4 APPENDIX A NOTICE OF VIOLATION Duquesne Light Company Docket No. 50-412 This refers to the inspection conducted by representatives of the Region I (Philadelphia) office at the Beaver Valley Power Station, Unit No. 2, Shippingport, Pennsylvania of activities authorized by NRC License No.

CPPR-105.

During this inspection, conducted on April 7-11, 1980, the fellowing apparent item of noncompliance was identified.

10 CFR 50, Appendix B, Criterion IX, states, in part, that "...

special processes, including... nondestructive testing are controlled and accomplished...in accordance with applicable codes...."

The Beaver Valley Power Station PSAR, Section 17, paragraph 17.2.1.9A, also states, in part, that:

... nondestructive testing (be) controlled and accomplished...in accordance with applicable codes...."

The Specification 2BVS-920, Field Fabrication and Erection of Piping, ASME III Class 1, 2, and 3, requires that:

"...These code class 1, 2, and 3 piping systems shall be designed, fabricated, installed, tested, and inspected in accordance with ASME III (1971 edition)."

The ASME III Code, Appendix IX, paragraph IX-3340, requires that: "The manufacturer shall record on a review form the interpretation and disposition of each film."

Contrary to the above, a review of radiographic film on April 19, 1980, for safety related pipe welds 2-RSS-021-F02, F04, F05, F07 and 2-RSS-062-F06, disclosed indications which had not been interpreted, dispositioned, and recorded on the review form.

This item is an infraction.

8 0 0813 0 J{ %

.