ML20003A578

From kanterella
Jump to navigation Jump to search
Forwards Util Clarifications of Regulations for Fire Protection Design.Individual Isolation Valves Not Provided for Each Fire Hydrant.Sectional Isolation Valves Permit Isolation of Hydrants from Fire Main for Maint
ML20003A578
Person / Time
Site: Summer 
Issue date: 01/30/1981
From: Nichols T
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Harold Denton
Office of Nuclear Reactor Regulation
References
NUDOCS 8102040321
Download: ML20003A578 (2)


Text

i 5

SOUTH CAROLINA ELECTRIC a GAS COMPANY m

g,

,mr c,,,a o u u,

Cotums:A,SourH CAnoLINA 29218 T. C;. NICHots, Jn. -

v.c.c. m.. e:..

t..:.~,

January 30, 1981

.x a.. c,....,

(:

I?.

~

fir.HaroldR.Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555

Subject:

Virgil C. Summer Nuclear Station Docket No. 50/395 Fire Protection

Dear Mr. Denton:

On October 27, 1980, the Commission approved for publication in the Federal Register a new section 50.48 and Appendix R to 10CFR Part 50 delineating certain fire protection provisions for nuclear power plants li-censed to operate prior to January 1,1979.

Although this fire protection rule does not apply to the Virgil C. Summer Nuclear Station, the applicant has reviewed this regulation against the fire protection design. Our initial review indicates general compliance with minor exceptions or clari-fications listed on the attached sheet.

If, in later detailed reviews, further clarifications or exceptions are noted, we will inform you.

If you have any questions, please let us know.

Very truly yours, l

,, A f, ',.JV 1 $, /

J T. C. Nichols, Jr.

RBC:TCN:rh Enclosures cc:

V. C. Summer G. H.

Fischer T. C. Nichols, Jr.

E. H. Crews, Jr.

O. W. Dixon, Jr.

W. A. Williams, Jr.

O. S. Bradham D. A. Nauman R. B. Clary A. R. Koon A. A. Smith J. B. Knotts, Jr.

J. L. Skolds B. A. Bursey H. N. Cyrus NPCF/Whitaker 810 204 0 U\\

File

FIRE DETECTION - APPENDIX R III.

C.

Individual isolation valves are not provided for each fire hydrant; however, sectional isolation valves permit isolation of hydrants from the fire main for maintenance or repair.

F.

Automatic fire detection systems are provided in accordance with commitments made in the V. C. Summer Nuclear Station Fire Protection Evaluation which has been submitted to the NRC.

These fire detection systems are capabic of operating with or without offsite power.

G.2 In some cases where low fire loading exists, separation of redundant cable is provided by a 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> fire barrier on one train. NRC represer-tatives listed this as an acceptable way to meet separation requiremento in our meeting with NRC in the Fall of 1979.

G.3 The control room was considered as an area which required alternative shutdown capability.

The control room, which is continuously manned, is provided with area smoke detectors, fire standpipes and hose cabinets, and manual fire extinguishers. We have taken tha position, as indicated in the Fire Protection Evaluation,.that fixed fire suppression is not needed in this area.

N.

An automatic total flooding CO suppression system is provided in the 2

Control Building for the relay room and the computer rooms. The computer rooms contain no equipuent required for safe shutdown. All doors into the relay room are self-closing fire doors.

Five doors into the relay room are alarmed security doors (i.e., electrically supervised).

Two doors between the relay room and the cable chases are self-closing fire doors but not alarmed. The permanent records storage room is provided with a llalon gas suppression system; the doors to this room, which contains no safe shutdown equipment, are not alarmed.

i