First Interim Deficiency Rept,Originally Reported on 810427, Re Motors Rated 440 Volts on 480-volt Sys.Vendors Requested to Determine If Motors Mislabelled.Either New Nameplates or New Motors Will Be Required.Next Rept by 810826
ML20004C239
Person / Time
Site: Sequoyah 
Issue date: 05/28/1981
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
10CFR-050.55E, 10CFR-50.55E, SQRD-50-328-81, NUDOCS 8106020382
Download: ML20004C239 (3)


Text

.

t

. - ',W i '9 ;.a.

400 Chestnut Street Tower II

's May 28, 1981

,/

[

(')

SQRD-50-328/81-36 j 3t33 0 l't99 #

g% u hQMllN

~

\\^k i

Mr. Jcaos P.

eilly, Director b / y /, ' /

W Office of Inspoo on and Enforcement l

U.S. Nuclear Regul ry Comission Region II - Suite 31 101 Marietta Street Atlanta, Georgia 30303

Dear Mr. O'Reilly:

SEQUDYAH NUCLEAR PLANT UNIT 2 - MOTORS RATED 440 VOLTS ON A 480-VOLT SYSTEM - SQRD-50-328/81 FIRST INTERlM REPORT The subject deficiency was initially reported to NRC-CIE Inspector l

R. V. Crlenjak on April 27, 1981 in accordance with 10 CFR 50.55(e) ss NCR SQN EEB 8111. Enclosed is our first interia report. We expect to submit our next report by August 26, 1981. The enclosure contains justificatimas for operations of Sequoyah unit 2 before correcting this NCR.

If you have any questions, please get in touch with D. L. Lambert at FTS 857-2581.

Very truly yours, TENNESSEE VALLEY AUTHORITY l

i l

L. M. Mills, Manager Nuclear Regulation and Safety Enclosure co:

Mr. Victor Stello, Dizsotor (Enclosure) l Cffice of Inspection and Enforcement l

U.S. Nuclear Regulatory Cosaission 30/Y l

Washington, DC 20555

.s

/ l l

f f

810602o382

)

ENCLOSURE SEQUOYAH NUCLEAR PLANT UNIT 2 MOTORS RATED 440 VOLTS ON A 480-VOLT SYSTEM SQRD-50-328/81-36 10 CFR 50.55(e)

FIRST INTERIM REFORT Description of Deficiency There are six motors in unit 2 that have a nameplate voltage rating of 440 volts ac and are supplied from the 480-volt ao Class IE auxiliary power system of units 1 and 2.

NEMA'MG1-12.43, 1967, requires that induction motors must be capable of operating under the steady-state running con-ditions with a voltage variation of plus or minus 10 percent at rated frequency. The maximum voltage these motors can withstand is 484 volts.

This contrasts with 506 volts that a motor rated 460 volts can withstand.

TVA design allows a maximum voltage of 506 volts at the motor terminals which is 15 percent above rated voltage for those motors rated 440 volts.

This discrepancy was discovered in the preparation of the field nameplate verification list on the 480-volt shutdown board load. This deficiency also exists at Watts Bar Nuclear Plant and is documented as nonconformance report WBN EEB 8104. The following are the affected motors at Sequoyah unit 2.

(1) Component Cooling System Pumps 2A-A and 2B-B to C-S Inlet

. Isolation Valve (2-FCV-70-78)

(2) Component Cooling System Pumps 2A-A and 2B-B to C-S Inlet Isolation Valve (2-FCV-70-76)

(3) Diesel Generator 2A-A Engine 2A1 Lube Oil Circulation Pump Motor (4) Diesel Generator 2A-A Engine 2A2 Lube Oil Circulation Pump Motor i

(5) Diesel Generator 2B-B Engine 2B1 Lube Oil Circulation Pump Motor (6) Diesel Generator 23-B Engine 2B2 Lube Oil Circulation Pump Motor Interim Progress TVA is in the process of contacting the vendors of the six affected motors to determine if the ' motors are actually rated 460 volts ao or if the motors can withstand a normal operating voltage of the 460 volts plus 10 percent, or 506 volts. If the former is correct, the vendor will be requested to supply new nameplates indicating the correct rating. If the latter is true, the vendor will be requested to submit documentation supporting their judgement. If both are false, new motors rated 460 volts will be required and placed in operation at the earliest possible opportunity.

Interim Justification for Operation The maximum voltage available at the motor terminals from the 480-volt ac, Class IE auailiary power system is 460 volta plus 10 percent, or 506 volts l

ac, which is in excess of 110 percent of 440 volts.

If the motors are repeatedly and continuously exposed to terminal voltages in excess of 110 percent of their rated values, the motors may suffer some loss of life over an extended period of time. Thia loss of life could be attributed to two l

conditions that would be present:

i l

6.

1.

The available locked rotor current would increase but would be accompanied by a corresponding decrease in the accelerating time characteristic of the motor.

2.

There may be a very slight rise in the total temperature of the motor. Although a decrease of approximately 4 degrees C could result due to a decrease in the full load amperes at 115 percent rated voltage, an increase in the core losses may offset the decrease. The core losses would increase due to an increase in the total flux.

Loss cf life depends upon several factors such as how often the motors are started and how long tL2 motors remain under locked rotor conditions. The

[

core losses are predominantly a function of the reluctance of both the core l

and the air gap and the total flux.. The reluctance of the iron core is l

usually disregarded due to its relatively small magnitude in comparison l

with the reluctance of the air gap. Therefore, what increase occurs in the I

iron core losses may offset the temperature decrease cited in No. 2.

i In any case, whether the loss of life is realized due to condition No.1 or 2, the destructive mechanism would be a loss of mechanical durability and l

dielectric strength of the motor insulation system. The total failure of the insulation system would result in a surge of current, the magnitude of

[

which should trip the motor circuit breaker. If the motor breaker failed l

to open, the feeder breaker to the board would be. required to trip. This would constitute a failure in that train.

Simultaneous failure of " identical" motors subjected to identical operating -

conditions is very unlikely. The destructive mechanism discussed.above.

works on the " weak link" of the motor insulation system. It is not probable that this vulnerability will occur in the same location.and to the same degree in each motor. As a result, the destructive mechanism will act upon the vulnerable areas of different motors at a different anate, thereby making the probability of simultaneous failure of these motors quite small.

An additiocal operating characteristic is that the motor will develop 132 percent of motor-rated torque when subjected to 115 percent motor-rated voltage.

This situation should not affect the ability of the plant to operate safely. The four lube oil circulation pump motors are not required either l

for start up or operation of the diesel generators. The one-horsepower L

motors are required solely to circulate lube oil and maintain. minimum lube oil temperature when the diesels are not operating. Failure of these motors would result in a low lube oil temperature indication in the MCR.

Because an individual lubricating oil-system is provided for each diesel generator, a failure of this nature in one lubricating oil system will not jeopardize the operation of the other diesel engines.

Loss of life in the component cooling system pumps isolation valves is also nonsignificant in terms of safety. These motors are periodically inspected, tested, and serviced. Any damage which might be detected during these inspections would be dealt with in such a manner as to ensure operation of the motors. The continued schedule of maintenance considered in light of the low probability of failure of the insulation system coupled with the redundant (trained) nature of these motors represents a justification for operation of unit 2 at Sequoyah until such time as the alternatives listed in " Interim Progress

  • aoove' can be' exercisec.

~