Forwards IE Info Notice 80-13, GE Type SBM Control Switches Defective CAM Followers. No Written Response Required
ML19330B984
Person / Time
Site: River Bend  
Issue date: 04/02/1980
From: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To: Weigand J
GULF STATES UTILITIES CO.
References
NUDOCS 8008070356
Download: ML19330B984 (1)


Text

.

PDR LPDR TIC /

NSIC

[guag,%.

UNITED STATES NUCLEAR REGULATORY COMMISSION CENTRAL FILES

+

@^

REGloN IV E

N o

611 RYAN Pt.AZA oRIVE, SUITE 1000 1

3' jj ARLINGTON, TEXAS 76012

^((. **

April 2, 1980

').

In Rsply Refer To:

i RIV Dockat Nos.

50 458/IE Information Notice No. 80-13 50-459/IE Information Notice No. 80-13 Gulf States Utilities j

Attu:

Dr. J. G. Weigand, Vice President Operations and Technical Systems Post Office Box 2951 Beaumont, Texas 77704 Gentlemen:

This IE Information Notice is provided as an early notification of a possibly significant matter.

It is expected that recipients will review the information for possible applicability to their facilities. No specific action or response is requested at this time; however, an IE Circular or Bulletin will be issued to reconsnend or request specific licensee actions, if required.

If you have questions regarding this matter, please. contact the director of the appropriate NRC regional office.

Sincerely,

[

1 V. Seyfri Director

Enclosures:

1.

IE Information Notice No. 80-13 2.

List of IE Information Notices Recently Issued i

l

~

8 0 0 8 0 7035f,

i SSINS No.: 6870 Accession No.:

UNITED STATES 8002280650 NUCLEAR REGULATORY COMMISSION 0FFICE OF INSPECTION AND ENFORCEMENT D

3 WASHINGTON, D.C.

20555 g

oo o

IE Information Notice No. 80-13 Date:

April 2, 1980 Page 1 of 1 GENERAL ELECTRIC TYPE SBM CONTROL SWITCHES DEFECTIVE CAM FOLLOWERS Description of Circumstances:

This IE Information Notice alerts licensees and holders of construction permits of a poteatial defect in the esa followers of General Electric (GE) Type SBN control switches.

Based on preliminary information, it appears that the defect is limited to switches manufactured prior to 1976 with cam followers of polycarbonate material, such as Lexan.

In brief, the problem is initiated by exposing such polycarbonate material to hydrocarbons.

Such exposure leads to severe cracking having a rock salt appearance which ultimately could progress to mechanical failure.

It has been determined that such exposure has occurred during fabrication and could occur while performing maintenance (e.g., cleaning i

the contacts).

On February 22 and March 10, 1980, we were informed that SBM switches with

{

defective cam followers had been found at Diablo Canyon Unit I and at the l

Cooper Station, respectively. Although the information was preliminary and sketchy,. the problem is a long-standing one for which GE has issued " Service Information Letters" to its BWR customers.

The problems associated with such switches, however, are not restricted to GE customers as evidenced by the Diablo Canyon case. Furthermore, these switches have a broad range of applica-tion. For example, the defective switches at the Cooper Station were used principally as hand control switches, most of which were located in the control In contrast, those at Diablo Canyon Unit I were used as auxiliary room.

contacts on the 4KV and 12KV "Magna Blast" circuit breakers, with three SBN switches used per breaker: (1) a breaker mounted auxiliary switch, (2) a cell mounted auxiliary switch, and (3) a cell interlock switch.

i This information is provided_as notification of a possibly significant matter that is still under_ review by the NRC staff.

It is expected that recipients will review the information for possible applicability.to their facilities.

No specific action or response is requested at this time.

If you have questions I

regarding this matter, please contact the Director of the appropriate NRC Regional Office.

l l

l

IE Information Notice No. 80-13 April 1, 1980 LISTING OF RECENTLY ISSUED IE INFORMATION NOTICES Infctmation Subject Date Issued To Notice No.

Issued 80-08 The States Company Sliding 3/7/80 All power reactor Link Electrical Terminal facilities with an Operating License (OL) or a Construction Permit 80-09 Possible Occupational 3/7/80 All holders of power Health Hazard Associated reactor Operating With Closed Cooling Systems Licenses (OLs) and For Operating Power Plants near term Construction Permits (cps) 80-10 Partial Loss of Non-Nuclear 3/7/80 All Power reactor Instrument System Power facilities holding Supply During Operation Operating Licenses (OLs) and Construction Permits (cps) 80-11 General Problems with ASCO 3/14/80 All holders of Reactor Valves in Nuclear Application Operating License (OL),

Including Fire Protection Construction Permit (CP),

Systems fuel fabrication and processing facilities 80-12 Instrument Failure Causes 3/31/80 All holders of Power Opening of PORV and Block Reactor Operating Valve Licenses (OLs) and Construction Permits (cps)

Enclosure l

l

,