ML19345B806

From kanterella
Jump to navigation Jump to search
Forwards LERs 80-069/01T-0,80-066/03L-0,80-068/03L-0, 80-070/03L-0,80-071/03L-0 & 80-072/03L-0
Date released: 12/25/2019 Download: ML19345B806


LER 80-072/03L-0:on 801031,river Water Train B Declared Inoperable When Pump 5 Tripped & Would Not Restart.Caused by Breaker Hea 86 Lockout Relay & 50G Instantaneous Overcurrent Relay Actuation
ML19345B840
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 11/26/1980
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19345B840 (1)
LER 80-071/03L-0:on 801027 & 28,containment Atmosphere Particuulate & Gaseous Radioactivity Monitoring Sys (R11 & R12) Declared Inoperable Due to Low Flow Pump Trips.Caused by Failing Bearings & Partially Opened Isolation Valve
ML19345B833
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 11/26/1980
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19345B833 (2)
LER 80-070/03L-0:on 801028,svc Water Bldg Train a Battery Sys Declared Inoperable Due to Low Cell Specific Gravity. Caused by Close Terminal Proximity & Poor Post Seal Design Allowing Formation of Acid Residue Which Shunted Current
ML19345B829
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 11/26/1980
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19345B829 (2)
LER 80-068/03L-0:on 801031,B Train River Water Pumps Declared Inoperable Due to Inadequate Lube & Cooling Water Flow.Caused by Dirty Strainers.Strainers Blown Down & Cleaned
ML19345B823
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 11/26/1980
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19345B823 (1)
LER 80-066/03L-0:on 801026,containment Atmosphere Particulate & Gaseous Radioactivity Monitoring Sys (R11 & R12) Declared Inoperable.Caused by Clogged Filter Paper from Stuck Filter Paper Takeup Reel Causing Pump Low Flow Trips
ML19345B816
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 11/26/1980
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19345B816 (1)
LER 80-069/01T-0:on 801112,water for Lubrication & Cooling of a Train Svc Water Pumps Found to Be Provided by B Train Water Header & Vice Versa.Caused by Design Error.Design Change to Provide Correct Separation Completed
ML19345B811
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 11/26/1980
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19345B811 (2)
Forwards LERs 80-069/01T-0,80-066/03L-0,80-068/03L-0, 80-070/03L-0,80-071/03L-0 & 80-072/03L-0
ML19345B805
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 11/26/1980
From: Clayton F
ALABAMA POWER CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References