Forwards Engineering Branch Evaluation of Viton-A Seal Matl for Reactor Coolant Pump Snubbers.Approval Recommended for Using Viton-A Seal Matl.Tech Specs Should Be Amended to Exclude Reactor Coolant Pump Snubbers
ML19329D631
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 12/13/1976
From: Eisenhut D
Office of Nuclear Reactor Regulation
To: Knight J
Office of Nuclear Reactor Regulation
References
NUDOCS 8003160254
Download: ML19329D631 (3)


Text

3 e

O

,p 4,

UNITED STATES y

NUCLEAR REGULATORY COMMISSION j

WASHINGTON, D. C. 20555 e

,s...../

DEC 131976 MEMORANDUM FOR:

J. Knight, Assistant Director for Engineering, Division of Systems Safety FROM:

D. Eisenhut, Assistant Director for Operational Tech-nology, Division of Operating Reactors SUBJEC7:

CRYSTAL RIVER UNIT NO. 3, DOCKET NO. 50-302 - EVALUATION OF VITON-A SEAL MATERIAL FOR REACTOR COOLANT PUMP SNUBBERS The Engineering Branch, Operational Technology, Division of Operating Reactors has reviewed Florida Power Corporation's request for approval of Viton-A seal material for the reactor coolant pump snubbers at the Crystal River Unit No. 3 Nuclear Power Plant. We recommend that Viton-A be approved for use, and the Crystal River Unit No. 3 Technical Specification 4.7.9.l(b) be amended to exclude the reactor coolant pump snubbers. Our evaluation is attached.

f3

/

!,/ N

  • D. G. Eisenhut, Assistan( Director for Operational Technology Division of Operating Reactors

Enclosure:

As stated cc:

D. Vassallo V. Stello R. Bosnak J. Stolz L. Engle S. Pawlicki L. Shao W. Hazelton R. Stuart V. Noonan F. Almeter 80 03160 25Y [

h' CRYSTAL RIVER UNIT NO. 3 NUCLEAR POWER PLANT DOCKET NUMBER 50-302 EVALUATION OF VITON-A SEAL MATERIAL FOR REACTOR COOLANT PUMP SNUDBERS

Background

The Crystal P.iver Unit No. 3 Technical Specification 4.7.9.l(b) specifies ethylene propylene as a seal material for hydraulic snubbers.

Snubber seal material not fabricated from ethylene propylene requires a visual inspection at least once per 31 days unless approved as such by the NRC.

The reactor coolant pump snubbers at Crystal River Unit No. 3 contain seals made of Viton-A material. The Florida Power Corporation has requested NRC's approval to use this material until the snubber seals can be replaced with ethylene propylene.

The operating environment in the area of the snubber installation is 5

150 F to 170 F at a radiation level of approximately 2.63 X 10 rads per year. The hydraulic fluid in the reactor coolant pump snubbers is Versilube F-50 Silicone lubricant.

Evaluation The fluorocarbon elastomer, Viton-A, material is stable at temperatures in the range of -20 F to +400 F.

The gama radiation stability of 6

Viton-A is relatively good up to approximately 4.5 X 10 rads at 212*F.

7 At 10 rads, Viton-A has a 66.7% deterioration in compression set, a 32% loss in elongation, and a 1% increase in hardness. These property changes relate to ambient temperature tests after radiation exposure at 96 F to 112 F in an inert atmosphere. However, Viton-A does not degrade as rapidly when immersed in silicone fluids.

Conclusion We consider the Viton-A seal material is acceptable for use in the operating environment of the reactor coolant pump snubbers at Crystal River Unit No. 3.

The material should maintain its integrity during the first 10 years of 9*'--e

E

~

. service life. Viton-A may have a useful service life for 20 years in the operating environment of the reactor coolant pump snubbers at Crystal River Unit No. 3.

We believe there is no significant safety hazard with the Viton-A seal material application in the reactor coolant pump snubbers at Crystal River Unit No. 3. Technical Specification 4.7.9.l(b) could be ammended to exclude the reactor coolant pump snubbers.

.,n,

.