Forwards IE Bulletin 74-09, Deficiency in GE Model 4KV Magne-Blast Circuit Breakers. Action Required
ML19329E415
Person / Time
Site: Midland
Issue date: 08/09/1974
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Howell S
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
References
NUDOCS 8006120749
Download: ML19329E415 (1)


Text

- - _ _ - _ _ _ _ _ _ _ - _ -.

.geGY O

UNITED STATES e

1 ATOMIC ENERGY COMMISSION 1

k,#o ' '

DIRECTORATE OF REGULATORY OPERATIONS REGION 111 res d 799 ROOSEVELT ROAD m

GLEN ELLYN ILLINOIS 60137 (3123 85s.2660 AUG

'S 1974 Cometumere Feuer Compeay Docket No. 50-329 ATTN Mr. Stephen M. Howell Docket No. 50-330 Vice Freefdent 1945 Parmall Road Jamh===, Miakig==

49201 Gentlement The amalmeed DED Bulletia No. 74-9, "Def4=4mmey in the General Elastria Model 4EY Masse-Blast Ciramit Breakers," is being sent to you relating experiease with some of thsee ciromit breakers at Vermont Yanke: and Calvert Cliffs analent faa414e4==.

This information may have applisability at your facility. Aatica on your part is identified in Sestica B of the enslaaed Bulletin.

Sinserely, James G. Espplar Regional Director Enslosuret DRO Bulletia No. 74-9 bee: Mp ' files da Central rile.

Loeal PDn THIS DOCUMENT CONTAINS FDR POOR QUALITY PAGES 8006120 7 k i

T t

m August 9, 1974 i

DRO Bulletin No. 74-9

/

f DEFICIENCY IN GENERAL ELECTRIC MODEL 4KV MAGNE-BLAST BREAKERS We have recently received information from the licensee of Calvert Cliffs Units 1 and 2 relating to circuit breaker malfunctions in engineered i

safety systems. These circuit breakers, General Electric Model 4KV safety Magne-Blast are used extensively at both PWR and BWR facilities.

The malfunctions, which could negate operation of engineered safety i

system components, were attributed to an oversized roller trip bar and improper clearances of related guide holes and linkages.

We have also received information from the licensee of Vermont Yankee station describing an installation deficiency of the auxiliary switch assembly installed in the General Electric Model 4KV Magne-Blast circuit breakers. Although the circuit breakers are similar in model to the units used at Clavert Cliffs, they are of a different type and are used at both PWR and BWR facilities. Pertinent details relating to both problems are contained in Section A below, and the related action requested by this Bulletin is contained in Section B.

A.

Description of Circumstances Calvert Cliffs Units 1 and 2 On several occasions in the past, there had been unexplained " trip open" operations of several 4KV circuit breakers. On each occasion, the anomaly occurred immediately following an attempt to close the circuit breakers.

Investigation into the problem disclosed that causes for failure were attributed to an oversized spring discharge i

roller bar located on the right side of the breaker cubicle and improper clearances in the roller bar guide hole and associated linkages. The purpose of the roller bar is to trip open the breaker unit in the event it is inserted into the breaker cubicle while in its closed position. However, the installed roller bars l

were found to be approximately 1/4" longer than the design length, causing interference with the breaker auxiliary switch linkage.

i Approximately 116 circuit breakers of the make and model described herein and equipped with the faulty roller bars and the above l

j mentioned clearance problem are used in the two nuclear units at the facility.

Because we are requesting that you determine whether or not the subject breakers are used or are planned to be used at your facility the following details are provided for your information:

Manufacturer: General Electric Company ggg

[

Ar-iliary Switch Assemblies in MC-4.76 Horizontal Drawout Metal Clad Switchgear I

I l'i

~

.. ~.

2 r~3

,/

Vermont Yankee The licensee reported that while investigating a problem involving a station service water pump 4KV circuit breaker, an electrician noted that the breaker stationary auxiliary switch assembly rear mounting bolt had loosened and was disengaged from its mounting plate. The loose bolt is one of two bolts that assist in maintain-ing proper switch contact alignment. The loosening and disengage-ment of the tie bolt caused misalignment of the switch auxiliary contacts which could have rendered those contacts inoperable.

Inspection of similar switch assemblies installed in forty-seven 4KV circuit breakers at this facility found that all switch assemblies exhibited varying degrees of bolt loosening, Because we are requesting that you determine whether or not the a

subject devices are used or are planned to be used at your facility, the following details are provided for your information:

Manufacturer: General Electric Company Type: Metal Clad, M26 Switchgear (This switchgear has the auxiliary switch assembly mounted to it and may be used with a large number of different circuit breakers.)

B.

Action Requested It is requested that you determine whether safety related (Class IE) circuit breakers of the described makes and models are in-stalled at your facilities and provide the R0 Regional Office with your findings within 20 days from receipt of this bulletin.

With regard to the problem at Calvert Cliffs Units 1 and 2, if the subject breakers are installed, please include in your response a description and the results of your program to deternine if you have oversized roller trip bars installed and the scheduled com-pletion date of your corrective actions.

For facilities under construction, please inform us of your plans to assure that appropriate modification has been implemented in all safety related circuit breakers of the type described that have been or will be installed at your facility.

With regard to the Vermont Yankee problem, it is requested that you ascertain the bolt tightness conditions of the switch assembly in question and include in your response a description and the results of your inspection program concerning these matters.

It is also requested that you inform us of your plans regarding the long term verification of bolt tightness of the switch assemblies.

.--e..e

-e l-