LER 80-123/03L-0:on 801219 & 801226,turbine Trip & Throttle Valve on Reactor Core Isolation Cooling Sys Failed.Failures Caused by Gall on Valve Poppet & Body & Improper Limit Switch Setting.Gall Removed & Switch Reset