ML19338F725

From kanterella
Jump to navigation Jump to search
Immediate Action Ltr Confirming 800919 Telcon Re Standby Gas Treatment Sys Operability.Lists Actions to Be Taken by 800925
ML19338F725
Person / Time
Site: Pilgrim
Issue date: 09/19/1980
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Howard J
BOSTON EDISON CO.
References
IAL-80-33, NUDOCS 8010270111
Download: ML19338F725 (1)


Text

_ _

/.a crog)o UNITED STATES g

hUCLEAR REGULATORY COMMISSION g ) ),>

g REGION 1

% 4

,[.:; y C,

631 PARK AVENUE g'O

, NG OF PRUSSI A, PENNSYLVANIA 19406 O

Docket' '.o. 50-293 IAL No. 80-33 Boston Edison Company N/C Nuclear ATTN: Mr. J. E. Howard Vice President - Nuclear 800 Boyiston Street Boston, Mass mhusetts 02199 Gentl emen:

This refers to the telephone conversation between Mr. R. D. Machon, Nuclear Operations Manager - Pilgrim Station and Mr. E. J. Brunner of this office on l

Septer. ber 19, 1980, regarding Standby Gas Treatment System (SBGTS) operability at Pilgrim Nuclear Power Station, Unit 1.

With regard to the matters discussed, we understand that by 2400 hours0.0278 days <br />0.667 hours <br />0.00397 weeks <br />9.132e-4 months <br /> on September 25, 1980, you will have:

1)

Demonstrated the methyl icdide removal capability of the charcoal absorber banks of each SBGTS train satisfy Technical Specification (TS) 3.7.B.l.b(2);

or, 2)

Declared one SBGTS train inoperable and made the other SBGTS train operable, the latter with a charcoal absorber bank of known elemental iodine and/or methyl iodide removal efficiency of at least 95%; or, 3)

Initiated actions to be in cold shutdown in 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br />.

If our understanding of your planned actions as described above is not in accordance with the actual plans and actions being implemented, please contact this office by telephone and in writing within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Sincerely, l

yW + Ylf.

ifb x I

' A yce H. Grier

[i'Virector cc:

R. D. Machon, Nuclear Operations Manager - Pilgrim Station 8010270///

[

_-_