PORTLAND GENERAL ELECTRIC COMPANY THE CITY OF EUGENE, OREGON PACIFIC POWER AND LIGHT COMPANY DOCKET NO. 50-344 TROJAN NUCLEAR PLANT AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 57 License No. NPF-1 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment by Portland General Electric Company, the City of Eugene, Oregon, and Pacific Power and Light Company (the licensee) dated November 30, 1977 and November 12, 1980, as supplemented January 21, 1981, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (f) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and secur'ty or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
e
'810so s o gy
~
. 2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this ifcense amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-1 is hereby amended to read as follows:
(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 57, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications, except as noted in paragraphs 2.C.(10) through 2.C.(12) below.
3.
This license amendment is effective upon entry into Operaticnal Mode 3 (Hot Standby) prior to startup for fuel cycle 4.
FOR THE NUCLEAR REGULATORY COMMISSION t
obert A. Clark, Chief Operating Reactors Branch #3 Div'. sten of Licensing
Attachment:
Changes to the Technical Specifications Date of Issuance: April 16, 1981 9
4 e,-
,,--,n
~,
- - -, - + -
-a-m -, -
-e,-
--.-r---
t ATTACHMENT TO LICENSE AMENDMENT AMENDMENT NO. 57 TO FACILITY OPERATING LICENSE NO. NPF-1 DOCKET NO. 50-344 Revise Appendix A as follows:
Remove Pages Insert Pages i
VII VII 3/4 8-4 3/4 8-4 l
3/4 8-11 3/4 8-12 3/4 8-13 3/4 8-14 3/4 8-15
s INDEX LIMITING CONDITIONS FOR OPERATION AND SURVEILLANCE REQUIREMENTS SECTION Page 3/4.7.2 STEAM GENERATOR PRESSURE / TEMPERATURE LIMITATION...... 3/4 7-12 3/4.7.3 COMPON ENT COOLING WATER SYSTEM....................... 3/4 7-13 3/4.7.4 SE RV I C E WATER SYSTEM................................. 3/4 7-15 3/4.7.5 ULTIMATE HEAT SINK...................................
3/4 7-17 3/4.7.6 CONTROL ROOM EHERGENCY VENTILATION SYSTEM............
3/4 7-18 3/4.7.7 SE ALED SOURCE CONTAMI NATION.......................... 3/7 7-21 3/4.7.8 FIRE SUPPRESSION SYSTEMS Fi re Suppression Wa ter System........................ 3/4 7-23 l
S p r i nkl e r Sys tems.................................... 3/4 7-27 F i re Ho s e S tati o n s................................... 3/4 7-29 3/4.7.9 PENETRATION FIRE BARRIERS............................
3/4 7-31 3/4.7.10 HY DRAU LIC SEU B B E RS................................... 3/4 7-32 3/4.7.11 CONTROL BUILDING MODIFICATION CONNECTION BOLTS.......
3/4 7-37 3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C. SOURCES 0 p e ra ti n g............................................ 3/4 8-1 Shutdown.............................................
3/4 8-5 3/4.8.2 ONSITE POWER DISTRIBUTION SYSTEMS A.C. Di stribution - Operating........................ 3/4 8-6 A.C. Di stribution - Shutd own......................... 3/4 8-7 D.C. Di stributi on - Operati ng........................ 3/4 8-8 D. C. Di s tri bu ti on - Sh utd own......................... 3/4 8-10 3/4.8.3 UNDERVOLTAGE PROTECTION 4.16 kV Emergency Bus Undervoltage Protection........ 3/4 8-11 TROJ AN-UNIT 1 VII Amendment N. Jg, 37, f/, 50, 57
3 ELECTRICAL POWER SYSTEMS SURVEILLANCE REOUIREMENTS (Continued) d)- Verifying that on diesel generator trip, the loads are shed from the emergency busses and the diesel re-star s on the auto-start signal, the emergency busses are energized with per-manently connected loads, the auto-connected emergency loads are energized through the load sequencer and the diesel operates for > 5 minutes while its generator is loaded with the emergency loads.
4.. Verifying the diesel generator set operates > 60 minutes while loaded to > 3364 kw.
Verifying that the auto-connected loads to each diesel 5.
generator unit do not exceed the 2000 hcur rating of 4752 kw.
- c. wAt least once per 18 months by verifying that each fuel trans-
' fer pump transfers fuel frem each fuel storage tank to the day tank of each diesel via the installed cross connection lines.
.fTROJAN-UNIT 1 3/4 8 2 Amendment No. 57 s_
s ELECTRICAL POWER SYSTEM 3/4.8.3 UNDERVOLTAGE PROTECTION 4.16 kV EMERGENCY BUS UNDERVOLTAGE PROTECTION LIMITING CON 0iTION FOR OPERATION 3.8.3.1 The 4.16 kV Emergency Bus Undervoltage Protection instrumen-tation shown in Table 3.8-1 shall be OPERABLE with their trip set-points set consistent with the values shown in the Trip Setpoint col-umn of Table 3.8-2.
APPLICABILITY: As shown in Table 3.8-1.
ACTION:
With a 4.16 kV Emergency Bus Undervoltage Protection instru-a.
mentation channel trip setpoint exceeding the value shown in Table 3.8-2, declare the channel inoperable and apply the applicable ACTION requirement of Table 3.8-1 until the channel is restored to OPERABLE status with the trip setpoint adjusted consistent with the Trip Setpoint value.
b.
With a 4.16 kV Emergency Bus Undervo!tage Protection instrumen-tation channel inoperable, take the ACTION shown in Table 3.8-1.
SURVEILLANCE REQUIREMENTS 4.8.3.1 Each 4.16 kV Emergency Bus Undervoltage Protection instrumen-tation channel shall be demonstrated OPERABLE by the performance of
,the CHANNEL CALIBRATION and CHANNEL FUNCTIONAL TEST operations during the modes and at the frequencies shown in Table 4.8-1.
- TROJAN-UNIT I 3/4 8-11 Amendmeat No. 57
4 TABLE 3.8-1, 4.16 kV EMERGENCY BUS UNDERVOLTAGE PROTECTION INSTRUMENTATION f
MINIMUM g3 TOTAL NO.
CHANNELS CitANNELS APPLICABLE 2
FUNCTIONAL UNIT OF CHANNELS TO TRIP OPERABLE MODES ACTION P
E a.
4.16 kV Emergency Bus
- 1 Undervoltage (Loss of Voltage) 4/ Bus 1/2 Twic" 3/ Bus 1, 2, 3*
1 j
r.
-l b.
4.16 kV Emergency Bus Undervoltage (Degraded Voltage) 4/ Bus 1/2 Twice 3/ Bus 1, 2. 3*'
1 i
So M
i l
i 1
=.'
j 3) 2 E
'A a
.E 1
I i
TABLE 3.8-1 (Continued)
TABLE NOTATION
ACTION STATEMENTS ACTION 1 - With the number of OPERABLE channels one less than the Total Number of Channels, operation may proceed provided both of the following conditions are satisfied:
a.
The inoperable channel is placed in the tripped condition within one hour.
b.
The Minimum Channels OPERABLE requirement is met; however, one additional channel may be bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing per Specification 4.8.3 l
l l
TROJAN-UNIT 1 3/4 8-13 Amendment No. 57 i
TABLE 3.8-2 4.16 kV EMERGENCY BUS UNDERVOLTAGE PROTECTION INSTRUMENTATION TRIP SETPOINTS A
FUNCTIONAL UNIT TRIP SETPOINT ALLOWABLE VALUES E
a.
4.16 kV Emergency Bus 2560 volts with a 2560 + 210 volts with a U
Undervoltage (Loss of 1.1 second time delay 1.1 + 0.1 second time delay Voltage) b.
4.16 kV Emergency Bus 3850 volts with a 3850 + 80 volts with a Undervoltage (Degraded 55 second time delay 55 + 3 second time delay Voltage)
M a
Z El a
2n
.O
=
~
TABLE 4.8-1 4.16 kV EMERGENCY BUS UNDERVOLTAGE PROTECTION INSTRUMENTATION SURVEILLANCE REQUIREMENTS g