05000366/LER-1980-153-03, /03L-0:on 801107,during Cold Shutdown,Test of Reactor Core Isolation Cooling Turbine Exhaust Isolation Valve 2ES1-F040 Revealed That Leakage Exceeded 10CFR50,App J Acceptance Criteria.Caused by Scratches on Valve Seat

From kanterella
(Redirected from ML19343B201)
Jump to navigation Jump to search
/03L-0:on 801107,during Cold Shutdown,Test of Reactor Core Isolation Cooling Turbine Exhaust Isolation Valve 2ES1-F040 Revealed That Leakage Exceeded 10CFR50,App J Acceptance Criteria.Caused by Scratches on Valve Seat
ML19343B201
Person / Time
Site: Hatch 
Issue date: 12/05/1980
From: Coggin C
GEORGIA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19343B195 List:
References
LER-80-153-03L, LER-80-153-3L, NUDOCS 8012150195
Download: ML19343B201 (2)


LER-1980-153, /03L-0:on 801107,during Cold Shutdown,Test of Reactor Core Isolation Cooling Turbine Exhaust Isolation Valve 2ES1-F040 Revealed That Leakage Exceeded 10CFR50,App J Acceptance Criteria.Caused by Scratches on Valve Seat
Event date:
Report date:
3661980153R03 - NRC Website

text

I w

U. S. NUCLE AR REGUL ATORY CO'.iMISSION NRC FOHM 30G (774 T

LICENSEE EVENT REPORT (a

CONTROL BLOCK: l l

l l

l l

l tPLE ASE PRINT OR TYPE ALL REQUIRED INFORM ATION) i e

[.G AI EI I Iill 2l @ l 0..]0_I-l0 l0 l0 l0 l0 l-l0 l0 l @l4 l1 l1 11 !I l @l l

l@

I o i F

8 9 LICENSEE CODE 14 tb LICENSL *evvu C H 25 26 LICENSE TYPE JJ bi L A T 16 CON'T loIil M"c'lLl@l015l0l0 01316l6L311111017l810l@ll121015I9lol@

S P

d t,4 61 DOC = ET.VV3 E H M

W EVE *4iDATE I4 7b PEPORT DAT E tia EVENT DESCRIPTION AND FROB ABLE CONSECUENCES h 1012110n 11-5-80. with Unit 2 in cold shutdown, an LLRT by procedur HNP 1 Io131 13952 was performed on the RCIC turbine exhaust isolation valve ?E51-F04RI 10111 10 n 11-7-80_3 when the LLRT coordinator reviewed the data it was deter-I lo151lained that the leakage exceeded 10CFR50 Appendix J acceptance criteria i

101c1Isection III.C.3 since the test volume could not be pressurized.

This ist lo l71 l a repeti tive occurrence - see LER _50-366/1980-152.

There were no ef-f lole l I fects on public health or safety due to this event.

I SYSTE*M

CAUSE

CALSE COVP.

VALVE CODE CODE SUSCODE COVPON E NT CODE SUSCOOE SveCCOE 1o191 I C l E l@ [f_j@ l F l@ IV l A ll l VI El XI@ l C l@ Lp_j @

7 8

9 to 11 12 13 18 19 20 SEQUENTI AL OCCURAENCE PEFCRT REVISION EVENT YE AR HEPORT NO.

COGE TYPE NO O "tg g pg 18101 L---J l 11 51 31 l-l 10131 W

L---J Lo_]

j(,g 21 22 23 24 26 27 23 29 Ju 31 22 TAKE ACT C PLA T vT NOUAS 22 5 8 1T D F R SUS.

5 DPL E VAN FA T HER Ln_J810 l@

LZ_J@

l 21 @

l OIO 101 I

lYl@

Q@

l A l@

lWl0l310l@

33 34 35 3/

43 41 47 43 44 gy CAUSE DESCRIPTION AND CORRECTIVE ACTIONS 2i 11 101IThe leakace of the RCIC turbine exhaust valve was due to scratches on I

i ithe seet of the valve which were probably caused by the valve closinc on!

11 l 21 I debri s.

The valve seat was polished to remove the scratches, and a suc-1 i a lcessful retest was performed by LLRT procedure HNP-2-3952 (as left leak-l i4 Iage = 300 accm).

1 80 I

7 8 9 A

% POV.E R OTHE R STATUS SO RY DISCOVERY DESCRtPTION l liIsI[L.j@ l0l0l0l@l NA l

l B l@i Performed LLRT l

i 80 i2 n

44

.s 46 Ae' Tivi TY CONTENT PELEASEO OF RE LE ASE AVOUNT OF ACTIVITY LOCATION OF RE LE ASF.

L ZJ @ [Z_j @ l NA l

l NA l

c 7

8 9 10 11 44 45 80 PE FISO*.*.E L E X POSUR E S NUYBER TYPE DE SCRIPTIO*J fi I 71 1 01 01 ol@LZ_J@l NA l

r

,E nsONNE L,.J ES otSCR.PfiON@

NuveEn 1 01 01 Ol@l NA l

i a 80 7

8 9 11 12 6055 OF OR D AV ACE TO F ACILITY Q TYPE D E SC AiP TIO*4

%./

I Zl@l NA l

i 9 80 7

d 9 to

    • 'cjEScm,,,0y @

S012150 (q

'Y NRC USE ONLY 17lnl

@l NA l

llllIllIiliIII 68 69 80 5 7

8 9 10 912-367-7781

{

w r nr pornnrn C. !. Cocoin...Suptm P1t. Ena. Serv.

Paoyt

O L

LER #:

50-366/1980-153 r

Licensee:

Ceorgia Power Company Facility Name:

Edwin I.

Hatch Docket #:

50-366

Narrative

Report for LER 50-366/1980-153 On 11-5-80, with Unit 2 in cold shutdown, a local leak rate test was performed per procedure HNP-2-3952,-

" Primary Containment Periodic Type B and Type C Leakage Tests", on the RCIC Lurbine exhaust isolation valve 2E51-F040.

On 11-7-80, the LLRT coordinator reviewed the LLRT in which the valve was found to be Icaking such that the test volume could not be pressurized.

Since the test volume could not be pressurized it must be assumed that the leakage exceeds the 30-day sealed water inventory acceptance criteria specified by

10CFR50, appendix J,

section III.C.3.

This is a repetitive occurrence see LER 50-366/1980-152.

There were no effects on public health or safety due to this event.

The Icakage of the RCIC turbine exhaust valve 2E51-F040 was due to scratches on the seat of the valve which were probably caused by the valve closing on debris.

The valve seat was polished to remove the scratches, and a retest was performed by LLRT procedure llNP-2-3952.

The retest leakage of 300 acem satisfied the acceptance criteria.

6