ENCLOSURE 1 TABLE 3.3-12 FIRE DETECTION INSTRUMENTATION
~-
(~
l l
80122so3\\k
TABLE 3.3-12 FIRE DETECTIOBi INSTRUMENTATI0fl Auxiliary Building Total Minimum #
Smoke of Operable Room Description Elevation Detectors Smoke Detectors 2128 RHR Heat Exchanger Room 83'-0" 10 5
2129 RHR Low Head Pump Room 77'-0" 1
1 2131 RHR Low Head Pump Room 77'-0" l
1 2160 Hatch Area 100'-0" 2
1 2161 South Corridor 100'-0" 2
1 2172 Hallway 100'-0" 3
2 2173 Charging / Safety Injection Pump Room 100'-0" 2
1 2174 Charging / Safety Injection Pump Room 100'-0" 2
1 2175 Hallway 100'-0" 2
1 2181 Charging / Safety Injection Pump Room 100'-0" 2
1 2184 Mcchanical Penetration Room 100'-0" 8
4 2185 CCW Heat Exchanger and Pump Room 100'-0" 13 7-2186 Boric Acid Trans. PPS 100'-0" 3
2 2188 Boric Acid Tanks 121'-0" 2
1 2190 MCC Panel Room 100'-0" 4
2 2191 Auxiliary Feeswater Pump Room 100'-0" 1
1 2192 Auxiliary Feedwater Pump Room 100'-0" 2
1 2193 Auxiliary Feedwater Pump Room 100'-0" l
1 2202 Hot Shdtdown Panel Room 121'-0" 4
2 2208 Corridor 121'-0" 2
1 2209 Hallway 121'-0" 3
2 TABLE 3.3-12 FIRE DETECTION INSTRUMENTATION (cont'd)
Auxiliary Building (cont'd)
~
Total Minimum #
Smoke of Operable Room Description Elevation Detectors Smoke Detectors l
2210 South Corridor 1 21'-0" 2
1 2212 Battery Room 1A 121'-0" 1
1 2213 Battery Service Room 1 21'-0" 1
1 2214 Battery Room 1B 121'-0" 1
1 2223 Mechanical Penetration Room 121'-0" 9
5 2224 DC Switchgear Room 121'-0" l
1 2226 DC Switchgear Room 121'-0" l
1
"~
2227 West Cable Chase 128'-0" 7
4 2229 AC Switchgear Room Train B 1 21'-0" 4
2 t
l 2233 AC Switchgear Room Train B 1 21 '-0" 3
2 i
j 2241 Main Steam and Feedwater Valve Room 127'-0" 8
4 l
2244 Mezzanine 131 ' -O','
2 1
~
2245 Mezzanine 1 31'-0" 2
1 l
2254 Hot Shutdown Panel Room 121'-0" l
1 1
2300 West Cable Chase 139'-0" 7
4 l
2309 Hatch Area 139'-0" l
1 2312 Corridor 139'-0" 4
2 2316 Corridor 139'-0" 2
1 2318 Cable Spreading Room 139'-0" 8
4 2319 West Corridor 139'-0" 2
1 l '
TABLE 3.3-12 FIRE DETECTION INSTRUMENTATION (cont'd)
Auxiliary Building (cont'd)
Total Minimum #
Smoke of Operable Room Description Elevation Detectors Smoke Detectors 2333 Electrical Penetration Room 139'-0" l
1 2334 Electrical Penett tion Room 139'-0" 3
2 2335 AC Switchgear Room Train A 139'-0" 3
2 2343 AC Switchgear Room Train A 139'-0" 3
2 2347
. Electrical Penetration Room 139'-0" 2
1 2401 Control Room 155'-0" 4
2 2452 Storage Area 155'-0" 7
4 2462 Non-Radioactive Vent Equipment Room 155'-0" 5
3 2466 West Cable Chase 155'-0" 7
4 l
2471 Control Room (Instrument Racks) 155'-0" 12 6
2500 West Cable Chase 168'-2" 7
4 Total Minimum #
Smoke of Operable Fire Zone -
Description Elevation Detectors
~ Smoke Detectors
- Containment
~
l 55 Containment Coolers 155'-0" 12/ Fan 6/ Fan 55 Containment 155'-0" 14 7
- The Fire Detection instruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage Rate Tests. __
. ~ _
TABLE 3.3-12 FIRE DETECTION INSTRUMENTATION (cont'd)
Total Minimum #
Smoke of Operable Fire Zone Description Elevation Detectors Smoke Detectors Service Water Intake Structure 72 A Pump Room Area 188'-9" 12 6
72 A Strainer Bay 167'-0" 12 6
72 B Switchgear Room - Train B 188'-9" 2
1 72 C Foyer - Train B 188'-9" 1
1 72 D Foyer - Train A 188'-9" 1
1 72 E Switchgear Rocm - Train A 188'-9" 2
1 73 Battery Room - Train B 188'-9" 1
1 74 Battery Room - Train A 188'-9" l
1 i
Diesel Generator Building f
l 56 A Switchgear Room - Train A 155'-0" 12 6
i 56 B Foyer 155'-0" 4
2 56 C Switchgear Room - Train B 155'-0" 12 6
3 71 Hallway 155'-0" 9
5 i
0 Total Minimum #
Heat of Operable Fire Zone Description Elevation Detectors Heat Detectors l
Diesel Generator Building (Heat Detectors) 57 Diesel Driven Generator 2C 155'-0" 5
3 58 Diesel Driven Generator 1B 155'-0" 5
3 o o
TABLE 3.3-12 FIRE DETECTION INSTRUMENTATION (cont'd)
Total Minimum #
Heat of Operable Fire Zone Description Elevation Detectors Heat Detectors
~~
DieselGeneratorBuilding(HeatDetectors)(cont'd.)
59 Diesel Driven Generator 2B 155'-0" 5
3 60 Diesel Driven Generator 1C 155'-0" 5
3 61 Diesel Driven Generator 1-2A 155'-0" 5
3 62 Day Tank Room 155'-0" 1
1 63 Day Tank Room 156'-0" 1
1 64 Day Tank Room 155'-0" 1
1 65 Day Tank Room 155'-0" 1
1 66 Day Tank Room 155'-0" 1
1 Y
l-i l
, l I
S S
O ENCLOSURE 2 TABLE 3.7-5 LIST OF SPRINKLER SYSTEMS m
e-
TABLE 3.7-5 LIST OF SPRINKLER SYSTEMS Location Sprinkler (Room No.)
Description Elevation System 2160 Hatch Area 100'-0" 2A-25 2161 South Corridor 100'-0" 2A-25 2172 Hallway 100'-0" 2A-101 2175 Hallway 100'-0" 2A-118
^
2185 CCW Heat Exchanger and Pump Roca 100'-0" 2A-27 2190 MCC Panel Room 100'-0" 2A-62 2209 Hallway 121'-0" 2A-35 2210 South Corridor 121'-0" 2A-36 l
2223 Mechanical Penetration Room 1 21'-0" 2A-45 2227 West Cable Chase 128'-0" 2A-23 2244 Mezzanine 1 31'-0" 2A-36 2245 Mezzanine 1 31'-0" 2A-36 2300 West Cable Chase 139'-0" 2A-23 2312 Corridor 139'-0" 2A-48 2316 Corridor 139'-0" 2A-48 2318 Cable Spreading Room 139'-0" 2A-43 2319 West Corridor 139'-0" 2A-59 2452 Clean Storage Area 155'-0" 2A-108 2462 Non-Radioactive Vent Equipment 155'-0" 2A-51 Room 2466 West Cable Chase 155'-0" 2A-23 2500 West Cable Ch:5e 168'-2" 2A-23 FARLEY-UNIT 2 3/4 7-57 v-.,