ML19339B266

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-37, Containment Cooler Leaks & Reactor Cavity Flooding at Indian Point Unit 2. No Written Response Required
ML19339B266
Person / Time
Site: Seabrook  
Issue date: 10/24/1980
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Tallman W
PUBLIC SERVICE CO. OF NEW HAMPSHIRE
References
NUDOCS 8011060638
Download: ML19339B266 (1)


Text

.

04l4 I

  1. pna b

'o UNITED STATES

! } ') W ',i NUCLEAR REGULATORY COMMISSION 3 x ',

l REGION I 631 PARK AVENUE 3,. * '

g U

KINO oF PRUSSIA, PENNSYLVANIA 19406

%,..... Jf October 24, 1980 Docket Nos. 50-443 fi 50-444 U

T m

i; Public Service Company of New Hampshire m

ATTN:

Mr. W. C. Tallman 54 "

A

[jj Chairman and Chief Executive Officer s;

s 1000 Elm Street J

Manchester, New Hampshire 03105 g

-g G

rn u

Gentlemen:

The enclosed IE Information Notice No. 80-37, " Containment Cooler Leaks and Reactor Cavity Flooding at Indian Point Unit 2,"

is forwarded to you for information.

No written response is required.

If you desire additional information regarding this matter, please contact this office.

Sincerely, i

oyce H. Grier 0irector

Enclosures:

1.

IE Information Notice No. 80-37 2.

List of Recently Issued IE Information Notices CONTACT:

E. G. Greenman (215-337-5267) cc w/encis:

John DeVincentis, Project Manager 8011060638

m D

3

2.E 1:3 hc SSINS No.:

6835 Accession No.:

8008220249 UNITED STATES IN 80-37 NUCLEAR REGULATORY COMMISSION CFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555

~

October 24, 1980 IE Information Notice No. 80-37:

CONTAINMENT COOLER LEAKS AND REACTOR CAVITY FLOODING AT INDIAN POINT UNIT 2 Discription of Circumstances:

This Notice contains information regarding multiple service water leaks into containment with resulting damage to reactor instrumentation and potential damage to the reactor pressure vessel.

Upon containment entry on October 17, 1980 at Indian Point Unit 2, to repair a malfunctioning power range nuclear detector, it was discovered that a significant an.ount of water was collected (approximately 100,000 gal) on the containment floor, in the containment sumps, and in the cavity under the reactor pressure vessel (RPV). This collected water probably caused the detector malfunction, and the water in the cavity under the RPV is believed to have been deep enough to wet several feet of the pressure vessel lower head, causing an unanalyzed thermal stress condition of potential safety significance.

This condition resulted from the following ccabination of conditions:

(1) Both containment sump pumps were inoperable, one due to blown fuses from an unknown cause and the other due to binding of its controlling float; (2) The two containment sump level indicating lights which would indicate increasing water level over the water level range present in the containment were stuck (on) and may have been for several days, leaving the operator with no operable instrumentation to measure water level in the containment; (3) The moisture level indicators in the containment did not indicate high moisture levels, apparently because they are designed to detect pressurized hot water or steam leaks (i.e., a LOCA), and are not sensitive to the lower airborne moisture levels resulting from relatively small cold water leaks; (4) The hold-up tanks which ultimately receive water pumped from the containment sump also receive Unit 1 process wcter, la5 drain water, etc.

These other water sources masked the effect of cessation of wtter flows from the Unit 2 sump; (5) There were significant, multiple service water leaks from the containment fan cooling units directly onto the containment floor.

These coulers have a history of such leakage, which cannot be detected by supply inventory losses since the supply system (service water system) is not a closed system; (6) The two submersible pumps in the cavity under the Reactor Pressure Vessel were ineffective since they pumo onto the con-tainment floor for ultimate removal by the (inoperable) containment sump pumps.

There is no wa.er level instrumentation in the cavity under the RPV, nor was there any indication outside the containment when these pumps are running.

The ifcensee has installed redundant sump level annunciated alarms in the l

control room and has installed an annunciated alarm in the control room to l

indicate if eithr submersible purp in the reactor cavity activates.

The l

licensee has alu repaired the zervice water leaks, installed guide bushings i

l on the sump pump control floats to prevent their binding, and has repaired the containment sump water level indicators.

l i

IN 80-37 October 24, 1980 Page 2 of 2 The licensee plans in the longer ters to replace the containment fan unit cooling cofis.

It is anticipated that results of a continuing NRC investigation into this incident will result in issuance of an IE Bulletin and/or an NRR Generic Letter in the near future which will recommend or require specific ifcensee and applicant actions.

In the interim, we recommend that all licensees ascertain that the potential does not exist for undetected water accumulation in the containment.

This Information Notice is provided to inform if censees of a possibly significant matter.

No written response to this Information Notice is required.

IE Information Notice No. 80-37 October 24, 1980 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued to Notice No.

Issued 80-36 Failure of Steam 10/10/80 All holders of a Generator Support power reactor Bolting OL or CP 80-35 Leaking and Dislodged 10/10/80 All holders of a Iodine-125 Implant Category G or G1 Seeds Medical Licensa 80-34 Boron Dilution of 9/26/80 All holders of a Reactor Coolant During PWR Power Reactor OL Steam Generator Decontamination 80-33 Determination of 9/15/80 All holders of Teletherapy Timer a teletherapy Accuracy license 80-32 Ciarification of 9/12/80 All holders of Certain Requirements an NRC or Agreement for Exclusive-use State License Shipments of Radioactive Materials 80-31 Maloperation of Gould-8/27/80 All holders of Brown Boveri 480V-Type a power reactor K-6005 and X-Don 6005 OL or CP C1rcuit Breakers 80-30 Potential for Unaccept-8/27/80 All holders of able Interaction a SWR power reactor Between the Control OL or CP Rod Drive Scram Function and Non-essential Control Air at Certain BWR Facilities 80-29 Broken Studs on 8/7/80 All holders of Terry Turbine a power reactor Steam Inlet Flange OL or CP Supplement Notification of 7/29/80 All holders of a to 80-06 Significant Events power reactor OL at Operating Power and near term OL Reactor Facilities applicants