ML20004C987

From kanterella
Jump to navigation Jump to search
Tech Spec Table 3.3-11 for Fire Detection Instruments
ML20004C987
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 06/01/1981
From:
ARKANSAS POWER & LIGHT CO.
To:
Shared Package
ML20004C985 List:
References
NUDOCS 8106080125
Download: ML20004C987 (1)


Text

.

TABLE'3.3-11 h

FIRE DETECTION INSTRUMENTS INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE HEAT SM0KE 1.

Containment North Penetration Area-Upper 2/ Area 2/ Area North Penetration Area-Lower 2/ Area 2/ Area South Penetration Area-Upper 2/ Area 2/ Area South Penetration Area-Lower

-2/ Area 2/ Area

2.. Cable Spreading -

Portective Wire 4

3.

Switchgear Room Room 2100-Elve. 372 2-Room 2101-Elev. 372 2

4.

Remote Shutdown Panels 1

5.

Emergency Diesel Generator Rooms Room 2093-Elev. 369 1

2 Room 2094-Elev. 369 1

2 6.

Diesel Fuel Storage Vaults 1/ Vault 7.

Penetration Rooms North Penetration Area-Upper 2/ Room North Penetration Area-Lower 2/ Room South Penetration Area-Upper

-2/ Room South Penetration Area-Lower 2/ Room ARKANSAS ~ - UNIT 2 3/4 3-44

'8106080 M