ML19331D726

From kanterella
Jump to navigation Jump to search
Forwards LER 80-032/03L-0
Date released: 12/11/2019 Download: ML19331D726


LER 80-032/03L-0:on 800805,while Performing Special Load Test,Emergency Diesel Generator 1A Tripped When Loaded. Caused by Actuation of Field over-current Relay Below Design Setpoint.Relay Adjusted to Proper Value
ML19331D734
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 08/28/1980
From: Heinamdy V
FLORIDA POWER CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19331D734 (2)
Forwards LER 80-032/03L-0
ML19331D725
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 08/29/1980
From: Hancock J
FLORIDA POWER CORP.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19331D725 (1)