs to that for Beaver Valley Unit 1.

i PD8

. Gt i

=

=

i 2

i This evaluation also addresses information provided in WCAP-12150 (proprietary Ve sion) and WCAP-12177 (Non-Proprietary Version), " Anti. Vibration Bar Insertion Depth and its Effect on U-Bend Flow Instability Velocity," January 1969(Reference 6). WCAp-12150 and WCAP-12177 provide additional information i

regarding the generic program developed by Westinghouse.

The conclusions of this SER will be incorporated by reference in plant-specific SERs, where applicable. Licensee programs which utillae alternate approaches to that developed by Westinghouse will be evaluated on a case basis.

2 BACKGROUND - CIRCUMSTANCES OF FAILURE AT NORTH ANNA UNIT 1 The circumstances of the North Anna failure were evaluated in detail by the staff in an SER dated December 3,1987, supporting return of North Anna Unit 1 tofullpoweroperation(Reference 2).

This Section provides a brief sumary of these circumstances.

Westinghouse findings discussed in this section were accepted by the staff in the above mentioned SER for North Anna Unit 1.

]

I The steam generator tube rupture event at North Anna Unit 1 occurred on July 15, 1987 shortly af ter the unit reached 2001 power. For several days prior to the event, operators hed observed erratic air ejector radiation monitor readings.

Grab samples were taken prior to the tube rupture for purposes of perfoming environmental release calculations.

Subsecuent analysis of this data indicated that increasing primary to secondary leakage had occurred over a 24. to 36 hour4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> period before the t'ube rupture event.

This leakage had been below the limit given in the Technical Specifications. The ruptured tube was located in Row 9 I

Column 51(R9-C51)insteamgenerator"C". The rupture location in this model 51 steam generator was at the top support plate on the cold leg side of the tube.

The rupture extended circumferential1y 360 degrees around the tube.

i

' A

,s

-3 A portion of the ruptured tube extending from the cold leg inlet to the fracture location was removed from the steam generator for laboratory examination. The examination of the fracture surface clearly established high cycle fatigue as the failure mechanism as evidenced from the pattern of striation marks and other fracture surface features associated with fatigue. Multiple initiation sites were observed over approximately a 40 degree are at the OD of the fracture surface. The geometric center of the initiation rone was oriented about 90 degrees from the plane of the U bend.

The initial alternating stress associated with fatigue crack initiation was determined by Westinghouse to be in the range of 4 to 10 ksi. This estis. ate was i

baseo on fracture mechanics analyses employing stress intensity factors estimated from the observed striation spacings on the fracture surface. Large-arp11tude flow-induced vibration, normal to the plane of the U-bend, was j

established as the driving mechanism for this alternating stress in view of 5

l large number of cycles ( 10 as inferred from the striation spacings observed on the fracture surf ace) required to propagate the crack from the point of initiation to complete fracture of the tuce.

This mechanism is consistent with the observed location of the crack initiation zone since the maximum bending stress produced by this mechanism also occurs 90 degrees from the plane of the U-bend.

I For alternating stresses in the 4 to 10 ksi range, a high mean stress caused by denting at the uppermost support plate was established by Westinghouse as a requisite condition for fatigue crack initiation. [Thestaffconcludedin Reference 2 that shallow intergranular attack (IGA) penetrations (1 or 2 grains) on the tube surface may also have contributed to fatigue crack initiation.)

Denting also served to shif t the maximum alternating (bencing) stress caused by flow-induced vibration to the vicinity of the upper support plate. Denting is known to have been present in the North Anna Unit I steam generators since the first operating cycle. '

e -

ei-w...w m

l L'

-4 Another requisite condition for the failure at North Anna was the absence of j

en AVE support at the U-bend region of the tube.

For a row p tube at North Anna, a[

]cantileverdeflectionoftheU-bend (asmeasuredattheapex)is necessary to develop the 4 to 10 ksi alternating stress which led to the I

fatigue failure. The presence of an AVB support will restrict tube motion and j

thus preclude the deflection amplitude reovired for fatigue. The original l

design configuration for North Anna required AYBs to be inserted down to as far l

es row 11. However, inspections show that some AVBs in the North Anna Unit 1 steam generators penetrate to row 8, exceeding the minimum AVB required depth.

However, no AYB support was present for the R9-C51 tube that ruptured.

I 3

DISCUS $10N l

This section describes the criteria and supporting rationale developed by Westinghouse for identifying tubes which may become susceptible to fatigue p

cracks such as occurred at North Anna.

Subsection 3.1 describes the flow-induced vibration mechanisms acting on steam generator tubes in the U-bend I

region.

Subsection 3.2 provides an overview of the various factors which may lead to excessive vibration amplitudes, thus creating the potential for fatigue failure.

Subsection 3.3 discusses the development of the Westinghouse methodology for identifying susceptable tubes.

3.1 FLOW INDUCED VIBpATION Westinghouse considered the following flow induced vibration sechanisms as possible contributors to the fatigue failure at North Anna Unit 1: vortex j

shedding, cross flow turbulence, and fluid-elastic instability.

\\

l i

l l

i 1

_~

2 i :

i i

3 Westinghouse analysis of linear turbulence and fluid-elastic excitation of the I

tubing was conducted with a computer program called FLOVIB. FLOVIB incorporates a finite element model of the tube and tube support system and evaluates the (yr,emic response vf the tube based on models for modal vibration amplitude in the turbulert and fluidelastic regires.

Thermal-hydraulic input to the FLOVIB program was provided by a computer program i

talled ATHOS which'used to model the Model 51 steam generator and operating l

conditions.

The program provides velocities, densities, and other parameter distributions for any specific tube (such as R9-CEI which ruptured).

The above mentioned model for evaluating tube response from the turbulence mechanism has been qualified against several series of tests including proto-typical two-phase tests. Turbulence induced vibration amplitudes for tube R9-C51 arepredictedtobeontheorderoflessthan[

5

)atthetubeapex. This order of amplitude would cause maximum stresses in the top of the uppermost support plate (where the rupture occurred) with peak-to-peak amplitudes of less than 2000 psi. Based on these low stress levels, Westinghouse. believes it to be highly improbable that the turbulence rechanism is primarily responsible for the North Anna tube rupture, i

l.

I

.. a.

s.

6 j

The fluidelastic mechanism vill have'a significant effect on the tube response in cases where the fluidelastic stability ratio ($R) equals or exceeds 2.0.

The-stability ratio is defined as Y

$R =

eff Yc

- were V,ff is the effective crossflow velocity and Y is the critical velocity e

beyond which the displacement response increases rapidly.

For R9-C51 at North Anna, the estimated stability ratio (from FLOVIB/ATHOS) utilizing nominal estimates of parameters such as damping ratio, stability constant, and natural frequency is [

] indicating no fluidelastic instability.

j As will be discussed later, these parameters are subject to significant uncer-tainties (particularly for damping ratio and local flow velocity) such that depending on the actual values of the parameters, the stability ratio may L

substantially exceed 1.0.

Motions and corresponding stresses developed by a tube in the fluid elastically unstable mode are quite large in comparison to the other known mechanisms. For this reason, and because none of the other mechanisms discussed above appear to

^

be a plausible mechanism for crack initiation, Westinghouse has concluded that

- the failed tube is most likely a result of its being fluid-elastica 11y unstable.

~

- Given fluid elastic instability as the mechanism for fatigue crack initiation, the

- stabilityratiosforthefailedtubecanbeinferredfrom[

i l

.o 7

3 To estimate the critical velocity and, hence, the stability ratios of the tube which failed, it is helpful to consider Figure 1.

A reference value of effec-tive velocity (termed Y in Figure 1) can be estimated from ATHOS/FLOVIB.

oper Additionally, FLOV!8 provides the turbulence response amplitude associated with thereferenceoperatingvelocity(i.e., point 1inFigure1). The displacement valueforpoint2inFigure1istheabove-mentioned [

] dis.

placement necessary to initiate a crack at the upper support plate.

l l

b i

l 1

FIGURE I Displacement Response Versus Velocity J

{

.D-3 From experimental results Westinghouse states that it is known that the turbu-lence response curve (in log-log coordinates) has a slope of [ J. Test results also show that the slope for the fluid-elastic response depends somewhat on the instability displacement amplitude. Westinghouse states that it has been shown i

by tests that a slope of [

]isappropriatefor i

displacement amplitudes in the range of [

],whereas below[

] are conservative (lower bound) values.

As can be seen from Figure 1, definition of points 1 and 2 and the slopes of the i

turbulence and fluid-elastic response curves are sufficient to solve for Vc and thus for stability ratio (i.e., V, On this basis, tube R9-C51 is estimated to have been operating (p,,fV ).

g prior to crack initiation) at a stability ratiointherangeof1.22[

]to1.56[

), assuming the tube to be vibrating with a displacement amplitude of [

]inchesandacorresponding alternating stress level of 7 ksi.

It follows from figure I that for a given reduction in stability ratio from SR g to SR, the corresponding reduction in displacement response (i.e., from 0 to 0 )

3 7

3 and alterr,ating stress (52 to S)) can be expressed as follows:

[

]

[

]

(Equation 1)

It can be seen from this equation that a small percentage reduction in stability ratio will lead to a much larger percentage reduction in displacement response and alternating stress. With a known reduction in alternating stress, the corresponding reduced value of fatigue usage factor can be estimated.

Westinghouse has also proposed a more generalized form of Equation 1 to compare l-

.the displacement and st'ress responses for different tubes in the same or other l

steam generators, accounting for possible differences in tube geometry, as follows(Reference 1):

. _~

n

.g.

9

[

]

l-

[

]

(Equation 2)*

where:

[

]

[

3 J

3.2 0FF. NOMINAL CONDITIONS POTENTIALLY LtADING TO HIGH STABILITY RATIOS As discussed in Section 3.1, the estimated stability ratio for tube Rg-CSI at North Anna is [

] using nominal estimates of parameters such as stability

~

l constant, natural frequency, and damping ratio. Thus, the tube would have been expected to be stable with considerable margin.

The following sunnerizes Westinghouse's assessment (References 1 and 3) of factors which may have caused l'

the actual statility ratio to significantly exceed 1.

l L

3.2.1 Natural Frequency Stability Constant, and Average Flow Field b

Uncertainties

(

i t -

Westinghouse considers uncertainties associated with calculated tube natural frequencies (in FLOVIB) to.be insignificant. 'This is basec on good correlations between analytical estimates and data for real structures, particulerly in

)

instanceswherethetubesare[

]atthesupportplatesas'a

. result of denting, 1

l:

The stability constant (beta) value used in the stability ratio and critical velocityevaluations(utilizingFLOVIB)arebasedonWestinghousedataandother

=i experimental results as documented in. Reference 1.

This includes data from [

1 i

  • [

)

c t -,

10 -

J This value is used in all stability ratio evaluations addressed in Reference 1 for leaver Valley and Reference 3 for North Anna 1 and presumably in similar Westinghouse evalva-tions for other plants.

The impact of uncertainties associated with ATH0S flow velocity and density distribution predictions on stability analyses were evaluated by using ATHOS to model high pressure steam water (MB-3) tests conducted at Mitsubishi Heavy Industries (MHI) in Japan.

The assumed stability constant of [

]wasfoundto be consistent'with the ATHOS predicted flow conditions and the MB-3 measured f

critical velocity.

Based on the above evaluations, Westinghouse has concluded that natural frequency, stability constant, and average flow field uncertainties contribut?

about[

] uncertainty to stability ratio and critical velocity estimates from FLOVIB. Thus, Westinghouse estimates that the maximum effect of these uncertainties would be to increase the nominal stability ratio estimate for R9-C51atNorthAnnafrom[

] to [

]whichisstillwellwithinthestable regime. Westinghouse further states that uncertainties associated with these parameters could not be large enough to lead to-instabilities (i.e. SR,1.0).

In making this statement, Westinghouse notes that uncertainties in the average flow field parameters, stability constant, and natural frequency are essentially the same for units with dented or non-dented top support plates.

If the errors associated with these uncertainties were large, similar instabilities would be expected in the non-dented units with resulting wear at either the top support plate or inner row AYBs. Westinghouse states that significant tube wear has not been observed in inner row tubes in operating steam generators without denting.

3.2.2 Damping Ratio Uncertainties l

Measurements of mechanical damping in air were performed using a U-bend shaker test facility. For [

l

<g q.

L,. l l

E

  • b The above air tests do not consider the additional damping in a two-phase water /

i steam environment. DatacitedbyWestinghouseshows[

1 1-l

]

Basedonthedatafor[

), Westinghouse assumed a nominal value of damping ratio of [

]whichis associated with the above-mentioned nemir.41 stability ratio estimate of [

]

The Westinghouse report for Beaver Valley (Reference 1) omits discussion of potential uncertainties in the damping ratio estimate.

However, Westinghouse in the earlier North Anna report (Reference 3) estimated a [

] uncertainty factor associated with the assumed [

] damping ratio which would contribute approximately [

] uncertainty to the nominal stability ratio estimate. The assumption of a [ ~

] would increase the nominal stability ratio estimate by about a factor of 2.

3.2.3 Local Flow Velocities Eddy current test results at North Anna Unit 1 established that the AVB supports generally extended as far as row 10 with most extending as for as row 9 and many

- as f ar as row 8.

These non-uniform AVB penetrations have been shown by Westing.

e

,-..a

~ -..,

1 L

).

1 house to have channeled some of the flow to row 8 and row 9 tubes without adjacent l

AVB supports causing a " velocity peaking" effect for these tubes. Preliminary analysis by Westinghouse in Reference 3 indicated that flow peaking may have increased the nominal stability ratio for R9-C51 at North Anna Unit 1 by a factorof[

J. As reported in Reference 1, however, Westinghouse now estimates l

on the basis of an air sodel tests that the AVB insertion configuration in the vicinity of R9 C51 may have increased the stability ratio for R9-C51 by from

[

] relative to the nominal stability ratio [

]asdetermined from FLOVIB/ATHOS.

It should be noted that the ATH0S code does not include the capability to model the presence of the AV8s in the U-bend region.

Flow peaking effects, including a description of the air sedel tests and analyses, are discussed in detail in Section 3.3.4.2.

1 3.2.4 Summary of Off-Nominal Conditions Potentially Associated with High Stability Ratios The following summarizes off-nominal conditions potentially contributing to the high stability ratio for tube R9-C51 at North Anna Unit:

i Stability Ratio Nor,inal stability ratio estimate from FLOVIB/ATH0S

[

]

Including [

]increasetoaccouritforpotential

[

]

l

~

uncertainties 1n natural frequency, stability constant, and average flow velocity Alsoincluding[

]increasetoaccountfordamping

[

]

[

uncertainty

l i

l

' l

, j Alsoincluding[

]increasetoaccountforflow

[

]

]

peaking associated with AYB configuration near tube j

L R9-C51 at North Anna i

Westinghouse now believes (Reference 3) that local flow peaking effects from non-uniform AVB penetrations was a major contributor to the fluid-elastic instability which led to the failure of R9-CSI at North Anna Unit 1.

Although Westinghouse is somewhat non-committal in Reference 1 on the potential contri-bution from lower-than-nominal damping ratios, the staff believes that such off-nominal damping cannot be ruled out as a possibility and, thus, as a significant contributor to the onset of an instability.

The staff notes that Westinghouse reported in Reference 3 that a few row 8 to row 10 tubes were found to contain wall thinning indications at AVB locations which may have occurred as a result j

of fluia-elastic exitation. Some of these tubes were located in regions of relatively uniform AVB penetrations where flow peaking effects would be minimal.

3.3 DEVELOPMEllT OF METHODDLOGY TO IDENTIFY SUSCEPTIBLE TUBES 3.3.1 Fatigue Strength Considerations "S/N curves" are curves relating the magnitude of alternating stress to the number of alternating stress cycles necessary to initiate a fatigue crack.

The S/h curves used by Westinghouse to evaluate conditions for crack initiation were takenfromdatain[

).

This data is based on fully reversed Iceding.

The natural frequency of the row 9 tube U-

- bends at North Anna is about [

).

Assuming that the fatigu' crack initiated over the g-year life-e l

time of the plant to date, then the number of loading cycles leading to fatigue 10 failure (assuming a plant availability factor of 751) was 1.3 x 10 cyc),,,

c

...i

.m m

r

. ~ _ - - -, - + - -

-.w

. c.

14 The corresponding fatigue strength is esti.mted by the staff to be 22 ksi utiliz-N e tsest fit $/N curve and 16 ksi utilizing a 3 standard deviation (3 sigma) lower bound $/N curve from the data in Reference 4.

These fatigue strength estimates exceed the 4 to 10 ksi alternating stress believed by Westinghouse to have caused fatigue crack initiation, but do not include an adjustment for mean j

stress at the fracture location induced by denting of the tube at the seventh support plate.

The mean stress at the fracture location was evaluated by Westinghouse with an elastic-plastic finite element analysis utilizing an axi-symmetric model. The (L

assumed denting ceflection profile from the bottom of the seventh support plate i

to the top was based on profilometry measurements conducted on the fractured j

tube and other adjacent tubes.

The fractured tube had a maximum radial displace-ment of 2.5 mils.

Steady state pressure and thermal loadings were also included in the model.

The results of the analysis revealed a tensile mean stress level i

at the tube OD at the yield strength level.

l The[

] was used to make the mean

)

stressadjustmenttotheS/Ncurvescerivedfromthe[

] data.

[

]

3 Inaddition,the[

] model provides the most reasonable reconciliation between 10 the observed number of cycles to failure (approximately 1.3 x 10 cycles) and

(

the range of initiating stress amplituces (4 to 10 ksi).

In Reference 2, the staff concluded that IGA could not be entirely discounted as L

a contributor to fatigue crack initiation in view of small. (1 or 2 grains) IGA penetrations which were observed as close as 4 mils from the fracture surface.

If IGA did play a role, IGA penetrations would have provided a stress raiser for i

the nominal 4 to 10 ksi initiating stress amplitude.

Thus, a mean stress effect L

as severe as that assumed by Westinghouse would not be necessary to explain

I crack initiation for this nominal stress range.

Even if an IGA influence is assuried, however, the staff believes it should not detract from the effectiveness of actions proposed by Westinghouse to ensure that nominal stresses are suffici.

ently low to minimize the potential for fatigue crack initiation.

~

3.3.2 Effect of 20% Stability Ratio Reduction for Rg-C51 at North Anna Westinghouse has conservatively estimated that a 10% reduction in stability ratio relative to that which led to the failure of Rg-CSI at North Anna would reduce fatigue usage sufficiently to preclude fatigue crack initiation over the 40 year lifetime of the unit. As previously discussed, Westinghouse estimates the alternating stress associated with fatigue crack initiation at North Anna to be in the 4 to 10 (actually 9.5*) ksi range. Assuming the upper bound value of g.5 ksi, it follows from equation I that a 10% reduction in stability ratio j

will reduce this stress to 4 ksi. This reduction has conservatively been estimatedassuminga[

i

).

The corresponding fatigue usage factor is.021 l

per year if the lower-bound, 3 sigma [

]adjustedS/Ncurveisused. This L

translates to a total fatigue usage factor of 0.84 cver 40 years indicating that crack initation shculd not occur.

Itshouldbenotedthatforthe3 sigma [

]

adjusted S/N curve, the assumption of an initial stress level of g.5 ksi is unrealistically high.

This is because the number of cycles to failure for g.5 ksi using this S/N curve is only about 10' cycles (less than one year) whereas 1

10 the actual failure occurred after 1,3 x 10 gygj,,,

  • Westinghouse estimates this to be the maximum possible stress consistent with the observed striation, spacings on the fracture surface without having to assume a physically impossible stress history during crack propagation (Reference 1).

.. ~.

Westinghouse has also performed a number of more realistic calculations to demonstrate that above-mentioned fatigue usage estimate of 0.021 per year conservatively upper-bounds the fatigue usage which would have occurred for R9-C51 at North Anna, given a 10% reduction is stability ratio for that tube.

These calculations considered a nun 6er of different combinations of initial stress level and $/N curves which were consistent with the observation that failure of R9-C51 occurred over 1.3 x 1010 cycles.

These calculations also explicitly considered the variations in steam generator flow parameters (e.g.,

mass flow rates, steam pressure) and, thus, fluid-elastic stability ratios and resulting alternating stresses which existed from cycle to cycle prior to the North Anne failure. The staff's review of these more realistic calculations indicates that fatigue usage associated with a 101 reduction in stability ratio for R9-C51 likely would not have exceeded 0.01 per year.

3.3.3 Stress Ratio Criteria As ciscussed in Section 3.3.2, a 10% reduction in stability ratio was establishtd by Westinghouse as sufficient to reduce the stress amplitude of R9-C51 at North l

Anna Unit I to a value (i.e., 4 ksi) which would nct have initiated a crack over the lifetime of the plant.

Assuring for the moment that 4 ksi is the maximum acceptable value for any tube in any steam generator, then the alternating stress for any such tube must satisfy the following criteria:

S(x)/4 ksi,1.0 (stress ratio criteria)

FromEquation2(discussedinSection3.1),thestressratiocanalsobe expressed as follows:

[

]

(Equation 3)

~

j l ]

where:

a refers to the specific tube being evaluated 9/$1 refers to R9-C51 at North Anna Unit 1 i

The quantity, $R(x)/$R(9/$1), is referred to as the normalized stability ratio l

for the tube under consideration. Westinghouse has chosen to work with normal.

ized stability ratios in lieu of absolute stability ratios to further minimize l

the impact of uncertainties in the stability ratio estimates by essentially

)

eliminating constant. error factors. Westinghouse calculates the normalized stabi-l lity ratio using the methodology described in Section 3.3.4 The corresponding

.I stress rattu is then calculated from Equation 3.

]

The stress ratio criterion is used by Westinghouse as a screening criterion to ensure that S(x) is less than or equal to 4 ksi. however, 4 ksi will not neces-sarily ensure acceptable fatigue usage for tubes whose stiffness and/or section modulus differ from that for R9-C51 at North Anna.

The fatigue usage can be conservativelyestimatedfromthelowerbound,3 sigma [

]$/Ncurveconsidering the natural frequency of the tube and the design basis service life.

The alter-natitig stress usso in these estimates is given by the expression:

[

]

(Equation 4) j l

3.3.4 Normalized Stability Ratio Estimates j

I As discussed in subsection 3.3.3, equations 3 and 4 are used to calculate the maximum alternating stresses for tubes in any steam generator which are dented at the uppermost tube support plate and which are unsupported by AVBs. For a giventube,the[

l

] are known quantities (as determined from [

J.

The remaining parameter which must be determined in order to solve for the maximum alternating stress is the normalized stability ratio (SR(x)/SR(9/51))forthetubeinquestion.

The normalized stability ratio can b'e broken down as follows:

SR(x)

S R,.(x )

FP(x)

(Equation 5)

SR(9/51)

SR(9/51)

FP(9/51) r L

L

I i

where:

SR Nominal stability ratio for uniform flow (no

=

r flow peaking) conditions local flow peaking factor l

FF

=

l 3.3.4.1 Nominal Stability Ratios

\\

Nominal stability ratios (SR ) are now determined with the Westinghouse r

proprietory finite element code called FASTVIB which calculates the response of l

individual tubes exposed to tube location dependant fluid velocities, densities, and void fractions.

[FASTVIBhasbeenverifiedbyWestinghousetobeequivalent to the FLOVIB program and an associated pre-processor program which were used for the analysis of R9-C51 at North Anna Unit 1.) The velocities, densities, i

and void fractures are determined using the 3D ATHOS code which models the steam generator and operating conditions (e.g., steam flow and pressure, circulation ra tio).

i The nor.inal stability ratio estimates are generally performed for a reference operating cycle for each plant. Actual stability ratios may vary from cycle to cycle due to differences in steam flow, steam pressure, and circulation ratio.

i Detailed FASTVIB/ATHOS analyses are very time consuming (and expensive) and are generally not performed for each cycle. However, approximate estimates of the i

cycle dependent stability ratios relative to the reference cycle are obtained from simplified, one-dimensional analyses considering relative values of the major operational parameters affecting stability ratio.

t 3.3.4.2 Flow Peaking Factors The ATHOS code does not have the capability to assess local flow peaking effects

)-

associated with non-uni, form AVB penetrations. Westinghouse has performed extensive air model (wind tunnel) testing to stu@ the flow peaking phenomenon and its potential effect on fluid-elastic stability ratios.

Thetestprocedureconsistedof[

19 J.

In rerun-ning a particular test, good repeatability of the results was demonstrated.

The uniform AYB insertion configuration was selected as the reference configura--

tion. The other configurations tested were taken to be representative of the configurations actually occurring in steam generators in the field, including i

that associated with'the failed North Anna tube (R9 C51). The flow peaking factor is defined as the ratio of the critical velocity associated with uniform AVB insertion (the reference configuration) divided by the critical velocity for the configuration of interest.

L Westinghouse has performed as detailec assessment of potential uncertainties associated with the flow peaking factors derived from the air model tests, and has directly considered these uncertainties to ensure conservative estimates of normalizedpeakingfactors(i.e,FP(x)/FP(R9-C51)). The major sources of uncer-l tainty which have been considered and accountee for in the peaking factor l-estimates are:

1) velocity test measurements 2) test repeatability L

3) geometry differences between the test model and the actual steam generators 4) use of air model tests to predict behavior of proto-typical steam-water mixture.

5) uncertainties in AVB insertion depth estimates as derived from eddy current test Flowpeakingfactorsweredeterminedtorangetoamaximumof.[

]forthe l

L various configurations tested. This maximum value only slightly exceeds the normal peaking factor o,f 1.56.for the AVB configuration which matched that which existed local to R9-C51 of North Anna Unit 1.

This is consistent with

i

]

'o

.e the observation that flow peaking was a primary contributor. to the North Anna

.h,re event. However, for purposes of calculating conservative normalized flow peaking factors for other tubes, Westinghouse has considered a lower bound flow peaking factor of [

]forR9-C51atNorthAnnaUnit1baseLon the uncertainty assessment discussed above.

J 3.3.4.2 Resolution of Staff Coments Pertaining to Flow Peaking Factors

)

During the staff review of initial plant-specific submittals (and subsequent

'l to the original version of this generic SER), the staff developed a number of questions relating to the following general topics:

j 1,

Uncertainties associated with test model asymetry with respect to j

the tube of interest 2.

The effect of partial tube gap penetration by AVBs in one or both sides of the tube of interest 3.

Justification for flow peaking factor estinates made by Westinghouse for a number of specific cases at several plants.

Westinghouse documented its response to these questions in WCAP-12150,

" Anti-Vibration Bar Insertion Depth and Its Effect on U-Bend Flow Instability Velocity, January 1989. WCAP-12150 includes a verbatim statement of the specific questions from the staff which had been informally transmitted to Westinghouse in November 1988.

The Staff has reviewed WCAP-12150 and, subject to the comments below, finds that Westinghouse has adequately demonstrated that:

m

21 1.

Flow peaking factor uncertainties associated with test model asymmetry are small (i.e., 255) and within the uncertainty already considered by Westinghouse in its peaking factor estimates to account for test repeatability.

2.

Partial gap penetrations by AVBs in one or both sides of the tube of-interest act to significantly reduce flow peaking factors for the vast majority of AVB configurations tested.

3.

Adequate justification exists for the flow peaking estimates questioned by the staff for a number of specific cases.

The staff notes that peaking factors estimates can have a significant influence in the overall stability ratio for a given tube. Furthermore, the flow peaking factor estimates vary quite significantly among different AVB configurations, even where the cifference between configurations is relatively subtle. Therefore, great care and good judgement is required to ensure that flow peaking f actor estimates are based on test data for idealized AVB configurations which are conservative for the actual AVB configurations in the field to which they are being applied.

3.3.5 AVB Insertion Depth Assessment-The AVB insertion depths are determined on the basis of interpretation of the eddy current test (ECT) signals produced by the intersection of AVBs with the U-bends anc the known geometry of the AVBs (apex radius and included angle). Detailed criteria for assessrent of these data have been developed by Westinghouse. The use of data 'iom multiple tubes in the same column provide consistency checks for the data from incivjdual tubes and also provide a means for estimating the location of AVB intersections for tubes which were previously plugged or for which ECT data could not be obtained. Although ECT is generally capable of 9

I 22 detecting AVB intersections of a tube, it coes not provide a direct indication of what side of the tube the detected AVB is located. This can be determined indirectly, however, by enforcing consistency of data between adjacent columns of tubes.

AYBs whose centerlines extend to at least the center-plane of a tube at the apex of the U-bend can be considered to provide an effective support to that tube.

Tubes with an effective AVB support on only one side of the tube can be considered to be fully supported. This latter point has been confirmed by air-model tests performed by Westinghouse. These tests show that the amplitude of vibration for a tube with a single-sided support is limited to gap between the tube and the support.

3.3.6 Summary of Westinghouse Methodology to Identify Susceptible Tubes The Westinghouse methodology for identifying tubes potentially susceptible to l

fatigue crack initiation is sumarized below. The expression.

  • region of in-terest, is interpreted by the staf f to include the region defined by the following bouncaries. The outer boundary is a tube row located at or beyond the row of the shallowest AVB penetration depth.

The inner boundary corresponds j

to a tube row where the net stability ratios (for dented, unsupported tubes)

L have attenuated sufficiently to be of no significance.

j i

Eddy Current Data Review Identify all tubes in the region of interest which are dented at the uppermost' tube support plate. Denting is a requisite condition for fat-igue crack initiation.

[AsstatedinBulletin88-02,thestaffnotes

]

that denting should be considered to include evidence of support plate corrosion and the presence of magnitude in the tube-to support plate l

crevices,regardlessofofwhetherthereisdetectabledistortion.]

l L

t

.:..i.o.

i I

23 -

Identify location of AYB support sigr.als fer all tubes in the region of interest.

l h

Evaluation Activities Evaluate AVB insertion depths to identify unsupported tubes in the region of interest and to assess flow peaking factors. The 'Jestinghouse method-ology for evaluating AYB insertion depths is briefly eep.rtbed in Section 3.3.5.

Evaluate normalized flow peaking factors (relative to R9 C51 at North Anna Unit 1)forunsupportedtubesinregionofinterestbasedonconfiguration

~

l of AVB insertion depths. The basis for the flow peaking factor estimates is described in Section 3.3.4.2.

i Perform ATHOS analysis for reference operating cycle to assess effective flow velocities, densities, void fractions, and other relevant thermal-hydrualic parameters for tubes within the region of interest. This analysis is briefly described in Section 3.3.4.1.

j Evaluate normalized stability ratios (without flow peaking effects) relative i

to R9-C51 at North Anna for tubes in the region of interest as discussed in Section 3.3.4.1.

l Determine net normalized stab'ility ratio (including flow peaking effects) fromEquation5(Section3.3.4)forunsupportedtubesinregionofinterest.

l.

Determine stress ratio for unsupported tubes utilizing equation 2 and corresponding maximum alternating stress from equation 3.

Equation 2 and 3 were presented earlier in Section 3.3.3.

Calculate corresponding

~

fatigue usage factors utilizing lower bound, 3 sigma [

]S/Ncurve. The l

number of stress cycles over the projected service life of the plant should be based on the natural frequency of the subject tube assuming l

l clamped supports.

N T"T

-we-7 9+TPa m.

l

~

j 24 Corrective Actions Plug unsupported, dented tubes with projected usage factors exceeding 1.0 over the service life of the plant. Sentinel plugs should be employed j

to ensure that any fatigue crack initiation subsequent to plugging will produce a detectable leak before the tube completely severes and causes i

damage to adjacent tubes. Alternatively, the tube should be stabilized to preclude possible damage to adjacent tubes.

4

$UMMARY OF STAFF FINDINGS j

i 1.

For reasons cited in Reference 2, the staff concurs with the Westinghouse conclusions that (1) the failure of R9-C51 at North Anna Unit I was caused

)

by fatigue, (2) the alternating stress associated with fatigue crack initiation was in the 4 to 10 ksi range, and (3) fluid-elastic instability has reasonably been established as the only credible mechanism for producing

- displacements of sufficient magnitude to cause a fatigue failure.

Further, it has reasonably been established that such an instability is possible within the uncertainty bounes of key parameters such as. stability constants, J

damping ratio, and local flow peaking factors.

/

2.

Tr.e mean stress model developed by Westinghouse (described in Section 3.3.1) provides a reasonable reconciliation of the estimatec stress level versus the observed nunber of cycles to failure for R9-C51 at North Anna. As discussed in Section 3.3.1, the staff believes that IGA cannot be entirely discounted as a contributor to fatigue crack initiation.

If IGA did play a role, a mean stress effect as severe as that assumed by Westinghouse is not necessary to explain fatigue crack initiation for tube R9-C51 at North Anna Unit 1.

Nevertheless, the finds 'that the assumed 3 sigma, lower bound [

]

S/N curve stemming.from the Westinghouse mean stress model should lead to conservative results.

s.

,a__ _ _ _ _ - _ _ _ _ _

m

-r

--+r

/

b

., i,p i

t 25 3.

The staff fincings herein are based on the premise that stress ratto and fatigue estimates will be based on the assumption of a full sean stress effect(i.e.,yieldstress). Westinghouse analyses show that if a tube is simply clamped at the upper support (due to support plate correstas) without actual distortion of the tubes, then the mean stress will be less than the yield stress, and thus only a partial mean stress correction of the S/N L

curve need be considered. However, the staff believes that a full mean stress adjustment is necessary to ensure a conservative analysis since the potential influence of small IGA penetrations in initiating fatigue cracks i

has not been directly considered in the Westinghouse model.

4.

Westinghouse's stress ratio method for identifying susceptible tubes, as I

identified in Section 3.3.6, does not ensure that unsupported, dented tubes remaining in service will have stability ratios less than 1.0, even if all such tubes exhibit nominal damping.

Lower-than-nominal damping would l

further increase the stability ratio.

The stress ratio method is intendeo to ensure that tubes which exhibit a fluid-elastic instability and which still remain in service will exhibit cisplacement and stress responses which j

are sufficiently small to precluce a fatigue failure such as occurred at North Anna Unit 1.

j 5.

The stress ratio equation, as expressed in Equations 2 and 3, is an j

approximate relationship since for it to be strictly valid, the instabi.11ty response curves for the tubes being compared must be identical. For this to be cese, all fluid and mechanical properties and, most importantly, the i

flow field must be identical. This will generally not be the case. The staff notes, however, that Westinghouse's application of this equation has utilized conservative slopes (for the instability response curves) and

%e

i 26 fatigue usage has been calculated with conservative S/N curves. The staff concludes that the stress ratio approach developed by Westinghouse represents a sound engineering approach which, if properly implemented, will provide j

reasonable assurance against future failures of the kind which occurred at North Anna Unit 1.

6.

Given the complexity of the problem (e.g., two phase flow, U-tubes, denting)

I and the associated uncertainties, the Westinghouse analyses conducted with ATHOS and FLOVIB provide only "ballpark estimates" of the response amplitudes and instability thresholds. Absolute values of predicted critical velocities

.]

and displacement amplitudes in the instability region incorporate significant uncertainty. However, the results of these analyses are appropriate for the l

use that Westinghouse has made of them; namely to develop relationships

)

between relative stability ratios and the corresponding relative displacement and stress responses, thus permitting an assessment of the relative potential

]

for failure (compared to R9-C51 at North Anna Unit 1).

j 7.

The air model tests conducted by Westinghouse clearly demonstrate (1) the irportance of local flow peaking effects (due to non-uniform AVB insertien) as a contributor to fluid-elastic instability and (2) that particular AVB configurations lead to more severe flow peaking than other configurations.

]

It is especially noteworthy that the configuration associated with the failed North Anna tube was found to be among the nest susceptible'of all the configurations tested.

The earlier Westinghouse analysis in Reference 3, which considered lower-than-nominal damping to be the dominant contri-i butor to the North Anna failure, did not fully explain why the failure l

affected tube R9-C51 rather than higher row tubes which were also unsup-ported (by AVBs) and which exhibited nominal stability ratios (flow I

peaking not con-sidered) which were higher than that for R9-C51.

L

i

-2 4

.o

\\

I 27 8.

The air model tests show that flow peaking factors very quite significan-tly among different AVB configurations, even where the difference between configurations is relatively subtle. Great care and good judgement is j

required to ensure that flow peaking estimates are based on test data for idealized AVB configurations which are conservative for the actual AVB configurations in the field to which they are being applied. The staff j

will closely review the flow peaking factor esthtes as part of its plant-specific reviews.

i g.

Although local flow peaking appears to have been a major contributor to the

]

instability of R9-C51 at North Anna, low damping relative to the nominal I

values assumed by Westinghouse may also have been an important contributor.

This is evidenced by the fact that a number of tubes at North Anna Unit 1 located in rows 8 to 10 exhibited wall thinning indications at AVB support locations which Westinghouse speculated in Reference 3 may have occurred as a result of fluid-elastic excitation. Some of these tubes were located in regions of relatively uniform AVB penetrations where flow peaking effects j

l woulc be minimal.

l 20.

For plants where indications of centing were found in accordance with item A of Bulletin 88-02, all tubes in the region of interest should be assumed l

to be cented (pursuant to the oefinition of denting provided in the bulletin) i l

except for tubes for which the absence of denting on both the het and cold leg side has been specifically verified by inspection.

Some non-dented tubes in the region of interest may become dented at a later time.

Shoule the licensee elect not to plug undented tubes which would otherwise be pluggable based on the estimated stress rat:o and/or fatigue usage factor, the licensee should submit and comit to an appropriate inspection progran i

L for these tubes to ensure the timely detection of the onset of denting of l

these tubes in the, future.

b mm-e


w-

~* - -

.a ' s, #

28 I

11. Calculated stress ratios and projected fatigue usage factors are based on j

reference steam generator operating parameters (e.g., steam flow and pressure, circulation ratio) which are assumed to exist over the remaining i

life of the plant, The licensees should commit to developing achinistrative j

controls to ensure updated stress ratio and fatigue usage calculations are i

performed in the event of any significant changes to these operating para-l l

meters relative to the assumed reference conditions.

S CONCLUSIONS I

l Based on the above evaluation, the staff concludes that the Westinghouse generic

. program identified in Reference 1 and summarized in Section 3.3.6 of this SER is an acceptable approach for implementing Item C.2 of NRC Bulletin 88-07. The

{

l Westinghouse approach, if properly implemented, will provide reasonable assurance against future failures of the kind which occurred at North Anna Unit 1.

l REFERENCES i

1.

Westinghouse Report WCAP-11799 (Proprietury Version) and WCAP 11800 (Non-Proprietary Version), " Beaver Valley Unit - Evaluation for Tube Vibration Incuced Fatigue," April 1988. NRC Assession No. 8805160073.

l 2.

NRC Letter dated December 11, 1987 to Mr. W. L. Stewart, Virginia Electric and Power Company, enclosing proprietary and non-proprietary versions of staff's Safety. Evaluation authorizing 1001 power operation of North Anna Unit I following steam generator tube rupture event on July 15, 1987.

t 3.

Westinghouse Report WCAP-11601 (Proprietary Version) and WCAP-11602 (Non-Proprietary Version), " North Anna Unit 1 Steam Generator Tube Rupture and l

Remedial Actions Technical Evaluation," September 1987. NRC Accession Nos.

8710050087 and 8710050084 l-4.

[

]

5.

[

]

i l '1; a y*,

m

/.

6.

Westinghouse Report WCAP-12150 (Proprietary Version) and WCAP-12177 (Non-Proprietary Version), " Anti-Vibration Bar Insertion Depth anc Its Effect on U-Bend Flow Instability Velocity," January,1989. NRC Assession No. 8902270625.

O

'3 i

e O

.'s