ML19350B185

From kanterella
Jump to navigation Jump to search
Forwards Revised IE Bulletin 81-01, Surveillance of Mechanical Snubbers, W/Corrected Pages 5 & 6.Change in Identification of Facilities W/Cp to Which Bulletin Is Applicable Does Not Affect Util Requirements
ML19350B185
Person / Time
Site: Seabrook  
Issue date: 03/04/1981
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Tallman W
PUBLIC SERVICE CO. OF NEW HAMPSHIRE
References
NUDOCS 8103200058
Download: ML19350B185 (1)


Text

T:' i jty UNITED STATES

[97 g

NUCLEAR REGULATORY COMMISSION a e REGION I g /g M' D [ U e\\

.f _

631 PARK AVENUE o

KINO OF PRUS$f A, PENNSYLVANIA 19406 Docket Nos. 50-443 MAR 4 1981

%' 3 50-444 g

IT Public Service Company of New Hampshire 5

k g 2 3 7ggI A C

-3 ATTN: Mr. W. C. Tallman 6

,,** QD'c's Chairman and Chief Executive Officer 4

1000 Elm Street g

Manchester,, New Hampshire 03105 g

Gentlemen:

IE Bulletin No. 81-01, " Surveillance of Mechanical Snubbers," transmitted to you on January 27, 1981, has been revised to change the identification of the power reactor facilities with construction permits to which the Bulletin is applicable.

This change does not affect your requirements with respect to the original Bulletin. As a result, the enclosed revised pages 5 and 6, are forwarded to you for information.

If ydu desire additional information regarding this matter, please contact this office.

Sincerely, CB a

oy e H. Grier Director

Enclosures:

Revised pages 5 and 6 of IE Bulletin 81-01 and List of Recently Issued IE Bulletins CONTACT:

D. L. Caphton (215-337-5266) cc w/encls:

John DeVincentis, Project Manager k

8103200058

SSlNS No.:

6820 Accession No.:

8005050075 IEB 81-01 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 January 27, 1981 IE Bulletin No. 81-01:

SURVEILLANCE OF MECHANICAL SNUBBERS Description of Circumstances:

Several instances of failures of mechanical snubbers suppliec by International Nuclear Safeguards Corporation (INC) have been identified that indicate possible deficiencies in these snubbers. A summary of the failures that have occurred is provided below:

1.

On August 9, 1974, the Tennessee Valley Authority st.bmitted event report BFAD-50-260/741W identifying 11 of 14 INC Model MSVA-1A snubbers that were found inoperable on Browns Ferry Nuclear Power Station Unit 2 and subsequently identified 5 of 14 inoperable units on Browns Ferry Nuclear Power Unit No 3.

All of these units were found to be frozen, and the cause was attributed to a failure to lubricate the parts during assembly.

The failed snubbers were replaced with new units produced by the same manufacturer.

2.

On April 12, 1976, the St. Lucie Plant Unit 1 facility of Florida Power and Light Corporation submitted event report No. 50-335-76-9 wherein five INC Model MSVA-1 snubbers were identified as inoperable because they were found to be frozen.

The failures were caused by oxidation on the internals and by. improper assembly. All.INC. mechanical snubbers were replaced with

~

units produced by another ma'nufacturer.

3.

On April 8,1977, Iowa Electric Light and Power Company submitted event report No. 77-23 for the Duane Arnold Energy Center facility that identi-fied 13 INC Model IMSVA-1 Type AS snubbers to be frozen; the cause of failure was attributed to large amounts of interior oxidation.

The units were replaced with those produced by another manufacturer.

4.

On December 5,1979, personnel from the Nuclear Regulatory Commission visited Department of Energy (DOE) facilities at Richland, Washington, to obtain information on DOE experience with INC snubbers at the Fast Flux Test Facility (FFTF).

The DOE-owned FFTF m equipped with more than 4,000 mechanical pipe restraints (snubbers) supplied by INC.

In 1978, FFTF examined more than suu from their installation and Q DUPLICATE DOCUMENT were frozen. The plant was f seen no service and had bee vt Entire document previously environments for 1 to 2 yea y

entered into system under:

000$0 $00_l$

b ANO of c>

Attachment:

4 Recently is' sued I$ bull'etins y

No. of pages:

[

~-

e

?

Y Y