Text
% As/,A L
/w~'
'o.,
UNITED STATES l'
[3
,. Q" [r }j g j ec NUCLEAR REGULATORY COMMISSION REGION 1 0, ',
631 PARK AVENUE
%, ' U g KING oF PRUSSIA, PENNSYLVANIA 19406
- r..
2 October 31, 1980
.s Docket Nos. 50-352 S
50-353 3
fPi Philadelphia Electric Company
= H, "
.c
- ~-
ATTN:
Mr. John S. Kemper E
ad
~
Vice President j
'E Engineering and Research o
2
~
2301 Market Street Philadelphia, Pennsylvania 19101 Gentlemen:
The enclosed IE Information Notice No. 80-39, " Malfunctions of Solenoid Valves Manufactured by Valcor Engineering Corporation," is forwarded to you for information.
No written response is required.
If you desire additional infonration regarding this matter, please contact this office.
Sincerely, Bo me H. Grier Director
Enclosures:
1.
IE Information Notice No. 80-39 2.
List of Recently Issued IE Information Notices CONTACT:
D. L. Caphton (215-337-5266) cc w/encls:
V. S. Boyer, Senior Vice President, Nuclear Power E011140
~~
i SSINS No.:
6835 l'
Acc2ssien No.:
8008220245 IN 80-39 UNITED STATES l
NUCLEAR REGULATORY COMMISSION l
OFFICE OF INSPECTION AND ENFORCEMENT l
WASHINGTON, D. C. 20555 October 31, 1980 IE INFORMATION NOTICE NO. 80-39: MALFUNCTION OF SOLENOID VALVES MANUFACTURED BY VALCOR ENGINEERING CORPORATION PURPOSE:
The intent of this Information Notice is to alert holders of construction pemits and operating licenses for nuclear power plants of a potentially i
generic problem involving the malfunctioning of certain solenoid valves manu-factured by the Valcor Engineering Corporation (Valcor).
The solenoid valves so involved are designated as Valcar Valve Model No. V52600-554-1.
Valcor has informed us that these valves have only been supplied to the McGuire facility; however, since these valves were substituted for solanoid valves of another manufacturer that did not meet the requirements of IE Bulletin.No. 79-01 and its amendments, licensees and holders of construction permits should take into account the problem identified in this Information Notice prior to making any similar substitution.
BACKGROUND:
By TWX dated June 27, 1980, Valcor submitted a preliminary 10 CFR Part 21 Report addressing the malfunctioning of Valcor solenoid valves at the McGuire facility.
The malfunctioning valves have been identified as Valcor Valve Model No. 52500-554-L This TWX was subsecuently followed by a letter dated July 3,1980, transmitting a more detailed Part 21 Report entitled," Quality Assurance Report", a copy of which is attached hereto as Enclosure No. 1.
In brief, the malfunction appears to be an intermittent type wherein the valve fails to cycle from OPEN to CLOSE to CPEN immediately after a sustained period of operation in the energized (OPEN) mode.
Although the valves are rated for
" continuous operation", Valcor contends that the valves were not designed to meet the operating conditions requiring the immediate cycling from GPEN to CLOSE to OPEN after a sustained period of continuous energization.
A major source of the problem, therefore, may be a misunderstanding of the term
" continuous operation".
By letter dated July 14, 1980 to Duke Power Company, Valcor transmitted its recommendations in this matter entitled, " Outline -
Suggested Modification Procedures", a copy of which is attached hereto as Enclosure No. 2.
Enclosures:
alit Assurance Report DUPLICATE DOCUMENT Entire document previously entered into system under:
ANOh$d hf No. of pages:
1
-