Alabama Power Company

  • J.#

600 North 18th Street Post Office Box 2641 Birmingham. Alabama 35291 Telephone 205 250-1000 b

F. L CLAYTON, JRJ

' Senior Vice President Alabama Power December 8, 1980 Docket No. 50-364 c

Director, Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Phillips Building, Room 116 7920 Norfolk Avenue Bethesda, Maryland 20014 Attention: Mr. A. Schwencer JOSEPH M. FARLEY NUCLEAR PLANT - UNIT 2 POST ACCIDENT RECIRCULATION LEAKAGE Gentlemen:

In accordance with your request concerning NUREG-0737, Item III.D.1.1, Alabama Power Company calculated, for Unit 2, the maximum allowable leakage limits for systems outside containment that may carry radioactive fluids following an accident.

The maximum leakage limits based on 10CFR100 limits were provided in our letter to you on October 20, 1080. Alabama Power Company proposes a leakage limit for any of the systems, listed below, of 5 gpm which is well below the maximum limits determined by 10CFR100.

1.

The recirculation portion of the high pressure safety injection system.

2.

The containment spray system.

3.

The letdown and makeup portion of the reactor coolant system excluding mixed bed and cation bed demineralizer flow paths.

4.

The residual heat removal system.

5.

The recirculation portion of the low pressure safety injection system.

The limit of 5 gpm is reasonable for Farley Unit 2 because it takes into consideration actual leakage values measured for Unit 1 during the 1979 refueling outage, an allowance for measurement inaccuracies, and a tolerance which provides a margin that would prevent unnecessary shutdowns.

If there are any questions, please contact us.

/

Yours very truly, 3

C L.'Clayto J r. [

/ /

RWS:rt cc: See Page 2 0012280

)

1

\\

Mr. A. Schwencer December 8, 1980 t

I cc: Mr. R. A. Thomas Mr. G. F. Trowbridge Mr. L. L. Kintner Mr. W. H. Bradford n -

~,

-e n

,