ML20004F730

From kanterella
Jump to navigation Jump to search
Proposed Changes to Table 4.1-1 & Tech Specs 4.5 & 4.12 Re Refueling Interval Surveillance
ML20004F730
Person / Time
Site: Crane 
Issue date: 06/15/1981
From:
METROPOLITAN EDISON CO.
To:
Shared Package
ML20004F726 List:
References
NUDOCS 8106220238
Download: ML20004F730 (6)


Text

_.

r

- )

s 00'

.H 9

O g

TABLE 4.1-1 (Continued)

M e.

M CllANNEL DESCRIPTION CllECK TEST CALIBRATE REMARKS CO 00 38.

Steam Generator Water Level W

NA R

l 39.

Turbine Overspeed Trip NA R*

NA 40.

Sodium Thiosulfate Tank Level NA NA R

Indicator 41.

Sodium flydroxide Taak Level NA NA R

Indicator 42.

Diesel Generator Protective NA NA R

Relaying I

43.

i KV ES Bus Undervoltage Relays NA M(1)

R (1) Relay operation will be checked (Diesel Start) by local test pushbuttons.

44.

Reactor Coolant Pressure S(1)

M R

(1) When reactor coolant system is Dli Valve Interlock Bistable pressurized above 300 psig of Taves is greater than 200 F.

S - Each Shift T/W - Twice per week R - Each Refueling Period D - Daily B/M - Every 2 months NA - Not Applicable W - Weekly Q - Quarterly B/W - Every two weeks M - Monthly P - Prior to each startup i

if not done previous week

  • Test to be performed prior to exceeding 20% power during Cycle 5 start up only.

s i

3

{

4.5 EMERGENCY LOADING SEQUENCE AND POWER TRANSFER, EMERGENCY CORE COOLING SYSTEM AND REACTOR BUILDING COOLING SYSTEM PERIODIC TESTING 4.5.1 E!fERGENCY LOADING SEQUENCE Applicability

-Applies to periodic testing requirements for safety actuation systems.

Obj ective To verify that the Emergency loading sequence and automatic power transfer is operable.

Specifications 4.5.1.l*

Sequence and Power Transfer Test a.

During each refueling interval, a test shall be condo' ted to demonstrate that the emergency loading sequence and power trrasfer is operable.

b.

The test will be considered satisfactory if the following pumps and fans have been successfully started and the following valves have completed their travel on preferred power and tran?ferred to the emergency power as evidenced by the control board ccmponent operating lights, and either the station computer or pressure / flow indication.

- M. U. Pump

- D. H. Pump and D. H. Injection Valves and D. H. Supply Valves

- R. B. Cooling Pump

- R. B. Ventilators

- D. H. Closed Cycle Cooling Pump

- N. S. Closed Cycle Cooling Pump

- D. H. River Cooling Pump

- N. S. River Cooling Pump

- D. H. and N. S. Pump Area Cooling Fan

- Screen House Area Cooling Fan

- Spray Pump. (Initiated in oincidence with a 2 out of 3 R. B. 30 psi Pressure Test Signal.)

  • This test shall be performed prior to Cycle 5 criticality.

l 4.5.1.2 Sequence Test a.

At intervals not to exceed 3 months, a test shall be conducted to demon-strate that the emergency loading sequence is operable, this test shall be performed on either preferred power or emergency power.

b.

The test will be considered satisfactory if the pumps and fans listed in 4.5.1.lb have been successfully stcrted and the valves listed in 4.5.1.lb have completed their travel as evidenced by the control board conponent operating lights, and either the station computer or pressure / flow indi-cation.

Bases The Emergency loading sequence and automatic power transfer controls the oper-ation of the pu=ps associated with the emergency core cooling system and Reactor Building cooling system.

4-39

T U

.t 31 cy m

4.5.2 EMERGENCY CORE COOLING SYSTEM e

_ Applicability s

Applies to. periodic, testing requirement for emergency core cooling systems.

-Objective' s

To verify that the-emergeacy core cooling systems are operable.

t Specification

- 4. 5. 2.1' High' Pressure Injection a.

During each refueling interval. and following maintenance or modification that affects system flow characteristics, system pumps and system high point vents shall be vented, and a system test shall be conducted to

~

l demonstrate that the system is operable.*

-s The M. U. Pump and its required supporting auxiliaries will be started manually by the operator and a test signal will be applied to the

'high p. essure injection valves MU-V-16A, B, C, D to demonstrate actua-tion of the high pressure injection system for emergency core cooling.

operation.

a b.

The test will be considered satisfactory if the valves have completed their travel and the M.'U. Pumps are running as evidenced by the control board component operating lights. Minimum acceptable injection flow must be greater than or equal to 500 gpm per HPI pump when pump discharge pressure lis 600 psig'or greater (the' pressure between the pump-and flow limiting device) and when the RC pressure is equal to or less than 600 psig.

i

.c.

Testing which requires HP1 flow thru MU-V16A, B, C, D shall be con-j ducted only under either of the following condit..ns:

1) T avg. shall be greater than 3200F.

I

2) Head of the Reactor Vessel shall be removed.
  • The High Pressure Injection Test shall 'tua performed prior to Cycle 5 criticality. l 1

4.5.2.2

- Low Pressure Injection a.

During each refueling period. and following maintenance or modification that.affects system flow characteristics, system pumps and high point vents shall be vented, and a system test shall be conducted to demonstrate that the system is operable. The auxiliaries required t

for low pressure injection are all included in the emergency loading sequence specified in 4.5.1.**

l b.

The test will be considered sa'tisfactory if tLe decay heat pumps 1

~

listed in 4.5.1.lb have been successfully started and the decay heat.

injection valves and the decay heat supply valves have completed their travel as evidenced by the control board component operating lights. Flow shall be verified to b( equal or greater than the v

flow assumed in the Safety Analysis for the single corresponding

-RCS~ pressure used in the test.

i E

4-41

90

.b.

Reactor Building Cooling and Isolation System 1.

During each refueling. period,~a system test shall be conducted to demonstrate proper operation of the system.* A test signal l

will actuate the R.B. emergency cooling system valves to demonstrate operability of the co31ers.

2.

The test will be considered satisfactory if the valves have completed the'.r expected travel as evidenced by the control board component operating lights, and either the station-couputer or local verification.

  • The system test shall be conducted prior to heatup following Cycle 4 refueling.

l 4.5.3.2 cor.ponent Tests a.

At intarvals not to exceed three months, the components required for reactc r building cooling and isolation will be tested.

b.

The test will be considered satisfactory if the valves have completed their expected travel as evidenced by the control board ccmponent operating lights, and either the station computer or local vetification.

Bases The reactor building cooling and isolation systens ant reactor building spray _

system'are designed to remove the heat in the. containment acrosphere to prevent the building pressure from excaeding the design pressure.

The delivery capability of one reactor building spray pump at a time can be tested by opening the valve in the line from the borated water storage tank, cpening the corresponding valve in the test line, and starting the corresponding pump.

With the pumps shut down and the borated water storage tank outlet closed, the reactor building spray injection valves can each be opened and closed by the operator action. With the reactor building spray inlet valves closed, low pressure air can be blown through the test connections of the reactor building spray nozzles to demonstrate that the flow paths are open.

The equipment, piping, valves and instrumentation of the reactor building cooling system are arranged so that they can be visually inspected. The cooling units and associated piping are located outside the secondary concrete shield. Personnel can enter the reacter building during power operations to inspect and maintain this equipment.

The reactor building fans are nortally operating periodically, constituting the test that these fans are operable.

Reference (D FSAR, Section 6 4,

.-a e

om.

e

y_t.-

4.12__. AIR TREATMENT SYSTEMS 4.12.1

EMERGENCY CONTROL ROOM AIR TREATMENT SYSTEM

(

Applicability

- Applies to the emergency control room a treatment system and associated-components.

- Obj ective

- To verify that this system and associated components will be able to perform its design functions.

Specification 4.12.1.]

At least every refueling interval or once every 18 months, whichever comes first, the pressure drop across the combined HEPA filters and charcoal adsorber banks of AH-F3A and 33 shall be demonstrar.ed to be less than 6 inches of water at system design flow rate (11G%).

4.12.1.2 a.*

The tests and sanole analysis required by Specifice.: ion 3.15.1.2 shall be perforned initially and at least once p c year for standby service or after every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of system operation and following significant painting, steam, fire or chemical release in any ventilation zone cewnunicating with the system that could contaminate the HEPA filters or charcoal adsorbers.

b.*

DOP testing shall be performed after each complete or partial replacement of the HEPA filter bank or after any structural maintenance on the system housing which t.ould affect the HEPA filter bank bypass leakage.

s c.*

Halogenated hydrocarbon testing shall be performed after each complete or partial replacement of the charcoal adsorber bank or af ter any structural maintenance on the system housing which could affect the charcoal adsorber bank bypass leakaya.

d.

Each AH-E18A and B (AH-F3A and B) fan / filter circuit shall be operating at least 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> every month.

i 4.12.1.3 At least once per Tefueling interval or once every 18 months, whichever comes first, automatic initiation of the Control Building isolation and recirculation Dampers AH-D28, 37, 39, and 36 shall be demonstrated as operable.

4.12.1.4 An air distribution test shall be performed on the HEPA filter bank 1-initially, and after any maintenance or testing that could affect the 4

air distribution within the system. The air distribution across the HEPA filter bank shall be uniform within I20%. The test shall be performed at 40,000 cfm (t10%) flow rate.

  • Surveillance to be performed prior to Cycle 5 criticality in lieu of once per refueling interval or once per 18 months.

1 5

4-55

,7-r s

r e

-. e w,,,,, -, -.

e p-

,-myr a-,-

m wa--eey

r

  • }, h. 95 W '

/1

(,

^9 a

4.12.2'LREACTOR BUILDING PURGE AIR. TREATMENT SYSTEM Applicability ~

e s.

-Applies to the reactor building purge air treatment system and associated U

-components.

Object!.ve To verify that this system and associated components will-be able to perform

.its design functions.

Specification 4

4.12. 2.~ 1' At least once per refueling interval or once per 18 months, whichever comes first it shall le demonstrated that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 6 inches of water at system design flow-rate (t10%).

4.12.2.2 a.* The tests and sample analysis required by Specification 3.15.2.2, l

shall be performed initially, once per refueling interval or

.18 months, wh!.chever comes first, or after each 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of operation ar following significant painting, steam, fire, or chemical rs_ ease in any ventilation zone communicating with the system th2t could contaminate the HEPA filters or churcoal adsorbers.

b.*

DOP testing shall be performed after each complete or partial l

replacement of a HEPA filter bank or after any structural maintenance ou the system housing which could affect HEPA frame bypass leakage.

c.*

Halogenated hydrocarbon testing shall be performed after each l

complete or partial replacement of a charcoal adsorber bank or

.af ter any structural maintenance on the system housing which could affect the charcoal adsorber bank bypass leakage.

d.*

The DOP and halogenated hydrocarbon testing shall be performed l

at the maximum available flow considering physical restrictions, i.e., purge valve position, and gaseous radioactive release criteria.

e.

The Reactor Building purge exhaust f ans AH-E7A and B shall be operated at least 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> every month, either during actual purging or using makeup air.

4.12.2.3 An air distribution test shall be performed on the HEPA filter bank initially and after any maintenance or testing that could affect the air distribution within the system. The air distribution across the HEPA filter bank shall be uniform within t20%. The test shall be performed at 25,000 cfm (Il0%) flow rate.

  • Surveillance to iie performed prior to Cycle 5 criticality in lieu of once per l

3 refueling interval or once per 18 months.

Bases Pressure drop across the combined HEPA filters and charcoal adsorbers of less

- l

.than 6 inches of water at the system design flow rate will indicate that the filters and adsorbers 'are not clogged by excessive amounts of foreign matter.

Pressure drop should be determined at least once every refueling interval to show system performance capability.

4-55b

-_