ML19350B552

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 81-06, Failure of Ite Model K-600 Circuit Breaker. No Written Response Required
ML19350B552
Person / Time
Site: Clinton  
Issue date: 03/11/1981
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Gerstner W
ILLINOIS POWER CO.
References
NUDOCS 8103200873
Download: ML19350B552 (2)


Text

.

\\*

0)

Y

~/

'/

g[f' r },Q.\\

Docket No. 50-461 9

Docke. No. 50-462 86=J-I MAR 171981 4

Illinois Power Company 6

.f ATTN:

Mr. W. C. Gerstner

"* M iu Y "

',/

Executive Vice President q

(

500 South 27th Street Ah i

T\\ I' Decatur, IL 62525 Cu cc

' nel:

tral Files AD/ Licensing AD/ Operating Reactors PDR Local PDR NSIC TIC Mary Jo Murray, Office of Assistant Attorney General Gary N. Wright, Deputy Director Randall L. Plant, Prairie Alliance 4

8103200 D 3

O

'o UNITED STATES

[

~

g NUCLEAR REGULATORY COMMISSION t

.. s REGION 111 q

f 7se ROOSEVELT ROAD f

OLEN ELLYN,ILUNOIS so137 March 11, 1981 Gentlemen:

The enclosed IE Information Notice No. 81-06 contains information that may be applicable to your facility regarding the failure of an ITE Model K-600 circuit breaker. No specific action or response is requested at this time; however, pending the results of NRC staff evaluations of this matter, further licensee actions may be requested.

Should you have any questions regarding this information notice, please contact this office.

Sincerely, O

f$M

$! W D

[wJamesG.Keppler U Director

Enclosure:

IE Information Notice No. 81-06

~

SSINS No.:

6335 Accession No.:

8011040269 IN 81-06 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 March 11, 1981 IE Information Notice NO. 81-06:

FAILURE OF ITE H0 DEL K-600 CIRCUIT BREAKER

Purpose:

The purpose of this information notice is to provide early notification of a matter that could adversely affect the safety of nuclear power plants.

Toward this end, this information notice alerts holders of operating licenses and construction permits of a possibly generic deficiency involving Model K-600 circuit breakers manufactured by ITE.

Description of Circumstance:

By letter dated February 20, 1981, the Sacramento Municipal Utility District informed us that, while performing preventive maintenance on electrical circuit breakers at its Rancho Seco facility, an ITE Model K-600 breaker was observed not to trip.

An investigation revealed that a tripping coil wire had slipped out of its terminal.

Further examinations revealed that the coil wire size was AWG 20, whereas the mating lug was sized for AWG 16-14 wire. A check.of other ITE electrical breakers indicated that the problem may be generic.

Subsequent to the letter, the Sacramento Municipal Utility District informed us orally that ITE Model K-1600 breakers have the same deficiency and that Model K-3000 breakers may be similarly affected.

The information provided by the Sacramento Municipal Utility District is pre-liminary and will be followed by a complete. report. Consequently, we have not yet evaluated the safety significance of this event.

Nevertheless, the i

information herein is being provided as an early notification of a possibly I

significant event. Although no specific action or response is requested at this time, recipients should review the information for possible applicability I

to their facilities.

If NRC evaluations so indicate, further licensee actions j

may be requested.

If you have any question regarding the information contained herein, please contact the Director of the appropriate NRC Regional Office.

Attachment:

Recently issued IE Information Notices l

Attachment IN 81-06 March 11, 1981 RECENTLY ISSUED IE INFORMATION NOTICES Inf ormation Date of Notice No.

Subiect Issue Issued to 81-05 Degraded DC System at 2/10/81 All power reactor Palisades facilities with an OL or CP 81-04 Cracking in Main Steam 2/27/81 All power reactor Lines facilities with an OL 81-03 Checklist for Licensees 2/12/81 All power reactor Making Notifications of facilities with an Significant Events in OL Accordance with 10 CFR 50.72 81-02 Transportation of 1/23/81 All Radiography Radiography Devices licensees 81-01 Possible Failures of 1/16/81 All power reactor General Electric Type facilities with an HFA Relays OL or CP.

80-45 Potential Failure of 12/17/80 All PWR facilities BWR Backup Manual Scram with an OL or CP Capability 80-44 Actuation of ECCS in the 12/16/80 All PWR facilities Recirculation Mode While with an OL or CP in Hot Shutdown 80-43 Failures of the Continuous 12/5/80 All power reactor Water Level Monitor for facilities with an the Scram Discharge Volume OL or CP at Oresden Unit No. 2 80-42 Effect of Radiation on 11/24/80 All power reactor Hydraulic Snubber Flutu facilities with an OL or CP 80-41 Failure of Swing Check 11/10/80 All power reactor Valve in the Decay Heat facilities with an Removal System at Davis-OL or CP Besse Unit No. 1 OL = Operating Licenses CP = Construction Permits