9 l

NUCLE AR ENERGY BU:llNESS GROUP

  • GENER AL ELECTRIC COMPANY SAN JOSE, CALIFORNI A 95125 9

GEN ER AL h ELECTRIC APPLICABLE TO:

NEDO-24081 PUBUCATION NO.

77NED355 T. l. E. NO.

LOCA ANALYSIS FOR PEACH 6

TITLE NO.

BOTTOM ATOMIC POWER STATION June 1980 DATE UNTT 2 NO TE: Correct all copies of the applicable December 1977 publication as specified below.

lSSUE OATE REFERENCES INSTRUCTIONS ON, A E ITEM pjSEc (CORRECTIONS AND ADDITIONS)

Ac Apg nE) 1 Page 3-1/3-2 Replace with revised page 3-1/3-2.

2 Page 4-9 Replace with revised page 4-9.

3 Page 4-12 Replace with revised page 4-12.

(Change bars in right-hand margin indicate areas of report which have been revised.)

PAGE 1 Of 1 8020020 qe:g

NEDO-24081 3.

INPUT TO ANALYSIS A li.t of the significant plant input parameters to the LOCA analysis is presented in Table 3-1.

Table 3-1 SIGNIFICANT INPUT PARAMETERS TO THE LOSS-OF-COOLANT ACCIDENT ANALYSIS Plant Parameters:

Core Thermal Power 3440 MWt, which corresponds to 105% of rated steam flow 6

Vessel Steam output 14.05 x 10 lbm/h, which corresponds to 105% of rated steam flow Vessel Steam Dome Pressure 1055 psia Recirculation Line Break Area for Large Breaks - Discharge 1.9 ft2 (DBA)

- Suction 4.1 ft (DBA)

Number of Drilled Bundles 360 Fuel Parameters:

Peek Technical Initial-Specification Design Minimum Linear Heat Axial Critical Fuel Bundle Generation Rate Peaking Power Fuel Type Geometry (kW/ft)

Factor Ratio A.

IC Type 2 7x7 18.5 1.5 1.2 B.

IC Type 3 7x7 18.5 1.5 1.2 C,

8D274L 8x8 13.4 1.4 1.2 D.

8D274H 8x8 13.4 1.4 1.2 E.

LTA260 8x8 13.4 1.4 1.2 F.

8DRB284 8x8R 13.4 1.4 1.2 G.

F8DRB284H 8x8R 13.4 1.4 1.2 H.

P8DRB285 8x8R 13.4 1.4 1.2

  • To account for the 2% uncertainty in bundle power' required by Appendix K, the SCAT calculation is performed with an MCPR of 1.18 (i.e., 1.2 divided by 1.02) for a bundle with an initial MCPR of 1.20.

3-1/3-2

NEDO-24081 i

1 Table 4-3c j

MAPLHGR VERSUS AVERAGE PLANAR EXPOSUPI Plant: PB-2 Fuel Type:

8D274L t

i Average Planar Exposure MAPLHGR PCT 0xidation (Mwd /t)

(kW/ft)

('F)

Fraction i

200 11.2 1758 0.006 1,000 11.3 1765 0.006 l

5,000 11.9 1845 0.008 10,000 12.1 1862 0.008 15,000 12.2 1890 0.009 l

20,000 12.1 1891 0.009 25,000 11.6 1853 0.007 30,000 10.9 1773 0.005 35,000 10.0 1664 0.003

~,000 9.3 1591 0.003 i

I I

l l

I I

l r

i 4-9

i NEDO-24081 i

Table 4-3d i

MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Plant:

PB-2 Fuel Type:

8D274H*

i

'i Average Planar Exposure MAPLHGR PCT 0xidation i

Ofwd/t)

(kW/ft)

(*F)

Fraction I

200 11.1 1755 0.006 i

1,000 11.2 1755 0.006 5,000 11.7 1830 0.007 4

i 10,000 12.1 1869 0.008 l

15,000 12.2 1894 0.009 20,000 12.0 1892 0.009 l

25,000 11.5 1848 0.007 i

30,000 10.9 1778 0.006 35,000 9.9 1664 0.003 1

I i

40,000 9.3 1591 0.003 1

{

  • Applicable to 80, 100 and 120 mil channels.

l 1

1 4-10 i

-,n..

~

'o NEDO-24081 Table 4-3 e MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Plant:

PB-2 Fuel Type:

LTA260 Average Planar Exposure MAPLHGR PCT 0xidation (Mwd /t)

(kW/ft)

(*F)

Fraction 200 11.4 1829 0.007 1,000 11.5 1839 0.008 5,000 12.1 1913 0.010 10,000 12.2 1929 0.011 15,000 12.3 1958 0.012 20,000 12.1 1961 0.012 25,000 11.7 1911 0.010 30,000 11.3 1882 0.009 35,000 10.3 1752

~

'0.006 ~

40,000 9.7 1678 0.004

~45,000 9.1 1603; 0.003 50,000 8.5 1567 0.002 Table 4-3f MAPLEGR VERSUS AVERAGE PLANAR EXPOSURE Fuel Type:

8DRB284 d

Exposure MAPLEGR PCT 0xidation (mwd /t)

(kW/fc)

(*F)

Fraction 200 11.3 1858 0.009 1,000 11.3 1862 0.009 5,000 11.8 1926 0.011 10,000 12.0 1937 0.011 15,000 12.0 1947 0.012 20,000 11.6 1910 0.010 25,000 10.9 1828 0.008 l

30,000 10.2 1751 0.006 4-11

c'

-?.

NED0-24081 Table 4-3g MAPLHGR VERSUS ' M GE PLANAR EXPOSLTE Fuel Type:

P8DRB284H*

Average Planar Exposure MAPLHGR PCT 0xidation (mwd /t)

(kW/ft)

(*F)

Fraction 200 11.2 1861 0.008 1,000 11.2 1865 0.008 5,000 11.7 1903 0.010 10,000 12.0 1938 0.011 15,000 12.0 1938 0.011 20,000 11.5 1907 0.011 25,000 10.8 1823 0.007 30,000 10.1 1744 0.005

  • Applicable to 80, 100, and 120 mil channels Table 4-3h MAPLHGR VERSUS AVERAGE PLANAR EXPOSURE Fuel Type: P8DRB285 Average Planar Exposure MAPLHGR PCT Oxidation (mwd /t)

(kW/ft)

(OF)

Fraction 200 11.0 1826 0.008 1,000 11.1 1836 0.008 5,000 11.9 1924 0%011 10,000 12.2 1948 0.012 15,000 12.1 1943 0.011 20,000 11.7 1903 0.010 25,000 11.0 1818 0.007 30,000 10.3 1740 0.005 4-12