-,j Lo
- TXX-90024 F1 e # 10130
~
~
IR 50-445/89-84 h
C C
IR 50-446/89-84 M# ELECTRIC Ref. # 10CFR2.201 January 19, 1990 wnu J.c.wu,Jr.
Esecutuve Vke President U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington,.D.C.
20555
SUBJECT:
COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)
DOCKET NOS. 50-445 AND 50-446 NRC INSPECTION REPORT NOS. 50-445/89-84; 50-446/89-84 RESPONSE TO NOTICE OF VIOLATION Gentlemen:
TU Electric has reviewed the NRC's letter dated December 21,.1989, concerning the inspection conducted by Mr. R. M. Latta and NRC consultants during the
-j period November 8 through December 5,1989. This-inspection covered activities authorized by NRC Construction Permits CPPR-126 and U PR-127 for y
CPSES Units 1 and 2.
Attached to the NRC's letter was a Notice of Violation.
TU Electric Fereby responds to the Notice of Violation in the attachment to this letter.
-l Sincerely, e
William J. Cahill,~Jr.
l WJH/bjh Attachment
(
c - Mr. R. D. Martin, Region IV l
Resident Inspectors, CPSES (3) i
.I 4
i E(
9001250039 900119 l
ADOCK0500g5 DR (pl
$}
400 Nonh Olive Street LR81 Dallas, Texas 73201
~_
i Attachment to TXX-90024 l
Page 1 of 2 NOTICE OF VIOLATION (445/8984-V-01) l f-Criterion V of Appendix B to 10 CFR Part 50 as implemented by Section 5.0 of f
the TU Electric Quality Assurance Manual requires that activities affecting quality shall be prescribed by and accomplished in accordance with documented instructions, procedures, or drawings.
Paragraph 3.2.2.1 of Electrical Installation Specification 2323-ES-100, Revision 6, requires that cable support systems shall be installed in accordance with the engineer's drawings and Appendix N of this specification.
Contrary to the above, the NRC inspector observed a cable grip which was-improperly suspended from the end of electrical penetration assembly E-76 module located inside the isolation tank for the containment spray motor operated valve 1-HV-4782. The improperly suspended cable gri) bail was located at the module polymer seal which could have damaged tie penetration seal and/or the Kapton insulted wires associated with'the penetration. The observed cable support configuration was contrary to the requirements of the applicable Design Change Authorization 59365, Revision 1.
RESPONSE TO NOTICE OF VIOLATION (445/8984-V-01)
TU Electric accepts the violation and the requested information follows.
1.
Reason for the Violation A review of records indicates the subject cable grip was initially installed in December 1987, removed in January 1988,'and reinstalled -in March 1988. The records review-also indicates that the cable grip bail was properly located at the completion of both the initial installation and subsequent reinstallation..TU-Electric has been unable to conclusively determine how the cable grip became mislocated.
However, the configuration of this cable grip installation is such that the cable grip bail could be relocated without being, disassembled.
It. is possible that the cable grip bail may have been relocated during other work activities in the area.
2.
Corrective Steos Taken and Results Achieved l
The Kapton insulation on the associated wires was inspected by QC and evaluated by engineering for damage. No damage was identified.
TU Electric does not consider that mislocation of the cable grip bail could damage the electrical penetration.
s
--,,ea r-
1 Attachment to TXX-90024 Page 2 of 2 The cable grip bail has been properly located per a Work Order.
A review was conducted to identify other cable grip installations where the cable grip bail can be relocated without the cable grip being disassembled. An additional three such installations were identified.
These three installations were examined by engineering personnel and all i
three cable grip bails were found to be properly located.
3.
Corrective Steos Which Will be Taken to Avoid Further Violations The cable grip installation identified in the NOV and the three other similar installations are all located inside valve isolation tanks.
These tanks are located inside locked rooms which have been turned-over to Nuclear Operations.
Entry into the valve isolation tanks requires a confined space entry permit and a specific work order. As a result, the q
4 level of work activity in these tanks is much less than during the
~'
construction phase. TU Electric considers that these conditions provide j
adequate assurance that unauthorized relocation of the cable grips will not occur in the future. Additionally, protective wraps have been installed over the Kapton insulated conductors.
4.
Date When Full Comoliance Will be Achieved Full compliance has been achieved.
!l i
I i
l i
1 l
!