r O

PHILADELPHIA ELECTRIC COMPANY 23O1 MARKET STREET P.O. BOX 8699 PHILADELPHI A. PA,19101 12151841-4502

..... = :: :: = : _

0EC 171980 Mr. Boyce Grier, Director United States Nuclear Regulatory Commission Office of Inspection and Enforcement, Region 1 631 Park Avenue King of Prussia, PA 19406

Subject:

USNRC IE Region Letter dated 11/18/80 RE: Site Inspection of October 7-30, 1980 Inspection Report No. 50-352/80-19 6 50-353/80-17 Limerick Generating Station - Units 1 5 2 File: QUAL 1-2-2 (352/80-19 6 353/80-17)

Dear Mr. Grier:

In response to the subject letter regarding items identified during the subject inspection of construction activities authori:ed by NRC License Nos.

CPPR-106 and -107, we transmit herewith the following:

Attachment I - Response to Appendix A Should you have any questions concerning these items, we would be pleased to discuss them with you.

Sincernly, C

JMC/mmk Attachment i

31 0223 0 \\@.

/

t ATTACHMENT I RESPONSE TO APPENDIX A Item of Noncompliance Infraction Appendix B, of 10CFR50, Criterion V, states in part:

" Activities affecting quality shall be accomplished in accordance with these instructions, procedures or drawings The Limerick PSAR, Appendix D, Quality Assurance Program, paragraph D.6.4 states, in part, that:

"Bechtel Constru

.o a Department is responsible for construction of the plant to approved engineering specifications, drawings, and procedures...."

The Specification for the Erection of Structural Cteel, 8031-C-63, paragraph 8.4.1, states in part, that:

"Any proposed method of correction for other than misaligned holes shall be submitted to the Project Field Engineer for approval.".

Contrary to the above, on October 21, 1980, control rod drive jet barrier plate, 39P-1, on drawing 8031-C43EE-54-2, reference drawing C-972, was observed to have been field trimmed such that a bolt hole did not meet the AISC for minimum edge distance.

No evidence was available to indicate that the Project Field Engineer (or his designee) had authorized the alteration.

Response to Infraction The minimum edge distance problem was reviewed by Project Engineering.

The field obtained Project Engineering approval on December 5, 1980 to plug veld and delete the bolt hole from the design of barrier plate 39P-1 after field alignment and trimming, thus-eliminating the minimum edge distance. violation.

The plug. weld is complete.

To prerent recurrence Specification 8031-C-63 is being reviewed and will be revised to more clearly distinguish those items which are minor, and those-which are major and require engineering evaluation and approval.

The specification revision will be completed by January 15, 1981.

I 1/1 50-532 19 50-532 18 a

L.

m m

m m

a.

.