Enclosure to Serial: RSEP/81-225 OPERATING DATA REPORT DOCKET NO:

DPR-23 DATE:

610203 N" "" ; tsY:

M. L. Watford TELEP110NE:

(803) 383-452; OPERATING STATUS Notes: There are presently 113 Spent fuel assemblies

1. Unit Name:

H. B. Robinson Two

" "E*"

2. Reporting Period: 810101,0000/810131,2400 2
3. Licensed Thermal Power (MWt): 2300
4. Nameplate Racing (Gross MUe):

739

5. Design Electrical Rating (Net MWe):

700

6. Maximum Dependable Capacity (Gross MWe): 700
7. Maximum Dependable Capacity (Net MWe):

665

8. If Changes Occur in Capacity Ratings (Item Number 3 through 7) Since Last Report, Give Reasons:

No change None

9. Pouer Lcral to Which Restricted, If Any (Net P..'c);

N/A

10. Reasons For Restrictions, If Any:

This Month Yr.-to-Date Cumulative 744 744 86,910

11. Hours in Reporting Period 669.07 669.07 66,434.35
12. Number of Hours Reactor Was Critical 74.93 74.93 1,052.81
13. Reactor Reserve Shutdown Hours 661.40 661.40 6u,820.22
14. Hours Generator On-Line 0.00 0.00 23.20
15. Unit Reserve Shutdown Hours
16. Gross Thermal Energy Generated (MWH) 1,458,329 1,458 329 132,670,703 _
17. Gross Electrical Energy Generated (MWH) 479,925 479,925 42,818,692
18. Net Electrical Energy Generated (M6*H) 456.022 456.022 40.572.474 88.90 88.90 74.58
19. Unit Service Factor 88.90 88.90 74.61
20. Unit Availability Face.or.

92.17 92.17 70.20

21. Unit Capacity Factor (Using MDC Net) 87.56 87.56 66.69
22. Unit Capacity Factor 'Using DER Net) 11.10 11.10 13.84
23. Unit Forced Dutage Rate
24. Shutdowns Scheduled Over Next 6 } baths (Type, Date, and Duration of Each):

Steam Generator Inspection April - May,1981, 3 weeks Februarv 4, 1981

25. If Shut Down At End of Report Period, Estimated Date of Startup:

Forecast Achieved

26. Units In Test Status (Prior to Commercial Operation):

INITIAL CRITICAL *TY INITIAL ELECTI:1 CITY CO}DIERCIAL OPERATION (9/77) sg

(

=-

Enclorure to Serial:

RSEP/81-225 Page 2 of 3 DOCKET NO.

DPR-23 UNITS!!UTDOWNS AND POWEtt :lEDUCTIONS l>N:T N A*.* E 11.

B. Robinson Two D,\\TE 810203 COM."LETEI) l Y M.

L Watford

!!EPOICT MONTil January TEl.LPilONE (8011 1Rhos?4 h'3

).E E E L

Cause & Correceive Licensee Hw, E

Action su N.t.

Date g

5?

4 isU livent u '!

e fE e

3gg itepius a WO E

Prevent llecurrence gr o

e 5

f 01-01 810110 F

A 4

1111 VALVEX "A" Feedwater Reg. Valve (FWRV) oscillating, replaced faulty capacitors in summator (Load Reduction) 01-02 810123 S

B 4

lill PIPEXX "A" Main Feedwater Pp recirc.

line elbow leaking, elbow replaced I

(Load Reduction) 01-03 810124 F

17.42 B

3 lill llTEXCil "6B" FW litr. tube leaks, leaks weld repaired 01-04 810129 F

65.18 A

3 XX PUMPXX E.ll. Oil Pump (s) Failure - One was replaced due to seal problems and the other had a crack repaired on

,g the discharge unloader piping g

g 6

3 h?'e)

I 2

3 4

fl F: Forced Reauin:

Method:

Exhibit G Instructions y

S: Sshedu!cd A Equipment Failure (Explain) 1 M w n:I for Prep.ir.ition of Data 1:4taintenance of Test 2 Mannil Scra:n.

Entry Sheets for laecn.ee gg C 1;ct ueling 3.\\uionatic Scram.

Event Itep nl (1.1 lt i I de iNUREG.

D.Iternlatory Restriction 1-Othee (Explain)

Ol6i)

L-Opeutin Tr:.ining & License Examination F Asinunisto:ive 5

G.uperational I nur (Explain)

Exinbii I Same Source 9

(9/77)

Il Othes (E sp?ain)

r.nclosura to seriaA:

te r.r/ o t-443

]

11 age 3 of 3

. AVERAGE DAlt.Y UNIT l'0WER LEVEL DOCKET NO. DPR-23 H. B. Robinson Two WIT DATE 810203 M. L. Watford CO\\!PLE1 E D itY TELEPilONE (803) 383-4524 3!0NTl!

January, 1981 DAY AhERACE DAILY POWER LEVEL DAY AVER AGE D \\tLY POhER LEVEL (31We-Net) g 31We-Net) 724 1

722 37 722 708 2

jg 22 m

3 l9 a

723 4

608 20 720 722 5

21 723 722 6

)

7-24 661 7

321 g

723 24 723 42 9

35

~

589 714 10 26 11 721 27 689 722 722 12 28 00 13 29 723 30