o

(

400 Chestnut Street Tower II s...

w\\

/4 June 25, 1981

~,

hkhgg@#e

.a b '}

BLRD-50-439/81-28 6 k'l w}

v.

'b

/

Mr. James O'Reilly, Director Office of I t, ion and Enforcement U.S. Nuclear R latory Conanission Region U - Sui 3100 101 Marietta Stre t Atlanta, Georgia 303

Dear Mr. O'Reilly:

s BELLEFONTE NUCLEAR PLANT UNIT 2 - CORROSION OF DIESEL GENERATOR CONTROL PAN!!L - BLRD-50-439/81 SECOND INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector J. Crlenjak on March 20, 1981, in accordance with 10 CFR 50.55(e) as NCR 1380. This was followed by our first interim report dated April 20, 1981. Enclosed is our second interim report. We expect to submi', our next report by October 6,1981.

If you have any questions concerning this matter, please get in touch with D. L. Lambert at FTS 857-2581.

Very truly yours, TENNESSEE VALLEY AUTHORITY L. P. Mills, Manager Nuclear Regulation and Safety Enclosure f

ec:

Mr. Victor Stello, Jr., Dimotor (Enclosure),V Office of Inspectice and Enforcement U.S. Nuclear Regulatory Conanission Washington, DC 20555 P

/[f 8106300 M S

o

D ENCLOSURE BELLEFCNTE NUCLEAR PLANT UNIT 2 CORROSION OF DIESEL GENERATOR CONTROL PANEL BLRD-50-439/81-28 SECOND INTERIM REPORT Description of Deficiency One of the Bellefonte diesel generator's control panels was improperly stored. As a result, the ferrous metal parts of the subcomponent y

voltage regulation panel have oxidised to the extent that the component is not capable of performing the function for which it was intended.

In addition, corrosion of other components in the control panel, plates, nuts, and bolts, etc., of the diesel have rendered it inoperable in its present condition.

' Interim Progress TVA has determined that the diesel's damaged voltage regulation panel must be repaired and recalibrated by the vendor (Transamerica Delaval). TVA has contacted the vendor, and the vendor has agreed to perform the repairs.

Accordingly, TVA is in the process of shipping the subject panel to the vendor.

-w