September 9, 1980 wer Petsietut TELEP=oe t:Anta 704 s
l
$ Tease PmODwct 0*u 373-4093 Mr. James P. O'Reilly, Director U. S. Nuc1 car Regulatory Comnission Region II 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303 1
Re: RII:GFM i
50-413/80-16 1
50-414/80-16 1
Dear Mr. O'Railly:
Please find attached a response to Deficiency No. 413/414/80-16-01 which was identified in the above referenced Inspection Report. Duke Power Company does not consider any information contained in this inspection report to be proprietary.
Ve truly yours, l
t' j
l
- d. cLA u.._
3 William O. Parker, Jr.
RWO:ses Attachment l
cc: Resident Inspector of NRC l
Catawba Nuclear Station 1
E*mcui.cm.,.
=.
. 8 02 os 2,, oss
Catawba Nuclear Station USNRC I&E Inspection Report 50-413/80-16 and 50-414/80-16 Response to Violation A of Appendix A Deficiency stated as follows:
As required by Criterion IX of Appendix B to 10CFR50, as implemented by Duke's Topical P.eport, Paragraph 17.1.9, measures shall be established to assure that welding is controlled in accordance with applicable standards.
Contrary to the above, installation Drawing CN-1915-05, Revision 10 displays synbols and letters which are not defined in DPC specifications, design documents, procedures, instructions or in the applicable AUS section for symbols.
Response
In the Catawba PSAR, Section 3.8, reference is made to the AISC fianual of Steel Construction, Seventh Edition, the AISC Specification of the Design, Fabrication, and Erection of Structural Steel Buildings and the AWS Structural Welding Code (AWS Dl.1) for the design, fabrication, and erection of the Nuclear Safety Related structural steel.
AWS Dl.1 references the latest edition of AWS A2.4, Symbols for Welding and Nondestructive Testing for the Definition of all Welding Symbols.
In addition, the text, AISC Structural Steel Detailing, cross-references the principal parts of the AISC Manual of Steel Construction and various applicable sections of the referenced AISC Specification, and is intended prinarily as a textbook for illustrating current good practice in detailing structural steel.
The referenced drawing for Class IE electrical cable tray supports references Specification CNS-ll21.00-1 which in turn references the AISC Manual and AWS Dl.1, for all field welding.
Further definition of the deficiencies noted on the referenced drawing is given in Section 5a of the Inspection Report, and is as follows:
"During the various interviews, the inspector was given different definitions of what the letters BS and the symbol stands for, which is e
s s4/'
\\
3/16 an undefined symbol and one of the undefined letters used on the aforenoted drawing."
The letters BS are defined in the text, AISC Structural Steel Detailing, Second Edition.
AWS Dl.1 and A2.4 state that in the tail of the welding symbol ad-ditional references may be stated.
Therefore, Duke concludes that drawing CN-1915-05, Revision 10 does display symbols and letters which are appropriately defined in accordance uith applicable standards.
However, to remove the apparent confusion concerning this abbreviation, a clarifying letter will be sent to all Design Engineering and Construction Departments fully explaini.79 the abbreviation and defining all refere nce documents.
\\
I Y
The referenced weld symbol is an incorrect symbol. The correct syr.bol is shown as follows:
/
/
(3/16)
\\
This symbol will be corrected on the referenced drawing.
In order to avoid future noncompliances of the same nature, a letter will be sent to all Design Engineering Departments re-emphasizing the use of AWS A2.4 for welding symbols.
The referenced corrective actions will be completed by October 1,1980.
$