Responds to IE Bulletin 80-25, Operating Problems W/Target Rock Safety Relief Valves at Bwrs. During Valve Assembly,At Wyle Lab,Checks Will Be Made to Ensure That Solenoid Actuators Are Free of Loc-Tite Pior to Operation
ML19350C314
Person / Time
Site: Brunswick  Duke Energy icon.png
Issue date: 03/20/1981
From: Furr B
CAROLINA POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
IEB-80-25, NO-81-489, NUDOCS 8103310904
Download: ML19350C314 (2)


Text

F

/ 7%

q

~7 Carolina Power & Light Company March 20, 1981 I I'!? Pd f; ^

n FILE: NG-3514 (B)

SERIAL [ 489

~

m c)

Mr. James P. O'Reilly, Director

[.

[, /

p.

U. S. Nuclear Regulatory Commission u[

hgg e

4///g8 Region II 9

101 Marietta Street, Suite 3100

_.c 44.kg

'4 h g [Q 0 8/J Atlanta, GA 30303

\\' \\

lxi BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS.'1?& 2 b

&>h N LICENSE NOS. DPR-71 AND DPR-62 DOCKET NOS. O M RESPONSE TO IE BULLETIN 80-25

Dear Mr. O'Reilly:

In response to your letter of December 19, 1980, transmitting IE Bulletin No. 80-25, Operating Problems with Target Rock Safety Relief Valves of BWR's, Carolina Power & Lighu Company is providing the following response with respect to the Brunswick Steam Electric Plant:

The Brunswick Steam Electric Plant is currently purchasing two-stage target rock safety relief valves for installation in Brunswick Unit Nos. 1 and 2.

During the assembly of these valves at WYLE Laboratories, appropriate checks will be made to ensure that the solenoid actuators are free of Loc-Tite prior to operation. An inspection will be made of each of these actuators and a signed statement concerning its condition will become a part of the purchase order file on the safety relief valve.

Appropriate changes to the plant Operating Manual have been made to ensure that in the event that a safety relief valve, regard-less of make or model (e.g., both two or three stage), fails to function as designed, excepting for pressure set point requirements, and the cause of the malfunction is not clearly determined, understood, and therefore corrected, that the entire valve be removed from service, disassembled, inspected, adjusted, and pressure set point tested with steam for proper operation prior to returning the valve to service. These overhaul requirements shall be at least equivalent to those applicable to periodic surveillance rehabilitation require-ments.

A review of the instrument air system supply to the safety i

relief valves has revealed that the maximum air pressure from the r.ain air compressor is limited by a relief valve set at 135 + 5 psig.

The air pressure from the emergency compressors is limited by relief valves set at 125 psig. Discussions with the vendor indicate that the two-stage Target Rock safety relief valves have previously been 8103310707 411 Fayetteville Street

  • P. O. Box 1551
  • Raleign. N. C. 27602

Mr. James P. O'Railly subjected to air actuation pressures of 145 psig without introducing spurious or unplrnned valve operation.

Therefore, the 135 psig limited actuation supply pressure at BSEP is corsidered totally acceptable.

An alternate means of pressurizing the air headers with nitrogen from the CAD system is available; however, a manual valve isolates this back-up supply from the air headers.

Independent pressure control valves which limit the pressure of the nitrogen line to less than 90 p;is 22i relief valves set at 100 + 3 psig limit the pressure to within acceptable !imits for proper safety relief valve operation.

Sufficient protective devices, therefore, exist to protect against supply pressures in excess of the safety relieve valve capability from all sources.

There presently exists a low pressure annunciator and Control Room indication of the main air supply pressure to the Reactor Building dual instrument air headers. Additional low pressure annunciators on each Reactor Building air header also alarm in the Control Room. A high pressure annunciator on each air header will be added to warn the operator of excessive air pressure. The location of these high and low pressure switches will be such that each supply to the air headers will be monitored.

Yours very truly, W