ML20006E312
| ML20006E312 | |
| Person / Time | |
|---|---|
| Site: | 05000112 |
| Issue date: | 02/14/1990 |
| From: | Office of Nuclear Reactor Regulation |
| To: | |
| Shared Package | |
| ML20006E310 | List: |
| References | |
| NUDOCS 9002220622 | |
| Download: ML20006E312 (2) | |
Text
7, 9-l
UNITED 8TATES NUCLEAR REGULATORY COMMISSION
{
,f wAsmwoToN, D. C. MSS 6 y....+,f x
SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION SUPPORTING THE ORDER TERMINATING FACILITY LICENSE NO. R-53 UNIVERSITY OF OKLAHOMA AGN 211P NUCLEAR REACTOR DOCKET NO. 50-112
1.0 INTRODUCTION
By letter dated October 25,1988,(UOorthelicensee)submittedaplanforas supplemen 1989, the University of Oklahoma dismantlement and decontamination of their AGN 211P Nuclear Reactor Facility'and l
a request for termination of Facility License No. R-53. Following a review by the NRC staff, the plan was approved and the licensee comenced dismantlement and decontamination.
Upon completion of the dismantlement and decontamination, the licensee submitted a report, by letter dated August 28, 1989, entitled " Dismantling and Decomis-sioning Activities for the University of Oklahoma AGN 211P Nuclear Reactor Facility," as a basis for license termination. On October 11, 1989, Region IV staff conducted a termination survey at the facility.
2.0 EVALUATION 1
l-In a memorandum dated November 28,1989(A.BillBeach,RegionIV, tot.S.
Michaels, NRR) Region IV concluded that, based on their termination survey, the residual contamination levels for the reactor facility comply with the criteria
-of Regulatory Guide 1.86, Table I, which establishes acceptable residual surf ace contamination levels, and is below the exposure limit, established by the NRC staff, of 5 micro R/hr above background at one meter (see section 5.0 Reference).
Therefore, the facility can be released for unrestricted use.
3.0 ENVIRONMENTAL CONSIDERATION
i The Comission has prepared an Environmental Assessment (EA)Y41).
which was published in the FEDERAL REGISTER on February 9, 1990 (55FR4 On the basis of the EA and the above Safety Evaluation, the Commission has determined that no Environmental Impact Statement is required and that issuance of this j
Order terminating the license will have no significant adverse effect on the quality of the human environment.
I
4.0 CONCLUSION
Based on the foregoing considerations, the staff concludes that Facility l
License No. R-53 can be terminated without undue risk to the health and safety l
of the public or workers, and without any significant impact on the public or the environment.
2&CK05000122 900214 p
2 PD
h.
- 3..
ll 5.0 REFERENCE.
= MemorandumforF.J.Congel(NRC)toB.-M. Morris (NRC), June 7,1988,
Subject:
Response to Staff Requirements Memorandum of March 30, 1988.
i Principal Contributor: Theodore S. Michaels
' Dated:
February 14, 1990 l
F r.i
'I l.
i l
.y
~
l I
i