w T

,l APPENDIX A NOTICE OF VIOLATION Duke Power Company License No. DPR-47 Oconee Based on the NRC inspection April 15-17 and 21-23, 1980, certain of your activi-ties were apparently not conducted in full compliance with NRC requirements as indicated below. These items have been categorized as described in correspondence to you dated December 31, 1974.

As required by (g)(4) of 10 CFR 50.55(a) and implemented by the Technical Specification, Paragraph 4.2, as updated, requires the surveillance program of Class 1, Class 2... components comply with ASE Section XI (74S75).

Paragraphs I-3131 and I-3210 require that basic calibration block config-uration reflector size and location comply with Fig. I-3131.

Contrary to the above requirement, on April 15, 1980, the size and location of holes and notches (reflectors) on ISI basic calibration blocks Nos.

40303 and 40304 did not comply with Fig. I-3131 of the above ASE Section XI code.

This is an infraction.