Telephone 6l7 3bb-9C TwX 710-390-0739 YANKEE ATOMIC ELECTRIC COMPANY ura 80-90 B.3.2.1

  • Yau&

i 20 Turnpike Road Westborough, Massachusetts 01581 xse August 1, 1980 United States Nuclear Regulatory Commission Washington, DC 20555 Attention:

Mr. Dennis M. Crutchfield, Chief Operating Reactors Branch #5 Division of Licensing

References:

(a) License No. DPR-3 (Docket No. 50-29)

(b)

YAEC Letter to USNRC dated November 28, 1978 (WYR 78-103)

(c) YAEC Letter to USNRC dated June 5,1980 (WYR 80-62)

Subject:

Environmental Qualification of Electrical Equipment

Dear Sir:

Enclosed is our revised equipment list for electrical equipment qualification purposes which we agreed to submit at our mid-July 1980 site audit with the NRC staff. This list has been revised to include only electrical equipment and displays involved in direct mitigation of a LOCA, MSLB, and FWLB.

The following changes have been made:

1.

Equipment required for cold shutdown has been added as per your guidelines.

2.

Enclosure B (asterisked items on Enclosure A) identifies equipment located in harsh environments (both inside and outside containment). Equipment in harsh environments resultird from recirculating fluid lines have not been identified. This information is still being developed and will be submitted in several weeks. Equipment not in a harsh environment (i.e., control room, switchgear room, and some locations in the PAB) remain on the list (Enclosure A) as per the guidelines.

3 Pneumatic equipment has been deleted for the purposes of this list.

4.

Equipment installed as a result of NUREG-0578 short term requirements has been added.

We are still in the process of updating our equipment data sheets for equipment in harsh environments and will submit these in several weeks.

800813053G t

J

United' States Nuclear Regulatory Commission

~ August 1, 1980 Attention:

Mr. Dennis M. Crutchfield,' Chief

~Page 2 These data sheets are being revised to provide additional information on the specific environment, to add radiation doses, and to supply vendor information.

The following additional information is also submitted and was requested at the site meeting. The maximum containment water level, after a LOCA, was calculated to be approximately elevation 1057' (refer to FM-lC and FM-lX attached). This calculation assumed an injection of approximately 18,580 ft3 of water into the containment and a concrete displacement of approximately 14000 ft3 The details of the calculation are summarized in Enclosure C.

We trust this information is satisfactory; however, if you have any questions,

. please contact us.

Very truly yours, YANKEE ATOMIC ELECTRIC COMPANY

.6 J. A. Kay.

Senior Engineer - Licensing JAK/ncj Enclosure

ENCLOSURE A.

FACILITY: YANKEE ROWE PACE 1 0F 13 DOCKET NO.:. 50-29 EQUIPMENT LIST SYSTEF.: Component Cooling Tag Number Description Location References P-20-1,-2 Motor, Component Cooling Pump PAsl CC-1 SYSTEM: Charging and Volume Control Tag Number Description Location References P-15-1,-2,-3

. Motor, Charging Pump PAB CH-1 SYSTEM: Containment Isolation Tag Number Description Location References K-CI-9,10,11,12 Relay, Containment Isolation Actuation SWGR CI-0 K-CI-13,14,15,16 Relay, Containment Isolation Actuation MCR CI-1 PS-CI-230 Pressure Switch, Cont. Iso. Actuation PAB CI-2 PT-CI-227 Transmitter Vapor Container Pressure PAB CI-3 SOV-CI-801-820 Containment Isolation Solenoid Operated Valves PAB CI-4 SOV-CI-901-920 Containment Isolation Solenoid Operated Valves PAB CI-5

r: '

r-FACILITY:. YANKEE ROWE ENCLOSURE A DOCKET No.:

50-29 PAGE'2 OF 13 EQUIPMENT LIST

,1' SYSTEM: Containment Isolation (Continued)

Tag Number Desc rip t

  • on Location References LOR-CI-A,B Lockout-Relay PAB CI-6 K-CI-21,22 Auxiliary Relay PAB CI-7 Switch Cont. Iso. Switch Pnl.

PAB/MCR K-CI-40-94 Relays, Cont. Iso. Reset Sys. A MCR CI-9 SYSTEM:

Service Water Tag Number Description Location References P-6-1,2,3 Motor, Service Water Pump SCRN SW-1

o FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.:

50 PACE 3 0F 13 EQUIPMENT LIST SYSTEM: Main Coolant Tag Number Description Location References PT-MC-6 Pressare Detector Pressurizer VC*

MC-3 PT-Mc-9 Pressure Detector MC VC*

MC-4 PT-MC-712 Pressure Xmitter LTOP VC*

MC-4 MC-MOV-301 Main Coolant Inlet / Outlet Valve VC MC-5 MC-MOV-302 Main Coolant Inlet / outlet Valve VC MC-5 MC-MOV-309 Main Coolant Inlet / Outlet. Valve VC MC-5 MC-MOV-310 Main Coolant Inlet / Outlet Valve VC MC-5 MC-MOV-318 Main Coolant Inlet / Outlet Valve VC MC-5 MC-MOV-319 Main Coolant Inlet / outlet Valve VC MC-5 MC-MOV-325 Main Coolant Inlet / outlet Valve VC MC-5 MC-MOV-326 Main Coolant Inlet / Outlet Valve VC MC-5 MC-TD-78 Main Coolant Cold Leg RTD VC MC-9 MC-TD-60 Main Coolant Cold Leg RTD VC MC-9 MC-TD-66 Main Coolant Cold Leg RTD VC MC-9 MC-TD-72 Main Coolant Cold Leg RTD VC MC-9

r :-

-Q ENCLOSURE A FACILITY: YANKEE ROWE PACE 4 OF 13 DOCKET NO.:

50-29 EQUIPMENT LIST SYSTEM:

Pressurizer Tag Number Description Location References LD-PR-8 Level Detector Pressurizer Level (WR)

VC PR-3 SOV-PR-90 Power Operated Relief Valve VC PR-4 PT-PR-700 Pressure Transmitter Sat. Monitor VC PR-h0V-512 Block Valve for PR-PRV-90 VC PR-5 ZT-PR-1A,B,C Transmitter Accoustic Acc. Pressurizer VC ZE-PR-1A,B,C Sensor Accoustic Acc. Pressurizer VC SYSTEM: Purification Tag Number Description Location References PU-MOV-541 Motor Operated Valve, Containment Isolation PAB PU-l

. FACILITY: YANKEE ROWE

' ENCLOSURE A

. DOCKET.NO.:

50-29 PAGE 5 0F 13

-EQUIPMENT. LIST

w

=

,g SYSTEM:

Feed Water Tag Number Deseription Location References.

LI-FW-1003,1103, Ind.' Steam Generator Level (NR)

MCR FW-3 1203,1303 LT-FW-1003,1103, Transmitter Steam Generator Level (NR)

'VC*

FW-4 I

.1203,1303-P/S-FW-1003,1103, Power Supply Steam Generator Level (NR)

SWGR FW-7 1203,1303 SYSTEM: Ilyd ogen Vent Tag Number Description Location References.

HV-SOV-1,2 Post-Accident H Vent Valve VC*

IIV-1 2

CA-HV-1 Hydrogen Analyzer SWGR HV-2 SYSTEM:

Radiation Monitoring 4.

Tag Number Description Location References 4

GG-RM-1 Emergency Rad. Monitor /High Range TB/MCR RM-1 RD-RM-112 Emergency Rad. Monitor /High Range TB RM-2

-RI-RM-112

. Emergency Rad. Monitor Indicator MCR RM-3

r FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.:

50-29 PAGE 6 OF 13 EQUIPMENT LIST SYSTEM: Miscellaneous Tag Number Description Location References FN18-1,2,3 Post-Accident Recire. Fan VC*

MIS-1 SYSTEM:

Safety Injection Tag Number Description Location References LI-SI-1 Level Indicator SI Tank Level MCR SI-1 LS-SI-1,2,3,4 Level Switch SI Accumulator Low Water Level PAB SI-3 SI-PP-LP1,2,3 Motor,' Low Pressure SI Pump PAB SI-4 SI-PP-ilP-1,2,3 Motor, liigh Pressure SI Pump PAB SI-5 PS-SI-14 Pressure Switch, 'vC Pressure /SI Initiation Ckt.

VC SI-6 PS-SI-238,239 Pressure Switch, SI Initiation Ckt.

PAB SI-7 Switch Auto - Manual Bypass Ch. A & B MCR SI-MOV-1 SI Accumulator Outlet Valve PAB SI-8 P/S-SI-1 Power Supply, SI Tank Level MCR SI-12

,o FACILITY:. YANKEE-ROWE ENCLOSURE A

_ DOCKET NO.:

50-29 PACE 7 0F 13 i

EQUIPMENT LIST SYSTEM: Safety Injection (Continued)

Tag Number Description Location References LSX-SI-1,2,3,4 Aux. Relay Vent Accumulator MCR SI-13 MOV-CS-533 LPSI Path Isolation Valve PAB SI-23

'MOV-CS-535 LPSI Path Isolation Valve VC*

SI-9

MOV-SI-48,49 HPSI Recirculation Valve PAB SI-8 MOV-SI-514,515 HPSI
o Charging Hdr. Iso. Valve PAB SI-8 MOV-SI-516 Containment Sump Isolation Valve PAB S!-8 MOV-SI-517 Containment Sump Isolation Valve PAB SI-8 MOV-SI-518 SI Tank Discharge Valve PA B SI-8 SOV-SI-45 Accumulator, Actuator for TV-608 PAB SI-10 SOV-SI-46 Accumulator, Actuator for TV-604,605,606 PAB SI-10 SOV-SI-47 Accunolator, Actuator for TV-604,605,606 PAB SI-10 SOV-SI-56,57-Safety Valve Accumulator PAB SI-11 1

a 1

=

0 l

ENCLOSURE A FACILITY: YANKEE ROWE PAGE 8 0F 13 DOCKET NO.:

50-29 EQUIPMENT LIST SYSTEM:

Safety Injection (Continued)

Location References Tag Number Description PAB SI-ll SOV-SI-639 Safety Valve Accumulator PAB SI-ll SOV-SI-640 Safety Valve Accumulator MCR SI-15 WL-SI-1 Relay, SI Initiation Ckt.

MCR SI-15 WL-SI-1-1 Relay SI Initiation Ckt.

MCR SI-16 TDC-PR-1,2,3,4 Relay, Pressurize Accumulator MCR SI-17 TDC-SI-1,2,3,4 TD Relay Accumulator MCR SI-18 X-SI-1-1,2 Relay Multiplier K-CI-7,8 Lockout Relay, Diverse Cont. Isol.

MCR SI-19 MCR SI-20 K-31,32 Auxiliary Relay MCR SI-21 K-SG Relay, Operates WL-SI-1-1 MCR SI-22 SIAS-A, B Lockout Relay

FACILITY: YANKEE ROWE ENCLOSURE A' DOCKET NO.:

50-29 PACE 9 0F 13 EQUIPMENT LIST SYSTEM: Service Water Tag Number Description Location References P-1,2,3 Service Water Pumps SCRN SYSTEM:

Shutdown Cooling Tag Number Description Location References P-1 Motor Shutdown Cooling Pump PAS SC-MOV-551,2,3,4 Shutdown Ccoling Valves VC*

i 1

e i

D i

ENCLOSURE A FACILITY:. YANKEE ROWE PAGE 10 0F 13 DOCKET NO.:

50-24 EQUIPMENT LIST SYSTEM:

Rea tor Protection

^

Tag Number Description Location References RPS Reactor Protection System (Westinghouse)

NCR RP-4 BK-1,2 Circuit Breaker, Rod Scam SWGR RP-5 SYSTEM: Electrical Equipment For All Systems Tag Number Description Location References Emergency Diesel Cen. 1,2,3 PAB J1 LT-DG-1,2,3 Level Transmitter Level Control Day Tank PAB J2

-SOV-DG-1,2,3 SOV Diesel Gen. Day Tank Fill Valve PAB J3 LIC-1,2,3 Level Receiver Level Control Day Tank PAB J4 f

No. 1&2 Battery SWGR J5 No. 3 Battery PAB J6 No.1&2 Battery Charger - MG Set SWGR J7 No. 3 Battery Charger - Static PA B,

J8 No.1&2 Battery Switchboard SWGP J9 No. 3, 3A, 3B Battery Switchboard PAB J10

c, -

FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.:

50-29 PAGE 11 OF 13 EQUIPMENT LIST s,

SYSTEM:- Electrical Equipment For All Systems (Continued)

Tag Number Description Location References

- 480 Volt Emergency Bus 1,2,3 PAB

~

J11 480 Volt Emergency MCC 1 SWGR J13 480 Volt Emergency MCC 2 PAB J14 Vital Bus Inverter (M-G Set)

SWCR J15 Vital Bus Distribution Cubicle SWCR J16 Terminal Block 12 Point VC J18 Penetration Assembly VC J19 I

ENCLOSURE A FACILITY: YANKEE ROWE DOCKET NO.:

50-29 PACE 12 OF 13' EQUIPMENT LIST SYSTEM: Elect rical Equipment For All Systems (Continued)

Tag Number Description Location References Cable Mineral Insulated VC J20 Cable Polyethylene /PVC VC J21 Cable Butyl Rubber /PVC VC J22 Cable Silicone Rubber / Asbestos VC J23 Cable XLP/ Neoprene (or Hypalon)

VC J24 Osbie PVC Shielded VC J25 Relay, Reverse Power (CRM-1)

MCR J29 Relay, Time Delay TDPU 2.5-50 Sec.

MCR J28 Selector Switch for MOV MCR J27 Cable Mineral Insulated

'*20 J20 Cable Polyethylene /PVC VC J21 Cable Butyl Rubber /PVC VC J22

FACILITY: YANKEE ROWE ENCLOSURE A DOCKET NO.:

50-29 PAGE 13 OF 13 EQUIPMENT LIST SYSTEM: Electrical Equipment For All Systems (Continued)

Tag Number Description Location References Cable Silicone Rubber / Asbestos VC J23 Cable XLP/ Neoprene (or Hypalon)

VC J24 Cable PVC Shielded VC J25 Control Switch MCR J33 Relay Over/Under Voltage (CV-7)

MCR J32 Relay Voltage (SV)

MCR J31 Relay Auxiliary (Various)

MCR J30.

  • Indicates equipment required to function in hostile environment.

t ENCLOSU RE C Summary _ of Calculation to Determine Maximum Water Elevation Inside Containment During the LOCA Injection Phase l'.

' Water ; volumes inside VC 700 ft3 LAccumulator Safety Injection Tank (max) 15,600 ft3 Loop Volumes' - 4 0 342 each 1,368 ft3 S.G. Primary - 4 @ 208 each 832 ft3 Pressurizer (water only) 90 ft3 2.'

Concrete displacement -

Vescel Support Area 3,750 ft3 Concrete posts 310 ft3 3

Formula to approximate water level-volume of a partially full hemisphere V = 1/3n h2 (3r - h)

- f- = 187.5h2-h3 e = 62 5 ft (v.c. radius) 4.

Solution: by trial and error h 3I 11.1 ft f.

.