LER-1981-022, /03L-0:on 810316,NRC Site Inspector Reported Finding Four 0.5-inch Holes Through Control Room Equipment Room East Fire Wall.On 810403,two Holes Found in Wall of Room 427B.Caused by Personnel Error |
| Event date: |
|
|---|
| Report date: |
|
|---|
| 3461981022R03 - NRC Website |
|
text
I' U. S. NUCLE AR RE%ULATORY COMMISSION NRC FORM 366 17-7 7 )
LICENSEE EVENT REPORT CONTROL BLOCK:
l l
l l
l (PLEASE PRINT OR TYPE ALL REQUIRED INFERMATl:N1
[.o l n l o l n l S l 11@l d l e l-l 0 l o l e l o l o l e l o l o j@l4 l1 l1 11111@l l
l@
o i 7
8 9 LICENSEE CODE 14 15 LICENSE NUVSEH 26 26 LlCENSE TYPE J0 67 CAT 58
"$"C ll.j@l e l s 1010 l e 1314 l 6 l@l 0 I111 l 6 l R 11 l@l 0 l 5 l 0 l 4 l 8 l 1 l@
COYT o i C0 68 DOCKE T NUMBER tid 63 EVENT DATE 74 75 REPORT DATE 80
'7 8
EVENT DESCRIPTION AND PROBABLE CONSEQUENCES h
@ lOIP-33-81-24) On 3/16/81, at 1300 hours0.015 days <br />0.361 hours <br />0.00215 weeks <br />4.9465e-4 months <br /> the NRC Site Inspector reported finding four j 4/3/81 inch unsealed holes through the Control Room Equipment Room east fire wall. on [o l3l [
lat 1440 hours0.0167 days <br />0.4 hours <br />0.00238 weeks <br />5.4792e-4 months <br />, the NRC Site Inspector found two inch unsealed holes in the north j
o 4 the station had entered the action statement of l
g l wall of room 427B.
In each case, There was no danger to the health and safety of the public or l
os l Tech. Spec. 3.7.10.
l to unit personnel. There was no fire which required the fire wall to have its l
o 7 l
l integrity intact.
80 oa CCMP.
VALVE SYSTEM
CAUSE
CAUSE CODE CODE SUBCCDE COMPONENT CODE SUSCODE SUSCODE FT97 i A I B l@ 'Ll@ LrJ@ l zl zl zl zl zl zl@ Lz_J@ L zJ @
7 8
9 10 11 12 13 18 19 20 REVISION SEQUENTIAL OCCURRENCE REPORT EVENT YE AR REPORT NO.
CODE TYPE No.
O"mj=R'ROl 81 1l
[_l lo1212i Ld IoI3i Lt_J 1, 1 Loj LE a
2.
u n
u u
n 2.
n 30 3
32
- IN 'AC
' Pt
'TU FO 8.
Lt M Nt TURfR iA f
O T
LxJ@Lx_]@
IJz._J@ LIJO Io I of ol oi I yl@
LN_J@
l Z l@
l Zl 9 l 9 l 9 l@
33 J4 36 sti 31 40 43 42 43 44 4;
CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h The personnel involved I
lThe cause of these occurrences was due to a personnel error.
i o were first opened.
When the holesI lshould have filled the holes with knowool when they i i Under Maintenance work I
lwere discovered, they were immediately filled with Knowool.
- I i 3 l orders 81-1837 and 81-2200 the holes were permanently filled with greut.
I i
1 4 l
80 7
8 9 STA S
% POWER oTHER STATUS 15 O RY OtSCOVERY DESCRIPTION l
[d5_) [Jjh l0 l714 lhl N/A l
lD l@l Reported by NRC Site Inspector ACTIVITY CO TENT LOCATroN OF RELE ASE RELEASED OF RELE ASE AMOUNT OF ACTivtTY l
( Zj @
@l N/A l
l N/A i 6 80 44 45 7
8 9 10 11 PERSONNEL E XPOSURES NUMBER TYPE
DESCRIPTION
1 l o l o l o l@[_Z_j@l N/A i 7 PERSoNNELiNdliES oESCRiPTiON@
1 NuM.E n lololol@l N/A i a 80 7
8 9 Il 12 LOSS OF OR DMt scE TO FACILITY l
TYPE
DESCRIPTION
[Zj@l N/A 9
80 7
8 9 to l
lllllllllllll$
es$UE @DESCR&PTION M
l N/A 810 5 08 () 2q So j 58 SS i-8 9 to ZAWR OF Pf1EPAHEH%%16t,ad PHONE: g;g)239 3000 m:t 299 8,
70LEDO EDISON CDIPANY DAVIS-BESSE NUCIEAR PGER STATICN UNIT ONE SUPPLDIENIAL INFORMATION EUR LER NP-33-81-24 DATE OF EVENT:
March 16, 1981 and April 3, 1981 FACILITY:
Divis-Besse Unit 1 INDENTIFICATICN OF OCCURRENCE:
Unsealed half-inch holes through fire walls Conditions Prior to Occurrence: The unit was in Mode 1, with Power (Mfr) = 2042.9 and Load (Gross ME) = 684 Description of Octmrrence: On March 16,1981 at 1300 -hours, the NRC Site Inspector -
reported finding four h inch unsealed holes through the Control Rocm Equignent Focm east fire wall. The holes open into the stairway east of the 03ntrol Ibcm and appear to have been left by the rcmoval of a plate frca the wall. The holes were Wintely filled with Kav.w3ol.
On April 3, 1981 at 1440 hours0.0167 days <br />0.4 hours <br />0.00238 weeks <br />5.4792e-4 months <br />, the NFC Site Inspector found two 15 inch unsealed loles in the north wall of rocm 427B, Ioa Voltage Switchgear Room. A firewatch was es-tablished until the holes were packed with Kaowool at 1535 hours0.0178 days <br />0.426 hours <br />0.00254 weeks <br />5.840675e-4 months <br />.
In each case, the Station had entered the action statenent of Ibchnical Specification 3.7.10.
The Technical Specification requires all penetration fire barriers protect-ing safety related areas to in functional at all times. The action statement re-quires that with a penetration fire barrier inoperable, establish a continuous fire watch on at least one side of the affected penetration within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. Both of these incidents were written up on DVR's and sulraitted April 3,1981.
Designation of Apparent Cause of Occurrence: The cause of this was personnel error as the holes should have been filled with Kaowool when they were first opened and the proper people should have been informed so the appropriate actions could have been taken to log the holes in the penetration log and to have the holes permanently filled with grout.
Analysis of Occurrence:
There was no danger to the health and safety of the public l
or to unit personnel. There was no fire which required the fire wall to have its integrity intact.
l
Corrective Action
The holes were ir:frediately filled with Kaowool and under Main-tenance Work Order's 81-1837 and 81-2200, the holes were permanently filled with I
grout.
Failure Data:
Previous violations of penetration fire barriers were reported in NP-33-80-11 (80-008), NP-33-79-63 (79-060), NP-33-79-61 (79-059), and NP-33-78-137 (78-117).
l LER f/81-022
..w
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000346/LER-1981-001, Forwards LER 81-001/01X-1 | Forwards LER 81-001/01X-1 | | | 05000346/LER-1981-001-01, /01X-1:on 810107,discovered Contractor Personnel on 801204 Disassembled Restraints Other than Those Requested & Failed to Perform Reassembly in Timely Manner. Caused by Inadequate Procedural Control | /01X-1:on 810107,discovered Contractor Personnel on 801204 Disassembled Restraints Other than Those Requested & Failed to Perform Reassembly in Timely Manner. Caused by Inadequate Procedural Control | | | 05000346/LER-1981-002-03, /03L-0:on 810102,reactor Coolant Pump 1-2 Was Shutdown Due to High Seal Return Temp & Deteriorating Seal Staging & on 810106,pump 2-1 Was Shutdown for Deteriorating Seal Staging.Caused by Seal Degradation.Seals Replaced | /03L-0:on 810102,reactor Coolant Pump 1-2 Was Shutdown Due to High Seal Return Temp & Deteriorating Seal Staging & on 810106,pump 2-1 Was Shutdown for Deteriorating Seal Staging.Caused by Seal Degradation.Seals Replaced | | | 05000346/LER-1981-002, Forwards LER 81-002/03L-0 | Forwards LER 81-002/03L-0 | | | 05000346/LER-1981-003-03, /03L-0:on 810106,breaker HX02B Tripped, de-energizing Bus B Which Reduced Electrical Distribution Less than Tech Specs Required.Caused by Personnel Error. Breakers Restored.Operators Counselled Re Attentiveness | /03L-0:on 810106,breaker HX02B Tripped, de-energizing Bus B Which Reduced Electrical Distribution Less than Tech Specs Required.Caused by Personnel Error. Breakers Restored.Operators Counselled Re Attentiveness | | | 05000346/LER-1981-003, Forwards LER 81-003/03L-0 | Forwards LER 81-003/03L-0 | | | 05000346/LER-1981-004, Forwards LER 81-004/03X-1 | Forwards LER 81-004/03X-1 | | | 05000346/LER-1981-005-03, /03L-0:on 810114,RCS Chloride Concentration Exceeded Tech Spec Limit.Caused by Use of Spotcheck in Cleaning Reactor Coolant Pump Seal Cavities.Instructions Issued for Use of Solvents in RCS | /03L-0:on 810114,RCS Chloride Concentration Exceeded Tech Spec Limit.Caused by Use of Spotcheck in Cleaning Reactor Coolant Pump Seal Cavities.Instructions Issued for Use of Solvents in RCS | | | 05000346/LER-1981-005, Forwards LER 81-005/03L-0 | Forwards LER 81-005/03L-0 | | | 05000346/LER-1981-006-03, /03L-0:on 810119,power Lost to Safety Features Actuation Sys Channel 1 Cabinet.Caused by Blown Supply Fuse from Panel Y-1 Due to Procedure Deficiency.Fuse Replaced & Procedure Modified | /03L-0:on 810119,power Lost to Safety Features Actuation Sys Channel 1 Cabinet.Caused by Blown Supply Fuse from Panel Y-1 Due to Procedure Deficiency.Fuse Replaced & Procedure Modified | | | 05000346/LER-1981-006, Forwards LER 81-006/03L-0 | Forwards LER 81-006/03L-0 | | | 05000346/LER-1981-007, Forwards LER 81-007/03L-0 | Forwards LER 81-007/03L-0 | | | 05000346/LER-1981-007-03, /03L-0:on 810122,door 306 Found Partially Open,So That Spent Fuel Pool Emergency Ventilation Sys Could Not Have Maintained Area at Correct Pressure.Caused by Maladjusted Door Closure.Maint Work Order Issued | /03L-0:on 810122,door 306 Found Partially Open,So That Spent Fuel Pool Emergency Ventilation Sys Could Not Have Maintained Area at Correct Pressure.Caused by Maladjusted Door Closure.Maint Work Order Issued | | | 05000346/LER-1981-008, Forwards LER 81-008/03L-0 | Forwards LER 81-008/03L-0 | | | 05000346/LER-1981-008-03, /03L-0:on 810127,345 Kv Switchyard Bus K Tripped & Locked out,de-energizing Startup Transformer 02.Caused by Action from Directional Ground Current Relay & Charred Phase Lightning Arrestor C on Startup Transformer | /03L-0:on 810127,345 Kv Switchyard Bus K Tripped & Locked out,de-energizing Startup Transformer 02.Caused by Action from Directional Ground Current Relay & Charred Phase Lightning Arrestor C on Startup Transformer | | | 05000346/LER-1981-009-03, /03L-0:on 810128,diesel Generator 1-2 Could Not Be Started W/Left Side Set of Air Start Motors During Diesel Generator Surveillance Test 5081.01.Caused by Failure of One Air Start Motor Due to Broken Solenoid Drive Shaft | /03L-0:on 810128,diesel Generator 1-2 Could Not Be Started W/Left Side Set of Air Start Motors During Diesel Generator Surveillance Test 5081.01.Caused by Failure of One Air Start Motor Due to Broken Solenoid Drive Shaft | | | 05000346/LER-1981-009, Forwards LER 81-009/03L-0 | Forwards LER 81-009/03L-0 | | | 05000346/LER-1981-010, Forwards LER 81-010/03L-0 | Forwards LER 81-010/03L-0 | | | 05000346/LER-1981-010-03, /03L-0:on 810202,MSIV Bypass Valve Ms 100 a Failed to Close.Probably Caused by Component Failure.Actuator Spring Adjusted to Increase Tension Until Valve Would Close | /03L-0:on 810202,MSIV Bypass Valve Ms 100 a Failed to Close.Probably Caused by Component Failure.Actuator Spring Adjusted to Increase Tension Until Valve Would Close | | | 05000346/LER-1981-011, Forwards LER 81-011/03L-0 | Forwards LER 81-011/03L-0 | | | 05000346/LER-1981-011-03, /03L-0:on 810205,post-accident Monitoring Instrument HPI Flow 1-2 Was Declared Inoperable.Caused by Bad Current Buffer.Current Buffer Was Repaired,Recalibr & Reinstalled.Hpi Flow 1-2 Was Returned to Operable Status | /03L-0:on 810205,post-accident Monitoring Instrument HPI Flow 1-2 Was Declared Inoperable.Caused by Bad Current Buffer.Current Buffer Was Repaired,Recalibr & Reinstalled.Hpi Flow 1-2 Was Returned to Operable Status | | | 05000346/LER-1981-012-03, /03L-0:on 810212,control Rod 1-3 Absolute Position Indication Declared Inoperable Due to Fluctuating Signals Causing Asymmetric Rod Alarms.Exact Cause Undetermined,But Absolute Position Indication Leads Picking Up Noise | /03L-0:on 810212,control Rod 1-3 Absolute Position Indication Declared Inoperable Due to Fluctuating Signals Causing Asymmetric Rod Alarms.Exact Cause Undetermined,But Absolute Position Indication Leads Picking Up Noise | | | 05000346/LER-1981-012, Forwards LER 81-012/03L-0 | Forwards LER 81-012/03L-0 | | | 05000346/LER-1981-013-03, /03L-0:on 810218,control Room Normal Ventilation Dampers Tripped Shut Resulting in No Power Available to Chlorine Detector 1 Above Control Room or in Block House. Caused by Failure of 10 Amp Fuse of Circuit Y111 | /03L-0:on 810218,control Room Normal Ventilation Dampers Tripped Shut Resulting in No Power Available to Chlorine Detector 1 Above Control Room or in Block House. Caused by Failure of 10 Amp Fuse of Circuit Y111 | | | 05000346/LER-1981-013, Forwards LER 81-013/03L-0 | Forwards LER 81-013/03L-0 | | | 05000346/LER-1981-014-03, /03X-1:on 810226,decay Heat Valve 64 Would Not Open During Testable ECCS Valves Quarterly Test.Caused by Loose Set Rod Bushing,Allowing Gear Box Set Rod to Move Which Unlocked Limit Switches from Adjusted Position | /03X-1:on 810226,decay Heat Valve 64 Would Not Open During Testable ECCS Valves Quarterly Test.Caused by Loose Set Rod Bushing,Allowing Gear Box Set Rod to Move Which Unlocked Limit Switches from Adjusted Position | | | 05000346/LER-1981-014, Forwards LER 81-014/03X-1 | Forwards LER 81-014/03X-1 | | | 05000346/LER-1981-015-03, /03L-0:on 810227,access Door 107 Found Propped Open from ECCS 2 Pump Room 115 to Miscellaneous Waste Monitor Tank & Pump Room 114.Caused by Failure to Follow Posted Signs While Clearing Odor from Room | /03L-0:on 810227,access Door 107 Found Propped Open from ECCS 2 Pump Room 115 to Miscellaneous Waste Monitor Tank & Pump Room 114.Caused by Failure to Follow Posted Signs While Clearing Odor from Room | | | 05000346/LER-1981-015, Forwards LER 81-015/03L-0 | Forwards LER 81-015/03L-0 | | | 05000346/LER-1981-016, Forwards LER 81-016/03L-0 | Forwards LER 81-016/03L-0 | | | 05000346/LER-1981-016-03, /03L-0:on 810308,dose Equivalent I-131 Level Exceeded Tech Spec Limit.Caused by Gas Leakage Through Fuel Cladding.Levels Monitored | /03L-0:on 810308,dose Equivalent I-131 Level Exceeded Tech Spec Limit.Caused by Gas Leakage Through Fuel Cladding.Levels Monitored | | | 05000346/LER-1981-017-03, /03L-0:on 810309,train 2 Hpi/Low Pressure Injection cross-connect Isolation Valve Dh 63 Would Not Open from Control Room During Quarterly Valve Surveillance Test 5051.13.Caused by Faulty Torque Switch in Valve Operator | /03L-0:on 810309,train 2 Hpi/Low Pressure Injection cross-connect Isolation Valve Dh 63 Would Not Open from Control Room During Quarterly Valve Surveillance Test 5051.13.Caused by Faulty Torque Switch in Valve Operator | | | 05000346/LER-1981-017, Forwards LER 81-017/03L-0 | Forwards LER 81-017/03L-0 | | | 05000346/LER-1981-018-03, /03L-0:on 810322 & 0401,chlorine Detector Ae 5358B Tripped.First Trip Probably Caused by Fouled Detector. Detector Cleaned.Detector & Circuit Board Replaced After Second Failure | /03L-0:on 810322 & 0401,chlorine Detector Ae 5358B Tripped.First Trip Probably Caused by Fouled Detector. Detector Cleaned.Detector & Circuit Board Replaced After Second Failure | | | 05000346/LER-1981-018, Forwards LER 81-018/03L-0 | Forwards LER 81-018/03L-0 | | | 05000346/LER-1981-019-03, /03L-0:on 810323,fluctuating Signals W/Numerous Asymmetric Rod Alarms Received,Resulting in Control Rod 4-7 Absolute Position Indication Inoperability.Probably Caused by Electrical Penetration Module Deficiency | /03L-0:on 810323,fluctuating Signals W/Numerous Asymmetric Rod Alarms Received,Resulting in Control Rod 4-7 Absolute Position Indication Inoperability.Probably Caused by Electrical Penetration Module Deficiency | | | 05000346/LER-1981-019, Forwards LER 81-019/03L-0 | Forwards LER 81-019/03L-0 | | | 05000346/LER-1981-020-03, /03L-0:on 810324,valve CV5011A,on Containment Air Sample Inlet Line to Hydrogen Analyzer,Would Not Stroke Closed W/Monitor Operator.Caused by Badly Worn Tripper in Motor Operator.Tripper Levers Replaced | /03L-0:on 810324,valve CV5011A,on Containment Air Sample Inlet Line to Hydrogen Analyzer,Would Not Stroke Closed W/Monitor Operator.Caused by Badly Worn Tripper in Motor Operator.Tripper Levers Replaced | | | 05000346/LER-1981-020, Forwards LER 81-020/03L-0 | Forwards LER 81-020/03L-0 | | | 05000346/LER-1981-021-03, /03L-0:on 810401,half Trip Occurred from Steam & Feedwater Rupture Control Sys Channel 1 Low Steam Generator Level Trip.Caused by Power Supply Failure.Power Supply Replaced Per Work Order on 810402 | /03L-0:on 810401,half Trip Occurred from Steam & Feedwater Rupture Control Sys Channel 1 Low Steam Generator Level Trip.Caused by Power Supply Failure.Power Supply Replaced Per Work Order on 810402 | | | 05000346/LER-1981-021, Forwards LER 81-021/03L-0 | Forwards LER 81-021/03L-0 | | | 05000346/LER-1981-022, Forwards LER 81-022/03L-0 | Forwards LER 81-022/03L-0 | | | 05000346/LER-1981-022-03, /03L-0:on 810316,NRC Site Inspector Reported Finding Four 0.5-inch Holes Through Control Room Equipment Room East Fire Wall.On 810403,two Holes Found in Wall of Room 427B.Caused by Personnel Error | /03L-0:on 810316,NRC Site Inspector Reported Finding Four 0.5-inch Holes Through Control Room Equipment Room East Fire Wall.On 810403,two Holes Found in Wall of Room 427B.Caused by Personnel Error | | | 05000346/LER-1981-023-03, /03L-1:on 810403,decay Heat Cooler Outlet Valve CC1467 Stroked Closed During Component Cooling Water Monthly Test & Would Not Reopen.Caused by Excessive Wear on Actuator Due to Design Deficiency.Actuator Rebuilt | /03L-1:on 810403,decay Heat Cooler Outlet Valve CC1467 Stroked Closed During Component Cooling Water Monthly Test & Would Not Reopen.Caused by Excessive Wear on Actuator Due to Design Deficiency.Actuator Rebuilt | | | 05000346/LER-1981-023, Forwards LER 81-023/03L-1 | Forwards LER 81-023/03L-1 | | | 05000346/LER-1981-024, Forwards LER 81-024/03L-0 | Forwards LER 81-024/03L-0 | | | 05000346/LER-1981-024-03, /03L-0:on 810418,bus J Was Rapidly Taken Out of Svc W/O Providing for Alternate Power Supply for Decay Heat Pump 1-1.Caused by Personnel Error.Procedure Modified & Operator Informed of Mods | /03L-0:on 810418,bus J Was Rapidly Taken Out of Svc W/O Providing for Alternate Power Supply for Decay Heat Pump 1-1.Caused by Personnel Error.Procedure Modified & Operator Informed of Mods | | | 05000346/LER-1981-025, Forwards LER 81-025/03L-0 | Forwards LER 81-025/03L-0 | | | 05000346/LER-1981-025-03, /03L-0:on 810423,during Review of Safety Tagging Log,Unit Entered Mode 4 W/O Required Two Makeup Pumps Operable.Caused by Personnel Error.Pumps Restored to Operation.Personnel Reinstructed in Procedures | /03L-0:on 810423,during Review of Safety Tagging Log,Unit Entered Mode 4 W/O Required Two Makeup Pumps Operable.Caused by Personnel Error.Pumps Restored to Operation.Personnel Reinstructed in Procedures | | | 05000346/LER-1981-026-03, /03L-0:on 810428,reactor Protection Sys Channel 1 Tripped on Flux/Delta Flux/Flow.Caused by Failure of Flow Differential Pressure Transmitter Primary Power Transformer Shorting to Ground.New Amplifier Installed & Calibr | /03L-0:on 810428,reactor Protection Sys Channel 1 Tripped on Flux/Delta Flux/Flow.Caused by Failure of Flow Differential Pressure Transmitter Primary Power Transformer Shorting to Ground.New Amplifier Installed & Calibr | |
|