l I
CONTENTS APPENDIX 15 15A ANSWERS TO QUESTIONS W kb 02,2,~,
I Amendment 3 A15-1 l
Docket 50-312 Amendment Na, 2 April 15, 1968 s
QUESTION Identify those items that will eventually be classified as 15A.1 technical specifications that now affect plant design.
Examples (DRL 15.1) include the minimum conditions of operation on:
engineered safety features; emergency generators; and in-core flux monitors.
ANSWER The plant design is influenced mainly by the 70 General Criteria for Nuclear Power Plant Construction Permits, together with con-siderations of performance objectives. Generally, the technical specifications refer to the implementation of many or all of these criteria. However, it is possible to anticipate some spec-ifications which also dictate the design rather than result from limitations of the design.
The most significant of the former ca tagory are listed below.
Specification Item Design Area Affected A.
Site Statement of exclusion Systems or components for con-area.
trolling normal or emergency release of radioac tivity.
B.
Containment
~
[ ';
Leak rate and frequency Provisions for testing contain-(
of testing.
ment and penetrations at pre-scribed frequency.
C.
Primary Coolant System Reactor vessel pressure, Reactor vessel design for environ-temperature, integrated mental exposure and provision for flux limitations, and any special operating procedure cooldown rate, which may be necessitated.
Primary coolant water Purification sys tem capability impurity and radio-and shielding, limitation on active contanination amount of cladding f ailure which limits.
limits operation.
D.
Primary Plant Auxiliary Systems Minimum core injection Injection system design, capability and system redundancy.
Requirement for periodic Provision for testing and test of safeguards.
system availability for i
testing.
3 0228 13A-1 nn...
UVj 77
Specification Item Desien Area Affected E.
Secondarv Coolant System Maximum radioactivity in Primary water purification system, secondary coolant.
steam generator operation with primary to secondary leaks.
F.
Reactor Core Maximum total mass of Fuel cycle planning, fuel handlin fuel in core, maximum and storage, power, maximum burnup.
Reactivity worth.
Borated water injection system.
G.
Control and Safety Systems Reactivity worth of System for controlling primary control systems, water boration.
Minimum hot and cold Provision of adequate normal and shutdown margins.
auxiliary shutdown systems.
Periodic testing of Provision for on-line or shutdown emergency power supply.
demonstrations of availability.
H.
Monitorinz Systems Requirement to determine Provisions for gaseous waste average activity in pri-discharge monitoring, and mary coolant and in rad-recording suitable for determin-waste system.
ing yearly average rates.
I.
Waste Disposal Systems Maximum waste discharge Waste concentration and holdup rates facilities.
J.
Ventilation Systems Frequency and method of Design of filters and air cleaning maintaining air filter-equipment, ing and air cleaning equipment.
K.
Emercency Cooline & Decay Heat Removal Systems Minimum capacity.
Engineered safeguards required to have redundant capabilities.
Requirement for periodic Provision for availability and
- test, testing.
0229 m,,,A uu>