Appendix A NOTICE OF VIOLATION f
Wisconsin Public Service Corporation Docket No. 50-305 Based on the results of NRC inspection conducted on August 1-31, 1980, it appears that certain of your activities were not conducted in full compliance with conditions of your NRC Facility License No. DPR-43 as indicated below. This is an infraction.
10 CFR Part 50, Section 50.55a(g) in part requires holders of an operating license to implement ASME Code Section XI requirements to test selected pumps and valves.
Contrary to the above, the licensee failed to fully implement ASME Code Section XI testing requirements to insure the operability of safety related equipment in that:
a i
1.
The monthly inservice inspection tests were not conducted on High Head Safety Injection Pumps, Residual Heat Removal Pumps, Auxiliary Feedwater Pumps (Motor Driven), Component Cooling Water Pumps, and Containment Spray Pumps during the May-June refueling outage or within one week after the plant was returned to normal operation on June 24, 1980.
2.
The quarterly inservice inspection tests of Category A and B valves associated with Surveillance Procedures 098, 099, 104, 167-1, 167-3 and 167-5 were not performed in accordance with IWV-3410 of Section XI.
3.
Reference values as specified in table IWP-3100-1 were not established for the turbine Driven Auxiliary Feedwater Pump.
4.
Limiting valves for stroke time have not been specified on the~ inservice data sheet for the following valves associated with SP-167-6:
SI-15A & B; RHR-300A & B; RHR-400A & B; LD-6; CVC-211, 212; RBV-1, 2, 3, 4; VB-10A & B; FW-12A & B; ICS SA & B, 6A & B; and CI-1001A & B.
l 1